VENTING INSTALLATION

Continued

Figure 16 - Offset with Wall Strap and 45° 

Elbows

45° Elbow

Wall Strap

Roof Flashing

Ceiling Firestop

Flat Ceiling Installation

1. Cut a 11 

1

/

2

" square hole in ceiling using locat-

ing hole as a center point. Opening should be 

framed to 11 

1

/

2

" x 11 

1

/

2

" inside dimensions, as 

shown in Figure 9 on page 12 using framing 

lumber the same size as ceiling joists. If area 

above ceiling is an insulated ceiling or an attic, 

nail firestop from top side. This prevents loose 

insulation from falling into required clearance 

space. If area above ceiling is a living space, 

install firestop below framed hole. Firestop 

should be installed with no less than three 

nails per side (see Figure 17, page 17).

2. Assemble desired lengths of pipe and el-

bows necessary to reach from fireplace flue 

up through firestop. Be sure all pipe and 

elbow connections are fully twist-locked 

(see Figure 9, page 12).

3. Cut a hole in the roof using locating hole as 

a center point. (Cover any exposed open 

vent pipes before cutting hole in roof.) The 

11 

1

/

2

" x 11 

1

/

2

" hole must be measured on 

the horizontal; actual length may be larger 

depending on pitch of roof. There must be 

a 1" clearance from vent pipe to combus-

tible materials. Frame opening as shown 

in Figure 9, page 12.

4. Connect a section of pipe and extend up 

through hole.

 

Note: If an offset is needed to avoid obstruc-

tions, you must support vent pipe every 3 feet. 

Use wall straps for this purpose (see Figure 

16). Whenever possible, use 45° elbows 

instead of 90° elbows. The 45° elbow offers 

less restriction to the flow of flue gases.

5. Place flashing over pipe section(s) extending 

through roof. Secure base of flashing to roof 

and framing with roofing nails. Be sure roof

-

ing material overlaps top edge of flashing as 

shown in Figure 16. There must be a 1" clear-

ance from vent pipe to combustible materials.

Vertical Termination Installation

Note: 

Vertical restrictor

 must be installed in 

all vertical installations.

1.  Determine route your vertical venting 

will  take.  If  ceiling  joists,  roof  rafters  or 

other framing will obstruct venting system, 

consider an offset (see Figure 16) to avoid 

cutting load bearing members. 

Note: Pay 

special attention to these installation 

instructions for required clearances (air 

space) to combustibles when passing 

through ceilings, walls, roofs, enclosures, 

attic rafters, etc. Do not pack air spaces 

with insulation. Also note maximum 

vertical rise of venting system and any 

maximum horizontal offset limitations.

2.  Set fireplace in desired location. Drop a 

plumb line down from ceiling to position 

of  fireplace  exit  flue.  Mark  center  point 

where vent will penetrate ceiling. Drill a 

small locating hole at this point.

3.  Drop a plumb line from inside of roof to 

locating hole in ceiling. Mark center point 

where vent will penetrate roof. Drill a small 

locating hole at this point.

Vent Termination Chart

Minimum Height

Roof Pitch

Feet Min.

Flat to 6/12

1

6/12 to 7/12

1.25

Over 7/12 to 8/12

1.5

Over 8/12 to 9/12

2

Over 9/12 to 10/12

2.5

Over 10/12 to 11/12

3.25

Over 11/12 to 12/12

4

Over 12/12 to 14/12

5

Over 14/12 to 16/12

6

Over 16/12 to 18/12

7

Over 18/12 to 20/12

7.5

Over 20/12 to 21/12

8.0

Содержание EADV36NE

Страница 1: ...nce Do not touch any electrical switch do not use any phone in your building Immediatelycallyourgassupplierfromaneighbor s phone Follow the gas supplier s instructions If you cannot reach your gas sup...

Страница 2: ...ation of Termination Cap 9 Requirements for the Commonwealth of Massachusetts 10 Venting Installation 11 Fireplace Installation 19 Operation 24 Gas Control Module System 25 Inspecting Burners 26 Clean...

Страница 3: ...or other flammable material on or near the appliance Never place any objects on the appliance Do not use this fireplace to cook food or burn paper or other flam mable material This fireplace reaches...

Страница 4: ...eplace SAFETY Continued 6 Have venting system inspected annually by a qualified service person If needed have venting system cleaned or repaired See Cleaning and Maintenance page 26 7 Do not use any s...

Страница 5: ...ither vertical or horizontal applications This fireplace may be installed in any room of your house provided all local codes and these installation instructions are followed Each time you turn on your...

Страница 6: ...n back sides or top of your fireplace except where standoff spacers are integrally attached If standoff spacers are attached to your fireplace these spacers can be placed directly against wall or fram...

Страница 7: ...stallation All minimum clearances must be met If you are using a separate combustible man tel piece refer to Figure 5 for proper instal lation height You can install noncombustible mantels at any heig...

Страница 8: ...ireplace Dimensions 21 1 8 36 25 1 8 42 29 36 34 3 4 42 12 36 13 3 4 42 4 1 2 41 36 48 42 20 1 2 36 24 42 44 36 48 42 38 7 8 36 43 3 4 42 1 1 2 35 36 42 42 43 36 50 42 1 1 33 36 37 42 3 1 4 11 36 11 1...

Страница 9: ...n US if greater than 50 000 36 91 cm in Canada if greater than 100 000 K clearance to a mechanical air supply inlet In Canada 6 ft 1 83m minimum In US 3 ft 91 cm above if within 10 ft 3 m horizontally...

Страница 10: ...ctly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than 1 2 in size GAS VENT DIRECTLY BELOW KEE...

Страница 11: ...pe components and terminations The venting system must terminate on the outside of the structure and can not be at tached to a chimney or flue system serving a separate solid fuel or gas burning appli...

Страница 12: ...gs indentations These lugs will slide straight into match ing slots on male ends of adjacent pipes Push pipe sections together and twist one section clockwise approximately one quarter turn until sect...

Страница 13: ...Siding standoff must sit flush against exterior fascia material 6 Connecting Vent Cap with Horizontal Vent Pipe Slide wall firestop over vent pipe before connecting horizontal run to vent cap see Figu...

Страница 14: ...ation Configurations Figures 14 and 15 page 15 show a configu ration for venting with horizontal termination with a chart of critical minimum and maximum dimensions which MUST be met If using a ventin...

Страница 15: ...lbow Wall Firestop H 90 Elbow V 90 Elbow Horizontal High Wind Square Termination 76 Min 42 73 Min 36 1 Pipe Min On Horizontal Run V Vertical Minimum Required Vertical Pipe H Horizontal Maximum 33 2 ft...

Страница 16: ...e 45 elbows instead of 90 elbows The 45 elbow offers less restriction to the flow of flue gases 5 Place flashing over pipe section s extending through roof Secure base of flashing to roof and framing...

Страница 17: ...n Double Wall Pipe Galvanized P58 48 48 Section Double Wall Pipe Galvanized PA58 712 Adjustable 7 12 Section Double Wall Pipe Galvanized E58 45 45 Elbow Galvanized E58 90 90 Elbow Galvanized HTS 58 Ho...

Страница 18: ...ATION Continued Figure 18 Vertical Venting Configuration Vertical Venting V 40 max Figure 19 Vertical Venting Configuration Using Two 90 Elbows Venting with Two 90 Elbows Vertical V1 Horizontal H 6 mi...

Страница 19: ...nt shutoff valve with 1 8 NPT tap is an acceptable alternative to test gauge connection Purchase the equipment shutoff valve from your retailer For propane LP connection only the installer must supply...

Страница 20: ...in Figure 21 Locate sediment trap drip leg where it is within reach for cleaning Install in piping system between fuel supply and fireplace Locate sediment trap drip leg where trapped matter is not li...

Страница 21: ...luid to all joints Bubbles forming show a leak Correct all leaks at once 5 Reconnect fireplace and equipment shutoff valve to gas supply Check recon nected fittings for leaks Test Pressures Equal To o...

