background image

RTM x42.IO.Modbus Installation Manual and Operating Instructions

 

 

03.02.2020

 

 

17 

 
 

13 to 16 

Additional, optional LED bars for max. of 10 channels, depending on 
system size. 

Table 4: Receiver module operation and display 

5.1

 

Offset Compensation of the Force Sensors 

Offset compensation is used to compensate for the weight of the pulley on the force 
sensor. The measuring system is practically “zeroed.” 
Observe the following:  
-

 

The force sensor may only be loaded with the pulley (no wire on the pulley) 

-

 

Rotate the lay-plate until the desired force sensor, for which the offset compensation 

is performed, is vertically over the axis of rotation (12 o’clock position)  

 

Figure 11: Lay-plate alignment  

RTM_X42_Modbus_BA_Manual.ai 

 
-

 

Press and hold the button >0< for min. 3 sec. 

-

 

Force sensor number is displayed  

-

 

Select the desired number by pressing the navigation buttons 

-

 

Press confirmation button to select the desired channel 

-

 

The display shows "Offset running" and "Offset complete" 

-

 

The calculated offset value is stored automatically 

-

 

For other channels, repeat the steps 

Press 

 to return to the main menu 

 

 

Please note 
The offset compensation must be carried out individually for each 
channel on the 12 clock position of the base plate. 

 
 
The offset compensation of the force sensor for the core strand can either be done via 
the measuring amplifier connected to this force sensor or the EMGZ482R. If you do it 

Содержание RTM IO

Страница 1: ...Cage and Tubular Stranders with analogue outputs up to 10 channels Document version 3 60 Published author 01 2020 NS Diese Bedienungsanleitung ist auch in Deutsch erh ltlich Bitte kontaktieren Sie Ih...

Страница 2: ...Receiver Module with battery 9 4 4 1 EMGZ482T 24VDC Receiver Module version without battery with 24VDC power supply via slip rings on the strander 10 4 5 EMGZ484T Channel Extension Module 12 4 5 1 EM...

Страница 3: ...y Information 2 1 1 Danger that Could Result in Minor or Moderate Injuries Danger warning caution Type of danger and its source Possible consequences of nonobservance Measure for danger prevention 2 1...

Страница 4: ...the components in the specified layout to one another Otherwise severe malfunctions may occur Thus the installation information on the following pages must be followed The local installation regulati...

Страница 5: ...s also straightforward Reliable radio transmission of the data and optional battery packs make slip rings obsolete The typical RTM X42 IO system can handle the measurement of up to 10 individual wires...

Страница 6: ...arger channel extension module s receiver module s pre fabricated connection cables force sensor to channel extension module and or to receiver module pre fabricated connection cables of the channel e...

Страница 7: ...Machine In rotating applications the force sensors are installed such that the centrifugal forces are compensated Note It is of utmost importance to compensate for the centrifugal forces generated th...

Страница 8: ...may have to be readjusted very precisely Some FMS force sensors feature an integrated mechanism facilitating this fine adjustment For force sensors without such features we recommend the use of shims...

Страница 9: ...ual and Operating Instructions 03 02 2020 9 Abbildung 4 Installation RTM_X42_Modbus_BA_Manual ai 4 4 Electrical Connection 4 4 1 EMGZ482T Receiver Module with battery The connection cables are pre fab...

Страница 10: ...ai 4 4 1 EMGZ482T 24VDC Receiver Module version without battery with 24VDC power supply via slip rings on the strander The connections between the force measuring rollers and transmitter are realized...

Страница 11: ...RTM x42 IO Modbus Installation Manual and Operating Instructions 03 02 2020 11 Figure 6 EMGZ482T 24VDC electrical connection RTM_X42_Modbus_BA_Manual ai...

Страница 12: ...annel Extension Module Figure 7 EMGZ484T electrical connection RTM_X42_Modbus_BA_Manual ai Bus Termination Plug All Bus Power Socket have to be connected Otherwise errors in communcaiton may occure Al...

Страница 13: ...l connection RTM_X42_IO_BA_Manual ai EMGZ482R pin assignment Pin s Description 1 24 VDC 2 24 VDC 3 PE 10 11 24 VDC output 12 GND for 24 VDC 13 Digital input for production length 14 Analog input for f...

Страница 14: ...on battery state of charge core tension value 19 29 Relay 4 1 4 2 Table 2 EMGZ482R pin assignment The RTM X42 system has pre configured relay outputs The respective alarm output is activated if the as...

Страница 15: ...15 1 bis 3 Output 0 to 10 VDC 0 4 to 20 mA 4 bis 6 Output 0 to 10 VDC 0 4 to 20 mA 7 19 Relay 1 1 1 2 8 20 Relay 2 1 2 2 9 21 Relay 3 1 3 2 10 22 Relay 4 1 4 2 13 bis 15 Output 0 to 10 VDC 0 4 to 20 m...

