background image

 

4

For more information, visit www.desatech.com

 

HEARTH EXTENSION: 

 
A hearth extension is required to protect the combustible floor 
constructed in front of the fireplace.  The hearth extension is 
not included and must be fabricated.  The hearth extension 
must project at least 12 inches beyond each side of the 
fireplace opening (see drawing on front cover). 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
The hearth extension must be made of non-combustible, 
inorganic material having an effective thermal conductivity 
“K” of 0.84 BTU IN/FT.HR.F (or less) at 1 inch thick. 
 
Thermal conductivity “K” of materials can be obtained from 
the manufacturer of the non-combustible material.  The 
minimum required thickness for any material could be 
obtained by the following formula: 
 

K factor at 1 inch  = thickness required 

                              0.84 
For example, if the material selected has a K factor of 0.25, 
such as a glass fiber, the following formula would apply: 
 

0.25 = 0.30 thickness required 

                          0.84 
If the hearth extension is to be covered, use non-combustible 
material such as tile, slate, brick, concrete, metal, glass, 
marble, stone etc.  Provide a means to prevent the hearth 
extension from shifting and seal the gap between the fireplace 
frame and hearth extension with a non-combustible material 
(see figure 5). 

 

OPTIONAL OUTSIDE AIR KIT (MODELS AK4E): 
 

The outside air kit must be installed during the rough framing 
of the fireplace due to the nature of its location.  Outside 
combustion air can be accessed through an exterior wall.  See 
figure 6 and Accessories on page 11. 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
Avoid installing outside air eyebrow in areas where inlet 
opening may be blocked by snow, bushes or other obstacles.  
It should also be located beyond the reach of children.  The 
maximum height of air inlet above platform of fireplace is 3 ft. 
below the termination flue gas outlet. 
For further details on the installation of the outside air kit, 
please refer to the instructions included with the air kit.  For 
operating instructions please refer to your owner’s manual. 
The outside air handle is located at the left-hand side of the 
fireplace refractory (see figure 7).  To close, pull down; to 
open, push up.  Always open the mechanism when starting a 
fire to provide adequate outside combustion air.  Close the 
mechanism when not in use to prevent cold air from entering 
the room.  
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
GAS LINE INSTALLATION (OPTIONAL): 

Gas line hook up should be done by your supplier or a 
qualified service person. 

NOTE:

 Before you proceed, make sure your gas supply is 

turned off. 
 

 WARNING:

 HEARTH EXTENSION IS TO BE 

INSTALLED ONLY AS DESCRIBED. 

 CAUTION:

AIR DUCTS MUST NOT TERMINATE 

IN ATTIC SPACE OR GARAGE. 

 

Figure 5          HEARTH EXTENSIONS 

 

Figure 6             AIR KIT INSTALLATION 

Figure 7             AIR KIT DAMPER ROD 

Содержание ELIMINATOR 36E

Страница 1: ...DESA hood must be installed when using a vent free gas log set See accessories on pg 11 WARNING ALWAYS LEAVE GLASS DOORS FULLY OPENED OR FULLY CLOSED WHEN OPERATING THIS FIREPLACE DESA INTERNATIONAL...

Страница 2: ...LLING THE FIREPLACE PG 3 8 HEARTH EXTENSION PG 4 9 OUTSIDE AIR KIT PG 4 10 GAS LINE INSTALLATION PG 4 11 VENT FREE GAS LOG INSTALLATION PG 5 12 COLD CLIMATE INSTALLATIONS PG 5 13 CHIMNEY PIPE PG 6 7 1...

Страница 3: ...rtant step in ensuring safe and continuous operation of this fireplace SELECTING LOCATION To determine the safest and most efficient location for your fireplace consider the following guidelines The l...

Страница 4: ...level of the fireplace and shim with sheet metal if necessary STEP 5 Before securing fireplace to prepared framing the ember protector provided must be placed between hearth extensions not supplied a...

Страница 5: ...5 OPTIONAL OUTSIDE AIR KIT MODELS AK4E The outside air kit must be installed during the rough framing of the fireplace due to the nature of its location Outside combustion air can be accessed through...

Страница 6: ...be installed when using an unvented gas log set see accessories on page 11 VENTED GAS LOG INSTALLATION If you install a decorative gas appliance vented gas log the decorative gas appliance must compl...

Страница 7: ...wall pipe segments planned for maximum adaptability to individual site requirements Actual lengths gained lineal gain after fitting overlaps must be taken into consideration see figure 12 Each double...

Страница 8: ...as required by most codes When the double wall pipe passes through a framed opening into an attic space the firestop must be place into the attic floor as in figure 16 When the pipe passes through a...

Страница 9: ...ermine the correct opening length and flashing required STEP 4 Remove the shingles around the opening measured and cut out this section STEP 5 Add the next sections of the pipe until the end penetrate...

Страница 10: ...E TERMINATION BEING USED Terminations with 16 slip pipe sections are available The RTT 8DM and RTTL 8DM are approved for flashing or chase installations The ETL 8DM and ETLO 8DM are terminations that...

Страница 11: ...inches above the opening of the fireplace see figure 25 Combustible materials above 9 inches and projecting more than 1 inches from the front face of the fireplace must be place at least 12 inches ab...

Страница 12: ...visit www desatech com Desa International 2701 Industrial Drive P O Box 90024 Bowling Green KY 42102 9004 www desatech com 800 323 5190 CONTACT YOUR LOCAL DEALER ACCESSORY PARTS CONTACT YOUR LOCAL DE...

Отзывы: