FiReplace installatiOn

FRAMING

1.  Frame  opening  for  fireplace  using  the 

dimensions shown in Figures 1 and 2.

2.  If  fireplace  is  to  be  installed  directly  on 

carpeting, tile (other than ceramic) or any 

combustible  material  other  than  wood 

flooring,  the  fireplace  must  be  installed 

upon  a  metal  or  wood  panel  extending 

the full width and depth of fireplace.

3.  Set fireplace directly in front of this open

-

ing and slide unit back until nailing flanges 

touch side framing.

4.  Check the level of the fireplace and shim 

with sheet metal if necessary.

5.  Before  securing  fireplace  to  prepared 

framing, the ember protector (provided) 

must be placed between the hearth ex

-

tension (not supplied) and under bottom 

front edge of fireplace to protect against 

glowing embers falling through. If fireplace 

is to be installed on a raised platform, a Z-

type ember protector (not supplied) must 

be fabricated to fit your required platform 

height. The  ember  protector  should  ex

-

tend under fireplace a minimum of 1 

1

/

2

". 

The ember protector should be made of 

galvanized sheet metal (28 gauge mini

-

mum) to prevent corrosion.

6.  Using screws or nails, secure fireplace to 

framing through flanges located on sides 

of fireplace.

21.875"

41.375"

41.250"

Figure 1 - Framing Dimensions

52.183"

17.253"

24.399"

73.798"

MAINTAIN 

3

/

4

"

CLEARANCE AT

SIDES AND BACK

OF FIREPLACE

3

/

4

" CLEARANCE

NOT REQUIRED AT

NAILING FLANGES  

Figure 2 - Corner Installation

SELECTING LOCATION

To  determine  the  safest  and  most  efficient 

location for the fireplace, you must take into 

consideration the following guidelines:
1.  The location must allow for proper clear

-

ances (see Figures 1 and 2).

2.  Consider a location where the fireplace 

will not be affected by drafts, air condition

-

ing ducts, windows or doors.

3.  A  location  that  avoids  the  cutting  of 

joists or roof rafters will make installation 

easier.

4.  An  outside  air  kit  is  available  with  this 

fireplace (see 

Optional Outside Air Kit

 on 

page 6).

MINIMUM CLEARANCE TO 

COMBUSTIBLES

Back and sides of fireplace  3/4" minimum*
Floor** 

0" minimum

Perpendicular wall to opening  12" minimum
Top spacers 

0" minimum

Mantel clearances 

see 

Mantels

, page 5

Chimney outer pipe surface 

1" minimum

* Not required at nailing flanges
** See step 2 of 

Framing

 WARNING: Do not pack re-

quired air spaces with insulation 

or other materials.

Minimum/Maximum Chimney Height for 

Residential Installation

The  minimum  height  of  the  chimney,  mea

-

sured from the base of the fireplace to the flue 

gas outlet of the termination, is 14.5 feet for 

straight flue or a flue with one elbow set. The 

maximum distance between elbows is 6 feet. 

For systems with two elbow sets, the minimum 

height is 22 feet. The maximum height of any 

system is 50 feet. This measurement includes 

the fireplace, chimney sections and the height 

of the termination assembly at the level of the 

flue gas outlet (see Figure 18, page 11).

Minimum/Maximum Chimney Height for 

Outdoor Installation

The  minimum  height  of  the  chimney,  mea

-

sured from the base of the fireplace  to the 

flue gas outlet of the termination, is 7 

1

/

2

 feet 

(minimum of 4 feet of chimney pipe sections 

required for outdoor installation).

Содержание (V)S36 Series

Страница 1: ...e gas log heater approved toANS Z21 11 2 standard AFMI PRODUCTS LLC hood must be installed when using a vent free log heater see Accessories page 16 This wood burning fireplace complies with UL127 CAN ULS S610 M87 standard as a FACTORY BUILT APPLIANCE FOR CANADA The authority having jurisdiction such as the municipal building department fire department etc should be contacted before installation t...

Страница 2: ...erty damage or loss of life Refer to this manual for assistance or additional information Consultaqualifiedinstall er or local distributor IMPORTANT Check local codes before installing this fireplace Before beginning installation of this fireplace read these instructions through completely This FMI PRODUCTS LLC fireplace and its components are safe when installed according to this installation man...

Страница 3: ...NOT LESS THAN 12 1 AIRSPACE TO COMBUSTIBLE COMBUSTIBLE WALL BOARD 0 TO MATERIAL NO COMBUSTIBLE MATERIAL ON FACE SIDEWALL TERMINATION SQUARE CHASE TOP GAS LINE KNOCK OUT AIR KIT KNOCK OUTS ROUND TOP TERMINATION GAS LINE KNOCK OUTS ELECTRICAL OUTLET LEFT SIDE RIGHT SIDE 8 125 10 435 14 437 41 25 37 41 35 21 8 32 5 14 25 22 2 5 8 717 1 11 217 2 5 8 125 7 092 8 717 12 5 41 1 0 625 29 21 ...

Страница 4: ...the safest and most efficient location for the fireplace you must take into consideration the following guidelines 1 The location must allow for proper clear ances see Figures 1 and 2 2 Consider a location where the fireplace will not be affected by drafts air condition ing ducts windows or doors 3 A location that avoids the cutting of joists or roof rafters will make installation easier 4 An outs...

Страница 5: ...o prevent the hearth extension from shifting and seal gap between the fireplace frame and hearth extension with a noncom bustible material see Figure 3 Fireplace Installation Continued Figure 3 Hearth Extension Seal Gap Fireplace Front Ember Protector Fireplace Front Raised Hearth Fireplace Front Elevated Ember Protector Ember Protector Seal Gap Hearth Extension WARNING Hearthextension is to be in...

Страница 6: ...e Check Local Codes Before Installing in a Vented Crawl Space Chimney Pipe The FMI PRODUCTS LLC chimney system consists of 12 18 24 36 and 48 snap lock double wall pipe segments planned for maximum adaptability to individual site requirements Actual lengths gained after fit ting overlaps must be taken into consideration lineal gain and are given in the lineal gain chart see Figure 6 Lineal gain is...

Страница 7: ...double wall pipe see offset chart and Figure 7 2 Chimney weight above offset rests on return elbow Straps must be securely nailed to rafters or joists see Figure 8 details A and B on page 8 3 Maximum length of pipe between supports return elbow or 12S 8DM is 6 of angle run Maximum of two 6 angle run sections per chimney system see Figure 7 4 All pipe connections between offset and return must be s...

Страница 8: ... of 8 Firestop Spacer Screws or Staples Min of 8 Penetrating roof To maintain a 1 clearance to the pipe on a roof with a pitch a rectangular opening must be cut 1 Determine center point through which pipe will penetrate roof 2 Determine center point of roof Pitch is the distance the roof drops over a given span usually 12 A 6 12 pitch means that the roof drops 6 for each 12 one measure horizontall...

Страница 9: ... Flashing Cone Underlap Shingles at Bottom Overlap Shingles Top and Sides Only Figure 13 Flashing Installation Storm Collar Installation SC1 or SC2 Place storm collar over pipe and slide down until it is snug against the open edge of the flashing see Figure 14 Use SC1 for all round terminations and SC2 for all terminations with slip sections Apply waterproof caulk around the perimeter of the colla...

Страница 10: ...e 16 Note If a decorative shroud is to be installed contact the manufacturer for specifications 10 foot rule All flue gas outlet chimney terminations must extend a minimum of 3 feet in height above the highest point where it passes through the roof and must be at least 2 feet above the high est point of the roof that is within a horizontal distance of 10 feet see Figure 17 24 Min 24 Min 18 Min Typ...

Страница 11: ...T MAX HEIGHT 14 5 FT MIN HEIGHT OF 22 FT WITH 2 ELBOW SETS MAX HEIGHT OF 50 FT MAX HEIGHT 50 FT ANY SYSTEM 30E 8DM Figure 18 Typical Residential Installations Gas line hook up should be done by your supplier or a qualified service person Note Before you proceed make sure your gas supply is turned off Use only a 1 2 black iron pipe and appropri ate fittings 1 Remove knockout indentation on refrac t...

Страница 12: ...lid Fuel Burning Fireplaces ANS Z21 60 Z21 84 or RG 2 72 and shall also be installed in accor dance with the National Fuel Gas Code ANSI 7223NFPA 54 latest edition WARNING Toavoidtheriskof damagingthefireplacematerials andincreasingtheriskofspread ingafire donotusethefireplace to cook or warm food WARNING If the fireplace hasbeenusedforwoodburning thefireboxandchimneymustbe cleaned of soot creosot...

Страница 13: ...nted or vent free decorative gas appliance incorporating an automatic shutoff device and complying with the Standard for Decorative Gas Appliances for Installation in Vented Fireplaces ANSI Z21 60 or American Gas Association draft requirements for Gas Fired Log Lighters for Wood Burning Fireplaces Draft NO 4 dated August 1993 If you wish to install an unvented vent free gas log set only unvented g...

Страница 14: ... com 111026 01G 14 Parts Wood burning Fireplace MODELS S36 S36H S36R S36RH VS36 1 VS36H 1 vs36r and vs36rh 9 26 16 33 27 16 27 4 32 34 19 12 25 20 30 17 8 1 5 21 2 35 18 11 14 3 13 22 10 6 31 7 37 38 36 28 29 24 23 15 ...

Страница 15: ...nt 1 20 110892 01 Air Deflector 1 21 111327 01 Fireplace Top Insulation 1 22 107775 01 Access Panel 1 23 107854 01 Right Refractory Bracket 1 24 107854 02 Left Refractory Bracket 1 25 111028 01 Grate 1 26 11418 Push On Nut 2 27 110890 01 Stainless Screen 2 28 16405 Collar Insulation 1 29 20023 Chimney Starter Collar 1 30 20027 Refractory Retainer 2 31 106539 02 Grate Retainer 2 32 111073 01 Door S...

Страница 16: ...tured Red Herringbone 1 106659 01 Right Refractory Smooth White Brick 1 108165 01 Right Refractory Smooth White Herringbone 1 11 106660 03 Rear Refractory Textured White Brick 1 108166 03 Rear Refractory Textured White Herringbone 1 106660 02 Rear Refractory Textured Red Brick 1 108166 02 Rear Refractory Textured Red Herringbone 1 106660 01 Rear Refractory Smooth White Brick 1 108166 01 Rear Refra...

Страница 17: ...fmiproducts com Accessories Double Wall Pipe 12 8DM 12 8HT 18 8DM 18 8 HT 24 8DM 24 8HT 36 8DM 36 8HT 48 8DM 48 8HT ROOF FLASHING 0 TO 6 12 PITCH V6F 8DM 6 12 TO 12 12 PITCH V12F 8DM ANTI DRAFT SHIELD Round Top Termination Only ADS 8DM Adjustable Hood Antique Brass Finish GA6053 Black Painted Finish GA6050 Required when installing a vent free gas log in this fireplace Bi Fold Glass Door BDO36 Blac...

Страница 18: ...Round Top Terminations RT 8DM RTL 8DM RounD Top Terminations with Slip Section RTT 8DM RTTL 8DM RounD Top Terminations with LOUVERS RTL 8DM Outside Air Kit for Side Wall Installation AK4 Outside Air Kit for Floor Installation AK4F Square Chase Top Termination ET 8DM ETO 8DM Econo Top Termination with Slip Section ETL 8DM ETLO 8DM ...

Страница 19: ..._______________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________...

Страница 20: ...111026 01 Rev G 09 09 2701 S Harbor Blvd Santa Ana CA 92704 1 866 328 4537 www fmiproducts com ...

Отзывы: