Venting installatiOn

Continued

Figure 9 - Elbow Offset

B

A

Screws

FIRESTOP SPACERS (3600FS-8DM-1)

Firestop spacers are required at each point 

where the chimney penetrates a floor space. 

Their  purpose  is  to  establish  and  maintain 

the required clearance between the chimney 

and the combustible materials. When the pipe 

passes through a framed opening into a living 

space above, the firestop must be placed onto 

the ceiling from below as shown in Figure 10.
They also provide complete separation from 

one floor space to another or attic space as 

required by most codes. When the double wall 

pipe passes through a framed opening into an 

attic space, the firestop must be placed into an 

attic floor as shown in Figure 11.

Figure 10 - Firestop Spacer with Living 

Space Above Ceiling

Figure 11 - Firestop Spacer with Attic 

Space Above Ceiling

Existing 

Ceiling 

Frame

Firestop 

Spacer

Screws or 

Staples 

(Min. of 8)

Firestop 

Spacer

Screws or Staples 

(Min. of 8)

PENETRATING ROOF

To maintain a 1" clearance to the pipe on a 

roof with a pitch, a rectangular opening must 

be cut.
1.  Determine center point through which pipe 

will penetrate roof.

2.  Determine center point of roof. Pitch is the 

distance the roof drops over a given span, 

usually 12". A 6/12 pitch means that the 

roof drops 6" for each 12" one measure 

horizontally down from the roof rafters.

3.  Use roof opening chart (Figure 12, page 

9) to determine the correct opening length 

and flashing required.

4.  Remove  the  shingles  around  opening 

measured. Cut out this section.

5.  Add next sections of pipe until end pen

-

etrates  roof  line.  Check  to  see  that  the 

proper clearances are maintained. Extend 

chimney by adding sections of double wall 

pipe until pipe is minimum of 30" above the 

highest point of the roof cutout. Termination 

and chimney must extend a minimum of 

36" above the highest point where it passes 

through the roof.

Existing 

Ceiling 

Frame

Figure 8 - Ceiling Support Pipe  

12S-8DM

2" Min.

Straps

Straps

Straps

Straps

Detail A

Return Elbow

Detail B

Angle Firestop

See Detail A

See Detail B

Содержание (V)S36 Series

Страница 1: ...e gas log heater approved toANS Z21 11 2 standard AFMI PRODUCTS LLC hood must be installed when using a vent free log heater see Accessories page 16 This wood burning fireplace complies with UL127 CAN ULS S610 M87 standard as a FACTORY BUILT APPLIANCE FOR CANADA The authority having jurisdiction such as the municipal building department fire department etc should be contacted before installation t...

Страница 2: ...erty damage or loss of life Refer to this manual for assistance or additional information Consultaqualifiedinstall er or local distributor IMPORTANT Check local codes before installing this fireplace Before beginning installation of this fireplace read these instructions through completely This FMI PRODUCTS LLC fireplace and its components are safe when installed according to this installation man...

Страница 3: ...NOT LESS THAN 12 1 AIRSPACE TO COMBUSTIBLE COMBUSTIBLE WALL BOARD 0 TO MATERIAL NO COMBUSTIBLE MATERIAL ON FACE SIDEWALL TERMINATION SQUARE CHASE TOP GAS LINE KNOCK OUT AIR KIT KNOCK OUTS ROUND TOP TERMINATION GAS LINE KNOCK OUTS ELECTRICAL OUTLET LEFT SIDE RIGHT SIDE 8 125 10 435 14 437 41 25 37 41 35 21 8 32 5 14 25 22 2 5 8 717 1 11 217 2 5 8 125 7 092 8 717 12 5 41 1 0 625 29 21 ...

Страница 4: ...the safest and most efficient location for the fireplace you must take into consideration the following guidelines 1 The location must allow for proper clear ances see Figures 1 and 2 2 Consider a location where the fireplace will not be affected by drafts air condition ing ducts windows or doors 3 A location that avoids the cutting of joists or roof rafters will make installation easier 4 An outs...

Страница 5: ...o prevent the hearth extension from shifting and seal gap between the fireplace frame and hearth extension with a noncom bustible material see Figure 3 Fireplace Installation Continued Figure 3 Hearth Extension Seal Gap Fireplace Front Ember Protector Fireplace Front Raised Hearth Fireplace Front Elevated Ember Protector Ember Protector Seal Gap Hearth Extension WARNING Hearthextension is to be in...

Страница 6: ...e Check Local Codes Before Installing in a Vented Crawl Space Chimney Pipe The FMI PRODUCTS LLC chimney system consists of 12 18 24 36 and 48 snap lock double wall pipe segments planned for maximum adaptability to individual site requirements Actual lengths gained after fit ting overlaps must be taken into consideration lineal gain and are given in the lineal gain chart see Figure 6 Lineal gain is...

Страница 7: ...double wall pipe see offset chart and Figure 7 2 Chimney weight above offset rests on return elbow Straps must be securely nailed to rafters or joists see Figure 8 details A and B on page 8 3 Maximum length of pipe between supports return elbow or 12S 8DM is 6 of angle run Maximum of two 6 angle run sections per chimney system see Figure 7 4 All pipe connections between offset and return must be s...

Страница 8: ... of 8 Firestop Spacer Screws or Staples Min of 8 Penetrating roof To maintain a 1 clearance to the pipe on a roof with a pitch a rectangular opening must be cut 1 Determine center point through which pipe will penetrate roof 2 Determine center point of roof Pitch is the distance the roof drops over a given span usually 12 A 6 12 pitch means that the roof drops 6 for each 12 one measure horizontall...

Страница 9: ... Flashing Cone Underlap Shingles at Bottom Overlap Shingles Top and Sides Only Figure 13 Flashing Installation Storm Collar Installation SC1 or SC2 Place storm collar over pipe and slide down until it is snug against the open edge of the flashing see Figure 14 Use SC1 for all round terminations and SC2 for all terminations with slip sections Apply waterproof caulk around the perimeter of the colla...

Страница 10: ...e 16 Note If a decorative shroud is to be installed contact the manufacturer for specifications 10 foot rule All flue gas outlet chimney terminations must extend a minimum of 3 feet in height above the highest point where it passes through the roof and must be at least 2 feet above the high est point of the roof that is within a horizontal distance of 10 feet see Figure 17 24 Min 24 Min 18 Min Typ...

Страница 11: ...T MAX HEIGHT 14 5 FT MIN HEIGHT OF 22 FT WITH 2 ELBOW SETS MAX HEIGHT OF 50 FT MAX HEIGHT 50 FT ANY SYSTEM 30E 8DM Figure 18 Typical Residential Installations Gas line hook up should be done by your supplier or a qualified service person Note Before you proceed make sure your gas supply is turned off Use only a 1 2 black iron pipe and appropri ate fittings 1 Remove knockout indentation on refrac t...

Страница 12: ...lid Fuel Burning Fireplaces ANS Z21 60 Z21 84 or RG 2 72 and shall also be installed in accor dance with the National Fuel Gas Code ANSI 7223NFPA 54 latest edition WARNING Toavoidtheriskof damagingthefireplacematerials andincreasingtheriskofspread ingafire donotusethefireplace to cook or warm food WARNING If the fireplace hasbeenusedforwoodburning thefireboxandchimneymustbe cleaned of soot creosot...

Страница 13: ...nted or vent free decorative gas appliance incorporating an automatic shutoff device and complying with the Standard for Decorative Gas Appliances for Installation in Vented Fireplaces ANSI Z21 60 or American Gas Association draft requirements for Gas Fired Log Lighters for Wood Burning Fireplaces Draft NO 4 dated August 1993 If you wish to install an unvented vent free gas log set only unvented g...

Страница 14: ... com 111026 01G 14 Parts Wood burning Fireplace MODELS S36 S36H S36R S36RH VS36 1 VS36H 1 vs36r and vs36rh 9 26 16 33 27 16 27 4 32 34 19 12 25 20 30 17 8 1 5 21 2 35 18 11 14 3 13 22 10 6 31 7 37 38 36 28 29 24 23 15 ...

Страница 15: ...nt 1 20 110892 01 Air Deflector 1 21 111327 01 Fireplace Top Insulation 1 22 107775 01 Access Panel 1 23 107854 01 Right Refractory Bracket 1 24 107854 02 Left Refractory Bracket 1 25 111028 01 Grate 1 26 11418 Push On Nut 2 27 110890 01 Stainless Screen 2 28 16405 Collar Insulation 1 29 20023 Chimney Starter Collar 1 30 20027 Refractory Retainer 2 31 106539 02 Grate Retainer 2 32 111073 01 Door S...

Страница 16: ...tured Red Herringbone 1 106659 01 Right Refractory Smooth White Brick 1 108165 01 Right Refractory Smooth White Herringbone 1 11 106660 03 Rear Refractory Textured White Brick 1 108166 03 Rear Refractory Textured White Herringbone 1 106660 02 Rear Refractory Textured Red Brick 1 108166 02 Rear Refractory Textured Red Herringbone 1 106660 01 Rear Refractory Smooth White Brick 1 108166 01 Rear Refra...

Страница 17: ...fmiproducts com Accessories Double Wall Pipe 12 8DM 12 8HT 18 8DM 18 8 HT 24 8DM 24 8HT 36 8DM 36 8HT 48 8DM 48 8HT ROOF FLASHING 0 TO 6 12 PITCH V6F 8DM 6 12 TO 12 12 PITCH V12F 8DM ANTI DRAFT SHIELD Round Top Termination Only ADS 8DM Adjustable Hood Antique Brass Finish GA6053 Black Painted Finish GA6050 Required when installing a vent free gas log in this fireplace Bi Fold Glass Door BDO36 Blac...

Страница 18: ...Round Top Terminations RT 8DM RTL 8DM RounD Top Terminations with Slip Section RTT 8DM RTTL 8DM RounD Top Terminations with LOUVERS RTL 8DM Outside Air Kit for Side Wall Installation AK4 Outside Air Kit for Floor Installation AK4F Square Chase Top Termination ET 8DM ETO 8DM Econo Top Termination with Slip Section ETL 8DM ETLO 8DM ...

Страница 19: ..._______________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________...

Страница 20: ...111026 01 Rev G 09 09 2701 S Harbor Blvd Santa Ana CA 92704 1 866 328 4537 www fmiproducts com ...

Отзывы: