PROFIBUS Interface
10.1
Wiring of the PROFIBUS Data Cable
Wiring of the PROFIBUS cables
The standardized PROFIBUS cable type A (STP 2x0.34
2
) [AWG] has to be used for
the PROFIBUS data cable. The cables are bared referring to fig. 6 and connected
to the terminals according to the wiring diagramm.
The shield is connected with the bracket to the shoulder inside the housing.
Caution
The shield of the PROFIBUS cable is only grounded if the bracket inside the
housing clamps directly to the shield. If the clamps to the plastic mantle, no
grounding is done! Therefore the plastic mantle has to be fixed only with the PG
gland (referring to fig. 6)
Termination
If both cables are connected (Bus in and Bus out), if has to be ensured that the
two termination dip switches are in off position.
If only one cable is connected (Bus in), both termination dip switches have to be
set in on position.
fig. 29: Profibus board
E621009 fig. 30: connection Profibus
B600030e
Note
The PROFIBUS network has to be terminated properly. Otherwise the installation
cannot be set into operation. It has to be ensured that only the last device of the
PROFIBUS chain is terminated.
Содержание BMGZ 610A
Страница 6: ...Operating manual BMGZ 600A 6 components in italic letters are option...
Страница 16: ...Operating manual BMGZ 600A 16 Repeat the procedure for the 2nd side disk...
Страница 18: ...Operating manual BMGZ 600A 18 8 Replace the earth cable and all the cables with connectors back to place...
Страница 20: ...Operating manual BMGZ 600A 20 6 6 Wiring Information fig 16 Terminal arrangement on terminal board B600007...
Страница 45: ...Operating manual BMGZ 600A 45 fig 31 Flat measuring roller B400013e...