background image

 

6

For more information, visit www.desatech.com

 

5.  Do not insulate on top of the firebox.  The opening in the 
collar around the chimney at the top of the fireplace must not 
be obstructed (see figure 11). 

 
6. Before finishing the fireplace enclosure, inspect all joints of 
the outer firebox.  Seal any gaps of the outer firebox with a 
non-combustible material.  Caulk any gaps between the 
nailing flange and framing. 
 

   
 

CHIMNEY SYSTEM: 

 
CHIMNEY HEIGHT 
 
Minimum chimney height measured from bottom of fireplace 
to flue gas outlet-end of the termination is: 
Straight 

run 

   14 

feet 

Run with one elbow set   

 

14 feet 

Run with two elbow sets   

 

22 feet 

 
An elbow set is consist of one starter elbow and one return 
elbow.  Uncommon circumstances such as neighboring hills, 
tall trees, or strong wind areas can cause downdrafts in the 
chimney system.  In such cases, going beyond the minimum 

recommended height would be preferable to provide a better 
draw. 
Maximum height approved for any chimney run with this 
fireplace system is 40 feet as measured from the bottom of the 
fireplace to the flue outlet-end of the termination. 
 
ASSEMBLING AND INSTALLING THE DOUBLE WALL 
CHIMNEY SYSTEM 
 
The DESA chimney system consists of 12, 18, 24, 36 and 48-
inch, snap-lock double-wall pipe segments, planned for 
maximum adaptability to individual site requirements.  Actual 
lengths gained (lineal gain) after fitting overlaps must be taken 
into consideration (see figure 12). 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Each double wall chimney section consists of a galvanized 
outer pipe, a stainless steel inner flue pipe and a wire spacer. 
The pipe sections must be assembled independently as the 
chimney is installed.  When attaching the chimney directly to 
the fireplace, the inner flue pipe section must be installed first 
with the female side up (see figure 12).  The outer pipe section 
can then be installed over the flue pipe section with the male 
end up. 
 
Press down on each pipe section until the lances securely   
engage the hem on the fireplace starter.  The wire will assure 
the proper spacing between the inner and outer pipe sections 
(see figure 12). 
 
Continue to assemble chimney sections as outlined above, 
making sure that both the inner and outer pipe sections are 
locked together. 
 
When installing double wall “snap-lock” chimney together, it 
is important to insure that the joint between the chimney 
sections is locked.  Check by pulling chimney upward after 
locking.  The chimney will not come apart if properly locked.  
It is not necessary to add screws to keep the chimney together.  
However, if desired, use screws per directions provided on 
page 7, figure 14.

 

 

Figure 10    COLD CLIMATE INSTALLATION 

Figure 11     FIREPLACE COLLAR OPENING

Figure 12 

          LINEAL GAIN 

Содержание ELIMINATOR 36E

Страница 1: ...DESA hood must be installed when using a vent free gas log set See accessories on pg 11 WARNING ALWAYS LEAVE GLASS DOORS FULLY OPENED OR FULLY CLOSED WHEN OPERATING THIS FIREPLACE DESA INTERNATIONAL...

Страница 2: ...LLING THE FIREPLACE PG 3 8 HEARTH EXTENSION PG 4 9 OUTSIDE AIR KIT PG 4 10 GAS LINE INSTALLATION PG 4 11 VENT FREE GAS LOG INSTALLATION PG 5 12 COLD CLIMATE INSTALLATIONS PG 5 13 CHIMNEY PIPE PG 6 7 1...

Страница 3: ...rtant step in ensuring safe and continuous operation of this fireplace SELECTING LOCATION To determine the safest and most efficient location for your fireplace consider the following guidelines The l...

Страница 4: ...level of the fireplace and shim with sheet metal if necessary STEP 5 Before securing fireplace to prepared framing the ember protector provided must be placed between hearth extensions not supplied a...

Страница 5: ...5 OPTIONAL OUTSIDE AIR KIT MODELS AK4E The outside air kit must be installed during the rough framing of the fireplace due to the nature of its location Outside combustion air can be accessed through...

Страница 6: ...be installed when using an unvented gas log set see accessories on page 11 VENTED GAS LOG INSTALLATION If you install a decorative gas appliance vented gas log the decorative gas appliance must compl...

Страница 7: ...wall pipe segments planned for maximum adaptability to individual site requirements Actual lengths gained lineal gain after fitting overlaps must be taken into consideration see figure 12 Each double...

Страница 8: ...as required by most codes When the double wall pipe passes through a framed opening into an attic space the firestop must be place into the attic floor as in figure 16 When the pipe passes through a...

Страница 9: ...ermine the correct opening length and flashing required STEP 4 Remove the shingles around the opening measured and cut out this section STEP 5 Add the next sections of the pipe until the end penetrate...

Страница 10: ...E TERMINATION BEING USED Terminations with 16 slip pipe sections are available The RTT 8DM and RTTL 8DM are approved for flashing or chase installations The ETL 8DM and ETLO 8DM are terminations that...

Страница 11: ...inches above the opening of the fireplace see figure 25 Combustible materials above 9 inches and projecting more than 1 inches from the front face of the fireplace must be place at least 12 inches ab...

Страница 12: ...visit www desatech com Desa International 2701 Industrial Drive P O Box 90024 Bowling Green KY 42102 9004 www desatech com 800 323 5190 CONTACT YOUR LOCAL DEALER ACCESSORY PARTS CONTACT YOUR LOCAL DE...

Отзывы: