Figure 2 - Common Fireplace Locations
Flush with a wall
Through exterior wall
enclosed in a chase
Corner
installation
Figure 3 - Fireplace Bottom Dimensions
D
RW
FW
21
1
/
8
"
29"
41"
PRE-INSTALLATION PREPARATION
LOCATION AND SPACE
REQUIREMENTS
Determine the safest and most efficient loca
-
tion for your FMI PRODUCTS, LLC direct-vent
fireplace. Make sure that rafters and wall
studs are not in the way of the venting system.
Choose a location where the heat output is
not affected by drafts, air conditioning ducts,
windows or doors. Figure 2 shows some com
-
mon locations. Be aware of all restrictions and
precautions before deciding the exact location
for your fireplace and termination cap.
When deciding the location of your fireplace,
follow these rules:
• Do not connect this fireplace venting to a
chimney flue serving a separate solid-fuel
burning fireplace or appliance.
• Due to high temperatures, do not locate this
fireplace in high traffic areas, windy or drafty
areas or near furniture or draperies.
• Proper clearances must be maintained.
• If your fireplace is to be installed directly on
carpeting, vinyl tile or any combustible mate
-
rial other than wood, it must be installed on a
metal or wood panel extending the full width
and depth of the fireplace. See Figure 3.
• Your fireplace is designed to be used in
zero clearance installations. Wall or framing
material can be placed directly against any
exterior surface on the back, sides or top of
your fireplace, except where standoff spac
-
ers are integrally attached. If standoff spac
-
ers are attached to your fireplace, these
spacers can be placed directly against wall
or framing material. See framing details on
page 7.
• If you plan on installing a television or
entertainment center recessed above
your fireplace, it is recommended that you
maintain a minimum 18" above top of louver
opening.
• When locating termination cap, it is impor
-
tant to observe the minimum clearances
shown in Figure 7, page 8.
• If recessing into a wall, you can avoid extra
framing by positioning your fireplace against
an already existing framing member.
• Do not recess termination cap into a wall
or siding.
• You may paint the termination cap with
450º F (232º C) heat-resistant paint to
coordinate with the exterior finish.
• There must not be any obstruction such
as bushes, garden sheds, fences, decks
or utility buildings within 24" from the front
of the termination cap.
• Do not locate termination cap where exces
-
sive snow or ice build up may occur. Be sure
to clear vent termination area after snow falls
to prevent accidental blockage of venting
system. When using snow blowers, do not
direct snow towards vent termination area.
• For horizontal installations above 2,000
feet, it is recommended that a 12" extension
pipe be added before starter elbow and a
round horizontal termination be used (see
High Altitude Installation
, page 17).
CLEARANCES
Minimum clearances to combustibles for the
fireplace are as follows:
*Back and sides
0"/cm
Perpendicular walls
6" (15 cm)
Floor
0"/cm
Ceiling to louver opening 42" (107 cm)
Front
36" (91 cm)
Top of Standoffs
0"/cm
Vent
(See venting instructions
for specific venting clear
-
ances.)
Combustible material with a maximum thick
-
ness of 5/8" may be flush with the top front
of fireplace.