PROVIDING ADEQUATE
VENTILATION

The following are excerpts from National
Fuel Gas Code. NFPA 54/ANS Z223.1, Sec-
tion 5.3, Air for Combustion and Ventilation.

All spaces in homes fall into one of the three
following ventilation classifications:

1. Unusually Tight Construction
2. Unconfined Space
3. Confined Space

The information on pages 4 through 6 will
help you classify your space and provide
adequate ventilation.

Unusually Tight Construction

The air that leaks around doors and win-
dows may provide enough fresh air for
combustion and ventilation. However, in
buildings of unusually tight construction,
you must provide additional fresh air.

Unusually tight construction is de-
fined as construction where:
a.

walls and ceilings exposed to the
outside atmosphere have a con-
tinuous water vapor retarder with
a rating of one perm (6x10

-11

 kg

per pa-sec-m

2

) or less with open-

ings gasketed or sealed and

b. weather stripping has been

added on openable windows and
doors and

c.

caulking or sealants are applied
to areas such as joints around
window and door frames, be-
tween sole plates and floors, be-
tween wall-ceiling joints, be-
tween wall panels, at penetra-
tions for plumbing, electrical, and
gas lines, and at other openings.

If your home meets all of the three
criteria above, you must provide ad-
ditional fresh air. See Ventilation Air
From Outdoors, page 6.

If your home does not meet all of the
three criteria above, proceed to De-
termining Fresh-Air Flow For Heater
Location, page 5.

Confined and Unconfined Space

The National Fuel Gas Code (ANS Z223.1,
1992 Section 5.3) 
defines a confined space
as a space whose volume is less than 50
cubic feet per 1,000 Btu per hour (4.8 m

3

 per

kw) of the aggregate input rating of all
appliances installed in that space and an
unconfined space as a space whose volume
is not less than 50 cubic feet per 1,000 Btu
per hour (4.8 m

3

 per kw) of the aggregate

input rating of all appliances installed in that
space. Rooms communicating directly with
the space in which the appliances are in-
stalled*, through openings not furnished
with doors, are considered a part of the
unconfined space.

This heater shall not be installed in a con-
fined space or unusually tight construction
unless provisions are provided for adequate
combustion and ventilation air.

* Adjoining rooms are communicating only
if there are doorless passageways or ventila-
tion grills between them.

AIR FOR
COMBUSTION AND
VENTILATION

Today’s homes are built more energy effi-
cient than ever. New materials, increased
insulation, and new construction methods
help reduce heat loss in homes. Home own-
ers weather strip and caulk around windows
and doors to keep the cold air out and the
warm air in. During heating months, home
owners want their homes as airtight as possible.

While it is good to make your home energy
efficient, your home needs to breathe. Fresh
air must enter your home. All fuel-burning
appliances need fresh air for proper com-
bustion and ventilation.

Exhaust fans, fireplaces, clothes dryers, and
fuel burning appliances draw air from the
house to operate. You must provide ad-
equate fresh air for these appliances. This
will insure proper venting of vented fuel-
burning appliances.

 WARNING: This heater shall

not be installed in a confined space
or unusually tight construction
unless provisions are provided
for adequate combustion and ven-
tilation air. Read the following in-
structions to insure proper fresh
air for this and other fuel-burning
appliances in your home.

Содержание FVFM27PR

Страница 1: ...pplier WARNING Improper installation ad justment alteration service or main tenance can cause injury or property damage Refer to this manual for cor rect installation and operational pro cedures For assistance or additional informationconsultaqualifiedinstaller service agency or the gas supplier WARNING This is an unvented gas fired heater It uses air oxygen from the room in which it is installed ...

Страница 2: ...ter with doors closed heat buildup inside fireplace will cause glass to burst Also if fireplace open ing has vents at the bottom you must open the vents before operating heater 9 Youmustoperatethisheaterwithfireplace screens in place Make sure fireplace screens are closed while running heater 10 This log heater is designed to be smoke less If logs ever appear to smoke turn off heater and call a qu...

Страница 3: ...slandfireboxes with multiple openings You may also in stall this log heater in a standard firebox SAFETY PILOT This heater has a pilot with an Oxygen Depletion Sensor Shutoff System ODS TheODS pilotisarequiredfeatureforvent free room heaters The ODS pilot shuts off the heater if there is not enough fresh air PIEZO IGNITION SYSTEM This heater has a piezo ignitor This system requires no matches batt...

Страница 4: ...ace as a space whose volume is less than 50 cubic feet per 1 000 Btu per hour 4 8 m3 per kw of the aggregate input rating of all appliances installed in that space and an unconfined space as a space whose volume is not less than 50 cubic feet per 1 000 Btu per hour 4 8 m3 per kw of the aggregate inputratingofallappliancesinstalledinthat space Rooms communicating directly with the space in which th...

Страница 5: ...ir from the outdoors and vents to the outdoors 4 Compare the maximum Btu Hr the space can support with the actual amount of Btu Hr used _________________ Btu Hr maximum the space can support _________________ Btu Hr actual amount of Btu Hr used Example 51 200 Btu Hr maximum the space can support 79 000 Btu Hr actual amount of Btu Hr used The space in the above example is a confined space because t...

Страница 6: ...ir From Outdoors Provide extra fresh air by using ventilation grills or ducts You must provide two per manent openings one within 12 of the ceiling and one within 12 of the floor Connect these items directly to the outdoors orspacesopentotheoutdoors Thesespaces include attics and crawl spaces IMPORTANT Do not provide openings for inlet or outlet air into attic if attic has a thermostat controlledp...

Страница 7: ...will ignite if highly heated A dirty chimney flue may create and dis tribute soot within the house In spect chimney flue for damage If damaged operate heater with flue damper closed WARNING Seal any fresh air vents or ash clean out doors lo cated on floor or wall of fireplace If not drafting may cause pilot outage or sooting Use a heat resistant sealant Do not seal chimney flue damper CAUTION This...

Страница 8: ...2 Installfireplacehoodaccessory HDABKorHDABR see Accessories page 21 Less than 8 Noncombustible material must be extended to at least 8 See Between 8 and 12 above If you cannot extend material you must operate heater with flue damper open NOTICE Manual control heaters maybeusedasaventedproduct If so you must always run heater with chimney flue damper open If running heater with damper open non com...

Страница 9: ...antel Top of Fireplace Opening Underside of Mantel Shelf Mantel Shelf 12 A 18 20 22 24 All minimum distances are in inches 2 1 2 6 8 10 Minimum Non Combustible Material 8 Min 12 15 18 All minimum distances are in inches 20 2 1 2 6 8 10 12 Distances to Underside of Mantel Hood Top of Fireplace Opening Log Sets All Models Underside of Mantel Shelf Mantel Shelf Figure 8 Minimum Fireplace Clearances I...

Страница 10: ...ter base assembly by the burner This could damage heater Only handle base assem bly by grates WARNING You must secure this heater to fireplace floor If not heater will move when you adjust controls Moving heater may cause a gas leak IMPORTANT Makesuretheheaterburner is level If heater is not level heater will not work properly CAUTION Do not remove the metal data plates attached to the heater base...

Страница 11: ...ant lightly to male threads This will prevent excess sealant from going into pipe Excess sealant in pipe could result in clogged heater valves CAUTION Use only new black iron or steel pipe Inter nally tinned copper tubing may be used in certain areas Check your local codes Use pipe of 1 2 diameter or greater to allow proper gas volume to heater If pipe is too small undue loss of pressure will occu...

Страница 12: ...d connections for leaks after installing or servicing Cor rect all leaks at once CAUTION Make sure exter nal regulator has been installed between propane LP supply and heater See guidelines under Con necting to Gas Supply page 11 CHECKING GAS CONNECTIONS Test Pressures Equal To or Less Than 1 2 PSIG 1 Close manual shutoff valve see Fig ure 15 2 Pressurize supply piping system by ei ther using comp...

Страница 13: ... of unit place top log 2 onto the pegs in the center of the bot tom log see Figure 19 3 Position log piece 3 by aligning holes on underside with remaining pegs on bottom log see Figure 20 4 Place lava rock on fireplace floor around base of heater Figure 17 Installing Bottom Log 1 Figure 18 Installing Log set Top View Logs Burner Ports Bottom Log 1 Burner Chassis CAUTION After installation andperio...

Страница 14: ...erating heater You must operate this heater with a fireplace screen in place Make sure fireplace screen is closed before running heater NOTICE During initial operation of new heater burning logs will give off a paper burning smell Open damper or window to vent smell This will only last a few hours Note Home owners generally prefer to operate their heater with the chimney damper closed This will pu...

Страница 15: ...entral heating system etc 1 Follow steps 1 through 6 under Light ing Instructions page 14 2 Depress control knob and light pilot with match 3 Keep control knob pressed in for 30 seconds after lighting pilot After 30 seconds release control knob Now follow steps 9 through 11 column 1 OPTIONAL REMOTE OPERATION NOTICE You must light the pilot before using the hand held re mote control unit See Lighti...

Страница 16: ...shows a correct pilot flame pat tern Figure 26 shows an incorrect pilot flame pattern The incorrect pilot flame is not properly heating the thermocouple When the thermocouple cools the heater will shut down If pilot flame pattern is incorrect as shown in Figure 26 turn heater off see To Turn Off Gas to Appliance page 15 see Troubleshooting pages 17 through 19 Pilot Burner Thermocouple INSPECTING B...

Страница 17: ...nnect ignitor cable 2 Free ignitor cable if pinched by any metal or tubing Keep ignitor cable dry 3 Tighten nut holding piezo ignitor to base panel of log set Nut is located behind base panel 4 Replace ignitor cable 5 Replace piezo ignitor 6 Replace piezo ignitor 7 Replace piezo ignitor 1 Turn on gas supply or open manual shutoff valve 2 Turn control knob to PILOT position 3 Press in control knob ...

Страница 18: ...tion and Venti lation requirements page 4 1 Turn control knob to LO position and let warm up for a minute 2 Operate burner until air is removed from line Have gas line checked by local pro pane LP gas company 3 Observe minimum installation clear ances see pages 7 through 9 4 Clean burner see Cleaning and Mainte nance page 20 or replace burner orifice 1 Turn heater off when using furniture polish w...

Страница 19: ...n with most heaters If noise is excessive contact qualified ser vice person 1 Open window and ventilate room Stop using odor causing products while heater is running 2 Locate and correct all leaks see Check ing Gas Connections page 12 1 Open window and or door for ventilation 2 Contact local natural gas company 3 Clean ODS pilot see Cleaning and Maintenance page 20 1 Locate and correct all leaks s...

Страница 20: ...or Holder On Outlet Burner Tube 5 Blow air into the primary air holes on the injector holder 6 In case any large clumps of dust have now been pushed into the burner repeat steps 3 and 4 Clean the pilot assembly also A yellow tip on the pilot flame indicates dust and dirt in the pilot assembly There is a small pilot air inlet hole about two inches from where the pilot flame comes out of the pilot a...

Страница 21: ...page of this manual FIREPLACE HOOD Black HDABK Part 01244 Brass HDABR Part 01245 Antique Brass GA6053 For all models Helps deflect heat away from mantel or wall above fireplace Fits openings 28 to 49 wide LAVA ROCK 02016 Not Shown For all models Order when additional rock is desired 3 lb bag DAMPER CLAMP 02017 not shown Permanently opens chimney flue damper for vented operation Can be used only wi...

Страница 22: ...ROPANE LP GAS LOG HEATER FIREPLACE MANUFACTURERS INCORPORATED ILLUSTRATED PARTS BREAKDOWN FVFM27PR 5 O F F P I L O T O N H I L O O F F P I L O T O N H I L O 1 9 3 2 13 12 15 14 18 17 12 12 16 21 12 19 6 8 7 4 11 12 20 9 10 ...

Страница 23: ...e Injector 1 8 104591 01 Burner 1 9 099387 13 Pilot Tube 1 10 103781 02 Gas Control Valve 1 11 104611 01 Lower Bracket 1 12 098304 01 Screw 8 x 38 7 13 104590 01CK Painted Base Assy 1 14 098271 06 Ignitor Cable 1 15 102445 01 Piezo Ignitor 1 16 103587 02 Plate Switch 1 17 103784 02 Flame Adjustment Knob 1 18 103784 01 Off Pilot On Knob 1 19 M12461 26 Screw Hex Slt Wsr 10 32 x 38 4 20 103284 02 Wir...

Страница 24: ...rdance with all local codes and instructions furnished with the unit This warranty does not apply to parts that are not in original condition because of normal wear and tear or parts that fail or become damaged as a result of misuse accidents lack of proper maintenance or defects caused by improper installation Travel diagnostic cost labor transportation and any and all such other costs related to...

Отзывы: