400A/W 220 V 60 Hz/230 V/50 Hz Ice Machines
RIDE model ice machine ventilation and exhaust requirements
Fabricator-supplied, custom air intake grilles must have 305mm x 305mm (12" x 12") opening yielding 645 sq. cm (100
sq. inches) of open air space within duct perimeter. Block off any open area outside of the air duct.
Intake air requirements — air-cooled ice machines (MCC400A & C/ER400A only)
1. Check that 51mm (2") duct is installed on condenser front.
2. Cut a 305mm x 305mm (12" x 12") opening in counter face to align with duct.
3. Position ice machine to mate duct fl ush with back of counter opening.
4. Install supplied grille on outside of counter opening.
Exhaust air — all ice machines (MCC400A/W & C/ER400A/W)
Provide 645 sq. cm. (100 sq. in) of counter opening for exhaust air at least 457mm (18") from intake opening but not
more than 3m (10 ft) away.
Provide at least 645 sq. cm
(100 sq. inches) of counter opening
for exhaust air
Air out through louver
Exhaust air out
side to opening at
least 457mm (18" )
from air intake
Standard 51mm (2") duct
mates counter opening
(behind grille) to condenser
front
Air in
through louver
Supplied 2" (51mm) duct MUST be installed
to front of ice machine and mated flush to
inside of counter face opening.
Standard
louvered grille
(supplied)
Air intake
Exhaust air
MCC400A & C/ER400A — Side view
Front view