Страница 16: ...set compensation 3 Cal Calibration 4 Para access to parameter menu 5 Main operating field with Navigation button scroll within a menu Change button change values up or down Confirmation button confirm...

Страница 17: ...is vertically over the axis of rotation 12 o clock position Figure 11 Lay plate alignment RTM_X42_Modbus_BA_Manual ai Press and hold the button 0 for min 3 sec Force sensor number is displayed Select...

Страница 18: ...defined weight attached to its end The cable must correspond to the real material course in the machine wrap angle distances between the rollers etc The displayed determined digit value must now be a...

Страница 19: ...t_Akku_10Ah_01 png Connect battery to charger The state of charge LED lights up red if the battery is discharged The safety circuit protects the batteries from overcharging Charging is finished as so...

Страница 20: ...ule e g shows RTM X42 V 3 60 This describes the currently loaded firmware The RTM X42 system is now ready and can be configured 6 2 Menu and navigation All configuratable paramters are defined in mult...

Страница 21: ...ly via web browser Only limited configuration via operating panel parameters LANspeed Gateway IP Adres Supnet RL CTRL Unit Values RTM X42 PC Default RTM X42 FiltMode Off Deactivated N Linear Non linea...

Страница 22: ...eway Gateway IP address static Is entered in 4 blocks Unit Min 0 Max 255 Default 192 168 000 100 RM unit Unit of production length Unit Values m ft Default m RMpulses Pulses per rotation of the capsta...

Страница 23: ...it Min 0 001 Max 20 000 Default 1 000 F_Nenn Nominal force of the sensor Unit N Min 0 001 Max 99 999 Default 1000 F OutMax Scaling oft he maxium force oft he bar graph Unit N Min 0 001 Max 99 999 Defa...

Страница 24: ...AlarmMin Lower threshold Unit N Min 99 999 Max 99 999 Default 0 AlarmMax Upper threshold Unit N Min 99 999 Max 99 999 Default 0 AlarmT Alarm pending time Unit s Min 0 0 Max 600 0 Active Activate chan...

Страница 25: ...iolation of core threshold SumPreA collective violation of one pre alarm thresholds SumAlarm collective violation of one threshold Radio ok bad radio signal quality Batt ok violation of minimum batter...

Страница 26: ...t must be certain that the receiver uses an IP address in a static block not assigned by the server For the integration of EMGZ482R in your Ethernet network please contact your IT system administrator...

Страница 27: ...RTM x42 IO Modbus Installation Manual and Operating Instructions 03 02 2020 27 Figure 16 current reading...

Страница 28: ...us Installation Manual and Operating Instructions 03 02 2020 28 Figure 17 parameters channel and core Select the channels from the dropdown menu Always store you changes with Safe changes Figure 18 et...

Страница 29: ...RTM x42 IO Modbus Installation Manual and Operating Instructions 03 02 2020 29 Figure 19 system parameters Figure 20 relay parameters...

Страница 30: ...RTM x42 IO Modbus Installation Manual and Operating Instructions 03 02 2020 30 Figure 21 default settings...

Страница 31: ...RTM x42 IO Modbus Installation Manual and Operating Instructions 03 02 2020 31 8 Dimensions Figure 22 Dimensions of the EMGZ482R receiver module Figure 23 Dimensions of the EMGZ482T transmitter module...

Страница 32: ...RTM x42 IO Modbus Installation Manual and Operating Instructions 03 02 2020 32 Figure 24 Dimensions of the EMGZ484T channel extension module...

Страница 33: ...olution 8192 digit 14 bit Analog inputs 1 and 2 1 strain gauge force sensor 350 0 to 5 4 mV max 7 4 mV Temperature range 0 to 50 C 32 to 122 F Protection class IP52 Weight 0 52 kg 1 15 lbs without bat...

Страница 34: ...0 05 FS Sensor excitation 3 0 VDC max 20mA highly stable Power supply 24 VDC supply via bus power cable from EMGZ482T MODBUS A D converter resolution 8192 digit 14 bit Analog inputs 1 to 4 1 strain g...

Страница 35: ...FCC Rules Certification FCC Registration 0020311882 RTM X42 CAB Radio Certification for Japan Magnitude of Test Coverage Low power data communi FXD Art 38 24 Paragraph 1 of radio law Certification Art...

Страница 36: ...850 60 06 info fms technology com www fms technology com FMS USA Inc 2155 Stonington Avenue Suite 119 Hoffman Estates IL 60169 USA Tel 1 847 519 4400 Fax 1 847 519 4401 fmsusa fms technology com FMS U...

Отзывы: