Malfunctions, possible causes and solutions
BOILER STATUS
MALFUNCTION
PROBABLE CAUSE
USER'S TASKS
QUALIFIED PERSONNEL'S
TASKS
E09
System pressure is too close to
the max. limit.
During manual illing, a system
pressure too close to the safety
valve drain value has been
restored.
Contact qualiied personnel
Progressively drain the
system until the error symbol
disappears.
E12**
Boiler water heater probe
failure (top part).
Probe is disconnected.
Contact qualiied personnel
Reconnect it.
Probe is faulty.
Contact qualiied personnel
Replace it.
E15**
Return probe failure.
Probe is disconnected.
Contact qualiied personnel
Reconnect it.
Probe is faulty.
Contact qualiied personnel
Replace it.
E24**
Solar collector failure.
Probe is disconnected.
Contact qualiied personnel
Reconnect it.
Probe is faulty.
Contact qualiied personnel
Replace it.
E27**
Solar valve probe (standard in
M versions) failure.
Probe is disconnected.
Contact qualiied personnel
Reconnect it.
Probe is faulty.
Contact qualiied personnel
Replace it.
E28**
Solar water heater probe
failure (low part).
Probe is disconnected.
Contact qualiied personnel
Reconnect it.
Probe is faulty.
Contact qualiied personnel
Replace it.
E31**
Remote Control connection
failure (only shown on Remote
Control display).
The Remote Control is not
connected to boiler board.
Contact qualiied personnel
Reconnect it.
Remote control faulty.
Contact qualiied personnel
Replace it.
Boiler board is faulty.
Contact qualiied personnel
Replace it.
E35**
Safety thermostat triggering to
protect the mixed "zone 2" (on
versions V, MV, Z and MZ only).
Mixer valve is faulty.
Contact qualiied personnel
Replace it.
Thermostat is disconnected.
Contact qualiied personnel
Reconnect it.
Thermostat is faulty
Contact qualiied personnel
Replace it.
E36**
Flow probe fault in one of the
installed zones (with indication
of the zone number).
Probe is disconnected.
Contact qualiied personnel
Reconnect it.
Probe is faulty.
Contact qualiied personnel
Replace it.
E40*
Fan failure.
Fan disconnected.
Contact qualiied personnel
Reconnect it.
Fan faulty.
Contact qualiied personnel
Replace it.
E41**
No communication between
board and peripheral devices
(panel interface and/or zone/
solar boards).
Interface display is
disconnected.
Contact qualiied personnel
Reconnect it.
Zone/solar boards are
disconnected.
Contact qualiied personnel
Reconnect them.
Interface display and/or zone/
solar boards are faulty.
Contact qualiied personnel
Replace them.