Instructions for the installer
Parameter
Settable values
Default values
Notes
P34
PWM circulation pump control
0 ÷ 1
1
With P34 = 0: PWM=100% pump stopped and
PWM=0% pump at maximum operation.
With P34 = 1: PWM=100% pump at maximum
operation and PWM=0% pump stopped.
P35
Setting of default parameters (except P0, P1,
P2, P3)
0 ÷ 1
0
0 = user parameters; 1 = default parameters
P36
Display of reset shut-down and fault
0 ÷ 1
n.a.
0 = OFF; 1 = shut-downs and faults reset
P37
Post-ventilation timer
0 ÷ 60 sec.
10 sec.
-
P38
Water heater flow temperature
0 ÷ 50 °C
0 °C
With P38 = 0: automatic modulating water
heater flow temperature.
With P38 > 0: water heater flow temperature =
P38 + water heater set-point.
P39
heating temperature minimum limit for
STANDARD range
20 ÷ 59 °C
20 °C
-
P40
heating temperature maximum limit for
STANDARD range
60 ÷ 78 °C
78 °C
-
P41
heating temperature minimum limit for
REDUCED range
20 ÷ 30 °C
20 °C
-
P42
heating temperature maximum limit for
REDUCED range
31 ÷ 45 °C
45 °C
-
P43
Ambient or external temperature
-
-
only with connected ambient or external probe
P44
Flow temperature
-
-
-
P45
Nominal calculated flow temperature
-
-
only with connected ambient or external probe
P46
DHW temperature
-
-
-
P47
Boiler return temperature
-
-
-
P48
Flue gas temperature
-
-
-
P49
Display of boiler type
-
-
xyz
x= P0 value
y = P2 value
z = P3 value
Tab. 10 Limits to be set for TSP parameters and default values in relation to boiler type (TSP0) - III