INSTRUCTIONS WHEN OFFSET OF CHIMNEY IS 
NEEDED 
 

Installing offset and return elbow (30E-8DM) 

1.

 

To achieve desired offset, you may install 
combination of 12”, 18”, 24”, 36” and 48” length of 
double wall pipe (see figures 13 and 14). 

2.

 

The chimney weight above the offset rest on return 
elbow.  Straps must be securely fastened to rafters or 
joists (see figure 15, details A & B). 

3.

 

Maximum length of pipe between supports (return 
elbow or chimney support V12S-8DM) is 6’ of 
angled run.  Maximum of two (2) 6’ angled run 
sections per chimney system. 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
FIRESTOP SPACERS: (3600FS-8DM) 

 
Firestop spacers are required at each point where the chimney 
penetrates a floor or ceiling joist space.  Their purpose is to 
establish and maintain the required clearance between the 
chimney and the combustible materials. 
 
They also provide complete separation from one floor space to 
another floor or attic space as required by most codes.  When 
the double wall pipe passes through a framed opening into an 
attic space, the firestop must be place into the attic floor as in 
figure 16. 
 
When the pipe passes through a framed opening into a living 
space above, the firestop must be placed onto the ceiling from 
below as shown in figure 16. 
 

 

                             1 elbow set – 14 to 40 ft. system height, 2 elbow sets – 22 to 40 ft. system height. 

Figure 13                                                        TYPICAL OFFSET INSTALLATIONS 

 

 

 

 

 

 

 

 

 

Figure 14                  OFFSET CHART 

All pipe connections between 
the offset and return must be 
secured with two screws, 
only on the outer pipe, and 
must not penetrate the inner 
stainless. 

OFFSET

RISE

A

B

48"

36"

24"

18"

12"

4 - 3/8

16 -3/8

9 - 3/4

25 - 1/2

1

12 - 3/4

30 - 3/4

1

15

34 - 3/4

1

18

40

1

1

21 - 1/4

46 - 1/4

1

23 - 3/4

49 - 1/4

1

1

27 - 3/4

56 - 3/4

1

30

60 - 3/4

1

1

33

66 1

1

36

71

1

1

38 - 1/4

75

2

41 - 1/4

80 - 1/4

1

1

1

45

86 - 3/4

2

46 - 3/4

89 - 1/2

1

1

1

51

97

1

1

53 - 1/4

101

2

1

56 - 1/4

106 - 1/4

2

59 - 1/4

111 - 1/2

1

1

1

61 - 3/4

115 - 1/2

2

1

64 - 3/4

120 - 3/4

2

1

68 - 1/4

127

1

2

70

130

2

1

1

74 - 1/4

137 - 1/2

1

2

1

76 - 3/4

141 - 1/2

1

2

1

79 - 3/4

146 - 3/4

4

ELBOW SET ONLY

CHIMNEY LENGTH

Figure 15         OFFSET PIPE SUPPORT 

Содержание ELIMINATOR 36E

Страница 1: ...DESA hood must be installed when using a vent free gas log set See accessories on pg 11 WARNING ALWAYS LEAVE GLASS DOORS FULLY OPENED OR FULLY CLOSED WHEN OPERATING THIS FIREPLACE DESA INTERNATIONAL...

Страница 2: ...LLING THE FIREPLACE PG 3 8 HEARTH EXTENSION PG 4 9 OUTSIDE AIR KIT PG 4 10 GAS LINE INSTALLATION PG 4 11 VENT FREE GAS LOG INSTALLATION PG 5 12 COLD CLIMATE INSTALLATIONS PG 5 13 CHIMNEY PIPE PG 6 7 1...

Страница 3: ...rtant step in ensuring safe and continuous operation of this fireplace SELECTING LOCATION To determine the safest and most efficient location for your fireplace consider the following guidelines The l...

Страница 4: ...level of the fireplace and shim with sheet metal if necessary STEP 5 Before securing fireplace to prepared framing the ember protector provided must be placed between hearth extensions not supplied a...

Страница 5: ...5 OPTIONAL OUTSIDE AIR KIT MODELS AK4E The outside air kit must be installed during the rough framing of the fireplace due to the nature of its location Outside combustion air can be accessed through...

Страница 6: ...be installed when using an unvented gas log set see accessories on page 11 VENTED GAS LOG INSTALLATION If you install a decorative gas appliance vented gas log the decorative gas appliance must compl...

Страница 7: ...wall pipe segments planned for maximum adaptability to individual site requirements Actual lengths gained lineal gain after fitting overlaps must be taken into consideration see figure 12 Each double...

Страница 8: ...as required by most codes When the double wall pipe passes through a framed opening into an attic space the firestop must be place into the attic floor as in figure 16 When the pipe passes through a...

Страница 9: ...ermine the correct opening length and flashing required STEP 4 Remove the shingles around the opening measured and cut out this section STEP 5 Add the next sections of the pipe until the end penetrate...

Страница 10: ...E TERMINATION BEING USED Terminations with 16 slip pipe sections are available The RTT 8DM and RTTL 8DM are approved for flashing or chase installations The ETL 8DM and ETLO 8DM are terminations that...

Страница 11: ...inches above the opening of the fireplace see figure 25 Combustible materials above 9 inches and projecting more than 1 inches from the front face of the fireplace must be place at least 12 inches ab...

Страница 12: ...visit www desatech com Desa International 2701 Industrial Drive P O Box 90024 Bowling Green KY 42102 9004 www desatech com 800 323 5190 CONTACT YOUR LOCAL DEALER ACCESSORY PARTS CONTACT YOUR LOCAL DE...

Отзывы: