61
Instructions for the installer
Parameter
Settable values
Default values
Notes
P59
Type of temperature visualization on display
0 ÷ 7
0
0 = low temp.; 1 = SA1 probe temp.; 2 = SA2
probe temp.; 3 = external temp.; 4 = water
heater temp.; 5 = solar coll. temp.; 6 = solar
valve temp.; 7 = solar valve temp from solar
board
P60
Number of additional boards connected
0 ÷ 4
According to the
model
Maximum 4 boards (3 zone + 1 solar)
P61
Association of remote control, thermostat
and ambient probe for the control of zone 1
and zone 2
00 ÷ 07
00
00 = remote zone 2 / TA2 zone 1; 01 =
TA1 zone 2 / TA2 zone 1; 02 = TA2 zone
2 / remote zone 1; 03 = SA1 zone 1 / TA2
zone 2; 04 = SA1 zone 1 / SA2 zone 2; 05 =
remote zone 1 / SA2 zone 2; 06 = zone 1 not
managed / SA2 zone 2; 07 = TA1 zone 1 /
SA2 zone 2.
P62
Selection of zone 2 curve
0 ÷ 3
0.6
V, Z, MV and MZ versions
P63
Zone 2 set-point (ictitious temp.)
15 ÷ 35 °C
20 °C
V, Z, MV and MZ versions
P66
Selection of zone 3 curve
0 ÷ 3
0.6
Z and MZ versions
P67
Zone 3 set-point (ictitious temp.)
15 ÷ 35 °C
20 °C
Z and MZ versions
P70
Selection of zone 4 curve
0 ÷ 3
0.6
not used
P71
Zone 4 set-point (ictitious temp.)
15 ÷ 35 °C
20 °C
not used
P74
Low temperature zone mixer valve opening
time
0 ÷ 300 sec.
140 sec.
V, Z, MV and MZ versions
P75
Rise in nominal boiler temperature with
zone board
0 ÷ 35 °C
5 °C
V, Z, MV and MZ versions
P76
Thermal discharge enabling with solar board
0 ÷ 1
0
1 (M, MV and MZ
versions)
0 = disabled; 1 = enabled
P78
Interface back-lighting switching on
0 ÷ 2
0
0 = standard; 1 = LCD always on 2 = LCD and
keys always on
From P80 to P92 see "System check"
Tab. 19 List of parameters - III