Malfunctions, possible causes and solutions
BOILER STATUS
MALFUNCTION
PROBABLE CAUSE
USER'S TASKS
QUALIFIED PERSONNEL'S
TASKS
E12**
Water heater probe fault (KR/
KRB with external water heater,
optional and NTC probe,
optional for Kr, standard for
KRB).
Probe is disconnected.
Contact qualified personnel
Reconnect it.
Probe is faulty.
Contact qualified personnel
Replace it.
E15**
Return probe failure.
Probe is disconnected.
Contact qualified personnel
Reconnect it.
Probe is faulty.
Contact qualified personnel
Replace it.
E23**
External probe fault (only with
connected external probe).
Probe is disconnected.
Contact qualified personnel
Reconnect it.
Probe is faulty.
Contact qualified personnel
Replace it.
E31**
Remote Control connection
failure (only shown on Remote
Control display).
The Remote Control is not
connected to boiler board.
Contact qualified personnel
Reconnect it.
Remote control faulty.
Contact qualified personnel
Replace it.
Boiler board is faulty.
Contact qualified personnel
Replace it.
E40*
Fan failure.
Fan disconnected.
Contact qualified personnel
Reconnect it.
Fan faulty.
Contact qualified personnel
Replace it.
E44**
Ambient probe fault (only with
connected ambient probe).
Probe is disconnected.
Contact qualified personnel
Reconnect it.
Probe is faulty.
Contact qualified personnel
Replace it.
E70*
Problems with the air flow rate.
Possible clogging on flue gas
side of the heat exchanger.
Heat exchanger is clogged on
the flue gas side.
Contact qualified personnel
Check the heat exchanger.
E77
Problems in the electronic
board power supply.
Power mains not stable.
Contact qualified personnel
Check the power mains.
E78*
Flow temperature increases
too quickly.
Pump is seized.
Contact qualified personnel
Unseize the pump.
Pump is faulty.
Contact qualified personnel
Replace it.
Air present inside heating
system.
Contact qualified personnel
Bleed the air from the boiler
by opening the jollies on the
exchanger and pump.
E80*
The ∆T between flow and
return is not within the limits.
Flow and/or return probes are
faulty.
Contact qualified personnel
Replace them.
Obstructed bypass pipe
Contact qualified personnel
Remove any obstructions, or
replace the pipe.
The bypass valve is not
assembled or wrongly
assembled.
Contact qualified personnel
Restore bypass valve correct
assembling.
Heat exchanger primary circuit
is obstructed.
Contact qualified personnel
Clean or replace the exchanger.
E81*
The water circulation is the
boiler is not correct.
System pressure too low.
Contact qualified personnel
Check the system.
Water does not circulate
correctly in the system.
Contact qualified personnel
Check the system.