3.2.6.2. Ø 100/60 mm and Ø 125/80 mm air/flue gas coaxial duct system
The above data are referred to air intake/flue gas exhaust systems which are implemented by means of smooth, rigid manu-
facturer approved and supplied pipes.
Type C13
KC 24, KR 24 and KRB 24
Minimum permissible length of horizontal coaxial pipes is 1 meter,
without accounting for the first elbow connected to the boiler.
Maximum permissible length of Ø 100/60 mm horizontal coaxial pipes
is 9.5 meter not including the first elbow connected to the boiler.
Maximum permissible length of Ø 125/80 mm horizontal coaxial pipes
is 14.5 meter not including the first elbow connected to the boiler.
For each additional 1 meter straight pipe maximum permissible length
is to be reduced by 1 meter.
For each additional 90° elbow, maximum permissible length is to be
reduced by 1 meter.
For each additional 45° elbow, maximum permissible length is to be
reduced by 0.5 meter.
The wall terminal reduces maximum permissible length by 1.5 meters.
The air intake duct is to be tilted by 1% toward its exit, in order to avoid
rain water to enter it.
KC 28, KR 28 and 28
Minimum permissible length of horizontal coaxial pipes is 1 meter,
without accounting for the first elbow connected to the boiler.
Maximum permissible length of Ø 100/60 mm horizontal coaxial pipes
is 7.5 meter not including the first elbow connected to the boiler.
Maximum permissible length of Ø 125/80 mm horizontal coaxial pipes
is 11 meter not including the first elbow connected to the boiler.
For each additional 1 meter straight pipe maximum permissible length
is to be reduced by 1 meter.
For each additional 90° elbow, maximum permissible length is to be
reduced by 1 meter.
For each additional 45° elbow, maximum permissible length is to be
reduced by 0.5 meter.
The wall terminal reduces maximum permissible length by 1.5 meters.
The air intake duct is to be tilted by 1% toward its exit, in order to avoid
rain water to enter it.
KC 32, KR 32 and KRB 32
Minimum permissible length of horizontal coaxial pipes is 1 meter,
without accounting for the first elbow connected to the boiler.
Maximum permissible length of Ø 100/60 mm horizontal coaxial pipes
is 6.5 meter not including the first elbow connected to the boiler.
Maximum permissible length of Ø 125/80 mm horizontal coaxial pipes
is 11.5 meter not including the first elbow connected to the boiler.
For each additional 1 meter of straight pipe maximum permissible
length is to be reduced by 1 meter.
For each additional 90° elbow, maximum permissible length is to be
reduced by 1 meter.
For each additional 45° elbow, maximum permissible length is to be
reduced by 0.5 meter.
The wall terminal reduces maximum permissible length by 1.5 meters.
The air intake duct is to be tilted by 1% toward its exit, in order to avoid
rain water to enter it.
Type C33
KC 24, KR 24 and KRB 24
Minimum permissible length of vertical coaxial pipes is 1 meter.
Maximum permissible length of Ø 100/60 mm vertical coaxial pipes is
9.5 meters.
Maximum permissible length of Ø 125/80 mm vertical coaxial pipes is
14.5 meters.
For each additional 1 meter of straight pipe maximum permissible
length is to be reduced by 1 meter.
For each additional 90° elbow, maximum permissible length is to be
reduced by 1 meter.
For each additional 45° elbow, maximum permissible length is to be
reduced by 0.5 meter.
The roof terminal reduces maximum permissible length by 1.5 meters.
KC 28, KR 28 and KRB 28
Minimum permissible length of vertical coaxial pipes is 1 meter.
Maximum permissible length of Ø 100/60 mm vertical coaxial pipes is
7.5 meters.
Maximum permissible length of Ø 125/80 mm vertical coaxial pipes is
11 meters.
For each additional 1 meter of straight pipe maximum permissible
length is to be reduced by 1 meter.
For each additional 90° elbow, maximum permissible length is to be
reduced by 1 meter.
For each additional 45° elbow, maximum permissible length is to be
reduced by 0.5 meter.
The roof terminal reduces maximum permissible length by 1.5 meters.
KC 32, KR 32 and KRB 32
Minimum permissible length of vertical coaxial pipes is 1 meter.
Maximum permissible length of Ø 100/60 mm vertical coaxial pipes is
6.5 meters.
Maximum permissible length of Ø 125/80 mm vertical coaxial pipes is
11.5 meters.
For each additional 1 meter of straight pipe maximum permissible
length is to be reduced by 1 meter.
For each additional 90° elbow, maximum permissible length is to be
reduced by 1 meter.
For each additional 45° elbow, maximum permissible length is to be
reduced by 0.5 meter.
The roof terminal reduces maximum permissible length by 1.5 meters.
fig. 13
Sealing
cap
Gasket
fig. 14