38
4. Testing the boiler
Each boiler comes with a test certificate that must be completed when testing the boiler in order to benefit of the warranty.
4.1. Preliminary checks
Before testing the boiler, it is advisable to check that
• the installation complies with the current regulations;
• the flue gas exhaust pipe and terminal are installed as instructed. When the boiler is running, no combustion gas must leak from any of
the seals;
• the power supply to the boiler is 230 V – 50 Hz;
• the system is full of water and the pressure reading is 1-1.3 bar);
• any system pipe stopcocks are open;
• the gas supplied to the boiler corresponds to the setting; iIf necessary, the boiler must be converted according to the instructions in §
3.6 – Adapting to other gases. This operation must be carried out by a qualified service engineer;
• the gas cock is open;
• there are no gas leaks;
• the master switch is on;
• the boiler safety valve is not blocked.
• the condensate trap installed in the boiler is discharging condensate correctly and is not stuck.
If the boiler is not installed in accordance with the applicable rules and regulations, inform the system supervisor and do not test the
boiler.
If the boiler is not installed in accordance with the applicable rules and regulations, inform the system supervisor and
do not test the boiler.
4.2. Switching the boiler on and off
Refer to the User Instructions for details of how to switch the boiler on and off.
Содержание KR 55
Страница 1: ...IST 03 C 000 01 INSTALLATION USE AND MAINTENANCE TAHITI CONDENSING KR 55 KR 85 GB...
Страница 22: ...22 KR KR KR KR KR KR 0DIMACAR12 fig 12 Coupling Coupling M Flow 1 G Gas 3 4 F Cold water 1 2 R Return 1...
Страница 34: ...34 fig 21 A 3 5 Wiring diagram 55 KW...
Страница 35: ...35 fig 21 B 85 KW...
Страница 42: ...42...
Страница 43: ...43...