RTM x42.IO.Modbus Installation Manual and Operating Instructions
03.02.2020
23
6.4
List of channel 1 to 10 and core parameters
Channel and Core Parameters
Parameter Description
Offset
Compensation of pulley weight
Unit
[Digit]
Min.
–9999
Max.
9999
Default 0
Gain Gain
factor
Unit
[-]
Min.
0.001
Max.
20.000
Default 1.000
F_Nenn
Nominal force of the sensor
Unit [N]
Min.
0.001
Max.
99’999
Default
1000
F@OutMax
Scaling oft he maxium force oft he bar graph.
Unit
[N]
Min.
0.001
Max.
99’999
Default
1000
FiltMode Filter
characteristic of output filter. Prevents noise overlaying the output
signal. Unit
[-]
Values
N-Linear, Lowpass, Bypass,
Default N-Linear
Filt_Out
Cut off frequency of filter
Unit
[Hz]
Min.
0.1
Max.
100.0
Default 10.0
Out_Mode
Mode selection for current output