Страница 22: ...26 Removing Replacing Door Removing Glass Door If replacement of glass is necessary the entire frame assembly must be replaced Gloves must be worn when removing replacing glass door If glass is broke...

Страница 23: ...an open flame to check for a leak Apply noncorrosive leak de tection fluid to joints Bubbles forming show a leak Correct leaks at once CAUTION The gas supply shall be shut off prior to discon necting...

Страница 24: ...1 2 Turn off all electric power to fireplace 3 Turn safety shutoff switch to the OFF position Figure 29 Turning Equipment Shutoff Valve to the OFF Position Equipment Shutoff Valve 4 Remove face trim p...

Страница 25: ...wing posi tive and negative directions 4 Replace battery cover onto remote control unit CONTINUOUS PILOT FEATURE This allows the change from a spark to pilot system to a standing pilot system 1 There...

Страница 26: ...CK UP This fireplace is equipped with a battery back up If the power was to go out on the fireplace the battery back up allows the fireplace to remain operational Make sure to periodically check the c...

Страница 27: ...ac CAUTION Do not vacuum if pieces are hot Use only glass door replacement intended for this fireplace see Replacement Parts page 37 for detail on ordering No substitutions may be made See Removing Re...

Страница 28: ...ve is not opening 7 No power to unit or ignition module REMEDY 1 Check to see if you have gas supply and that equip ment shutoff valve is opened 2 Repeat lighting procedure several times to purge all...

Страница 29: ...rm the pilot is spark ing and lights Check the two plastic connectors that plug in the face of the gas control valve Confirm the gas control valve is properly grounded to the module 1 Check electrical...

Страница 30: ...efective 1 Foreign matter between control valve and burner 2 Gas leak See Warning statement at top of page 1 Debris around burner air mixer 2 Improper vent configuration OBSERVED PROBLEM Gas odor even...

Страница 31: ...imum Inlet Supply Pressure 11 w c Maximum Inlet Supply Pressure 13 w c Orifice 50 WIRING DIAGRAM AUX Green Orange White Valve Black Red Control Module Black Brown Brown Red Black AC Power Adapter To R...

Страница 32: ...www fmiproducts com 125996 01C 32 PARTS MODELS V EADV36NE V EADV36PE AND V EADV42NE 1 2 6 6 7 15 3 9 10 5 8 11 4 3 12 13 14...

Страница 33: ...125856 02 Burner Assembly 36 Propane LP 1 126010 01 Burner Assembly 42 NG 1 5 126028 01 Plenum Assembly 36 1 126028 02 Plenum Assembly 42 1 6 122652 01 Door Latch 2 7 121431 01 Gasket 36 1 111913 02...

Страница 34: ...www fmiproducts com 125996 01C 34 PARTS MODELS V EADV36NE V EADV36PE AND V EADV42NE 11 3 6 4 5 1 7 9 15 8 13 12 14 23 16 17 18 19 20 21 22 22 2 9 10...

Страница 35: ...ifice 27 NG 1 7 14296 Brass Elbow 1 8 11214 Bulkhead Fitting 1 9 116573 01 Flat Washer 6 10 14399 Brass Elbow 2 11 114027 01 Grommet 12 125063 01 Gas Valve NG 1 125063 02 Gas Valve LP 1 13 125064 01 C...

Страница 36: ...lain 42 1 2 125860 01P Panel Left Porcelain 36 1 125862 01P Panel Left Porcelain 42 1 3 125860 02P Panel Right Porcelain 36 1 125862 02P Panel Right Porcelain 42 1 PARTS MODELS V EADV36NE V EADV36PE A...

Страница 37: ...lling have ready your name your address model and serial numbers of your fireplace how fireplace was malfunctioning purchase date Usually we will ask you to return the part to the factory SERVICE HINT...

Страница 38: ...______________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ____...

Страница 39: ...______________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ____...

Страница 40: ...C who will provide original factory replacement parts Failure to use original factory replacement parts voids this warranty Travel handling transportation diagnostic material laborandincidentalcostsas...

Отзывы: