FIREPLACE INSTALLATION

CHECK GAS TYPE

Use proper gas type for the fireplace unit you 

are installing. If you have conflicting gas types, 

do not install fireplace. See retailer where you 

purchased the fireplace for proper fireplace 

according to your gas type.

INSTALLING GAS PIPING TO 

FIREPLACE LOCATION

  WARNING:  A  qualified 

service  person  must  connect 

fireplace to gas supply. Follow 

all local codes.

  CAUTION:  For  propane/LP 

units,  never  connect  fireplace 

directly to the propane/LP sup

-

ply.  This  fireplace  requires  an 

external regulator (not supplied). 

Install the external regulator be

-

tween the fireplace and propane/

LP supply.

 WARNING: For natural 

gas, never connect fireplace to 

private  (non-utility)  gas  wells. 

This  gas  is  commonly  known 

as wellhead gas.

Installation Items Needed

Before  installing  fireplace,  make  sure  you 

have the items listed below.

•  external regulator (supplied by installer)

•  piping (check local codes)

•  sealant (resistant to propane/LP gas)

•  equipment shutoff valve *

•  test gauge connection *

•  sediment trap

•  tee joint

•  pipe wrench

•  approved flexible gas line with gas connec

-

tor (if allowed by local codes)

* An equipment shutoff valve with 1/8" NPT 

tap is an acceptable alternative to test gauge 

connection. Purchase the equipment shutoff 

valve from your retailer.

For propane/LP connection only, the installer 

must supply an external regulator. The exter-

nal regulator will reduce incoming gas pres-

sure. You must reduce incoming gas pressure 

to between 11" and 14" of w.c. pressure. If 

you do not reduce incoming gas pressure, 

fireplace regulator damage could occur. Install 

external regulator with the vent pointing down 

as shown in Figure 20. Pointing the vent down 

protects it from freezing rain or sleet.

 CAUTION: Use only new, 

black  iron  or  steel  pipe.  Inter

-

nally-tinned copper tubing may 

be used in certain areas. Check 

your  local  codes.  Use  pipe  of 

1/2" diameter or greater to allow 

proper gas volume to fireplace. 

If pipe is too small, undue loss 

of volume will occur.

Installation must include an equipment shutoff 

valve, union and plugged 1/8" NPT tap. Locate 

NPT tap within reach for test gauge hook up. 

NPT tap must be upstream from fireplace (see 

Figure 21, page 20).

IMPORTANT:

 Install main gas valve (equip-

ment shutoff valve) in an accessible location. 

The main gas valve is for turning on or shutting 

off the gas to the appliance.

Figure 20 - External Regulator with Vent 

Pointing Down (Propane/LP Only)

Propane/LP 

Supply Tank

External Regulator 

with Vent Pointing 

Down 

Содержание EADV36NE

Страница 1: ...nce Do not touch any electrical switch do not use any phone in your building Immediatelycallyourgassupplierfromaneighbor s phone Follow the gas supplier s instructions If you cannot reach your gas sup...

Страница 2: ...ation of Termination Cap 9 Requirements for the Commonwealth of Massachusetts 10 Venting Installation 11 Fireplace Installation 19 Operation 24 Gas Control Module System 25 Inspecting Burners 26 Clean...

Страница 3: ...or other flammable material on or near the appliance Never place any objects on the appliance Do not use this fireplace to cook food or burn paper or other flam mable material This fireplace reaches...

Страница 4: ...eplace SAFETY Continued 6 Have venting system inspected annually by a qualified service person If needed have venting system cleaned or repaired See Cleaning and Maintenance page 26 7 Do not use any s...

Страница 5: ...ither vertical or horizontal applications This fireplace may be installed in any room of your house provided all local codes and these installation instructions are followed Each time you turn on your...

Страница 6: ...n back sides or top of your fireplace except where standoff spacers are integrally attached If standoff spacers are attached to your fireplace these spacers can be placed directly against wall or fram...

Страница 7: ...stallation All minimum clearances must be met If you are using a separate combustible man tel piece refer to Figure 5 for proper instal lation height You can install noncombustible mantels at any heig...

Страница 8: ...ireplace Dimensions 21 1 8 36 25 1 8 42 29 36 34 3 4 42 12 36 13 3 4 42 4 1 2 41 36 48 42 20 1 2 36 24 42 44 36 48 42 38 7 8 36 43 3 4 42 1 1 2 35 36 42 42 43 36 50 42 1 1 33 36 37 42 3 1 4 11 36 11 1...

Страница 9: ...n US if greater than 50 000 36 91 cm in Canada if greater than 100 000 K clearance to a mechanical air supply inlet In Canada 6 ft 1 83m minimum In US 3 ft 91 cm above if within 10 ft 3 m horizontally...

Страница 10: ...ctly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than 1 2 in size GAS VENT DIRECTLY BELOW KEE...

Страница 11: ...pe components and terminations The venting system must terminate on the outside of the structure and can not be at tached to a chimney or flue system serving a separate solid fuel or gas burning appli...

Страница 12: ...gs indentations These lugs will slide straight into match ing slots on male ends of adjacent pipes Push pipe sections together and twist one section clockwise approximately one quarter turn until sect...

Страница 13: ...Siding standoff must sit flush against exterior fascia material 6 Connecting Vent Cap with Horizontal Vent Pipe Slide wall firestop over vent pipe before connecting horizontal run to vent cap see Figu...

Страница 14: ...ation Configurations Figures 14 and 15 page 15 show a configu ration for venting with horizontal termination with a chart of critical minimum and maximum dimensions which MUST be met If using a ventin...

Страница 15: ...lbow Wall Firestop H 90 Elbow V 90 Elbow Horizontal High Wind Square Termination 76 Min 42 73 Min 36 1 Pipe Min On Horizontal Run V Vertical Minimum Required Vertical Pipe H Horizontal Maximum 33 2 ft...

Страница 16: ...e 45 elbows instead of 90 elbows The 45 elbow offers less restriction to the flow of flue gases 5 Place flashing over pipe section s extending through roof Secure base of flashing to roof and framing...

Страница 17: ...n Double Wall Pipe Galvanized P58 48 48 Section Double Wall Pipe Galvanized PA58 712 Adjustable 7 12 Section Double Wall Pipe Galvanized E58 45 45 Elbow Galvanized E58 90 90 Elbow Galvanized HTS 58 Ho...

Страница 18: ...ATION Continued Figure 18 Vertical Venting Configuration Vertical Venting V 40 max Figure 19 Vertical Venting Configuration Using Two 90 Elbows Venting with Two 90 Elbows Vertical V1 Horizontal H 6 mi...

Страница 19: ...nt shutoff valve with 1 8 NPT tap is an acceptable alternative to test gauge connection Purchase the equipment shutoff valve from your retailer For propane LP connection only the installer must supply...

Страница 20: ...in Figure 21 Locate sediment trap drip leg where it is within reach for cleaning Install in piping system between fuel supply and fireplace Locate sediment trap drip leg where trapped matter is not li...

Страница 21: ...luid to all joints Bubbles forming show a leak Correct all leaks at once 5 Reconnect fireplace and equipment shutoff valve to gas supply Check recon nected fittings for leaks Test Pressures Equal To o...

Страница 22: ...26 Removing Replacing Door Removing Glass Door If replacement of glass is necessary the entire frame assembly must be replaced Gloves must be worn when removing replacing glass door If glass is broke...

Страница 23: ...an open flame to check for a leak Apply noncorrosive leak de tection fluid to joints Bubbles forming show a leak Correct leaks at once CAUTION The gas supply shall be shut off prior to discon necting...

Страница 24: ...1 2 Turn off all electric power to fireplace 3 Turn safety shutoff switch to the OFF position Figure 29 Turning Equipment Shutoff Valve to the OFF Position Equipment Shutoff Valve 4 Remove face trim p...

Страница 25: ...wing posi tive and negative directions 4 Replace battery cover onto remote control unit CONTINUOUS PILOT FEATURE This allows the change from a spark to pilot system to a standing pilot system 1 There...

Страница 26: ...CK UP This fireplace is equipped with a battery back up If the power was to go out on the fireplace the battery back up allows the fireplace to remain operational Make sure to periodically check the c...

Страница 27: ...ac CAUTION Do not vacuum if pieces are hot Use only glass door replacement intended for this fireplace see Replacement Parts page 37 for detail on ordering No substitutions may be made See Removing Re...

Страница 28: ...ve is not opening 7 No power to unit or ignition module REMEDY 1 Check to see if you have gas supply and that equip ment shutoff valve is opened 2 Repeat lighting procedure several times to purge all...

Страница 29: ...rm the pilot is spark ing and lights Check the two plastic connectors that plug in the face of the gas control valve Confirm the gas control valve is properly grounded to the module 1 Check electrical...

Страница 30: ...efective 1 Foreign matter between control valve and burner 2 Gas leak See Warning statement at top of page 1 Debris around burner air mixer 2 Improper vent configuration OBSERVED PROBLEM Gas odor even...

Страница 31: ...imum Inlet Supply Pressure 11 w c Maximum Inlet Supply Pressure 13 w c Orifice 50 WIRING DIAGRAM AUX Green Orange White Valve Black Red Control Module Black Brown Brown Red Black AC Power Adapter To R...

Страница 32: ...www fmiproducts com 125996 01C 32 PARTS MODELS V EADV36NE V EADV36PE AND V EADV42NE 1 2 6 6 7 15 3 9 10 5 8 11 4 3 12 13 14...

Страница 33: ...125856 02 Burner Assembly 36 Propane LP 1 126010 01 Burner Assembly 42 NG 1 5 126028 01 Plenum Assembly 36 1 126028 02 Plenum Assembly 42 1 6 122652 01 Door Latch 2 7 121431 01 Gasket 36 1 111913 02...

Страница 34: ...www fmiproducts com 125996 01C 34 PARTS MODELS V EADV36NE V EADV36PE AND V EADV42NE 11 3 6 4 5 1 7 9 15 8 13 12 14 23 16 17 18 19 20 21 22 22 2 9 10...

Страница 35: ...ifice 27 NG 1 7 14296 Brass Elbow 1 8 11214 Bulkhead Fitting 1 9 116573 01 Flat Washer 6 10 14399 Brass Elbow 2 11 114027 01 Grommet 12 125063 01 Gas Valve NG 1 125063 02 Gas Valve LP 1 13 125064 01 C...

Страница 36: ...lain 42 1 2 125860 01P Panel Left Porcelain 36 1 125862 01P Panel Left Porcelain 42 1 3 125860 02P Panel Right Porcelain 36 1 125862 02P Panel Right Porcelain 42 1 PARTS MODELS V EADV36NE V EADV36PE A...

Страница 37: ...lling have ready your name your address model and serial numbers of your fireplace how fireplace was malfunctioning purchase date Usually we will ask you to return the part to the factory SERVICE HINT...

Страница 38: ...______________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ____...

Страница 39: ...______________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ____...

Страница 40: ...C who will provide original factory replacement parts Failure to use original factory replacement parts voids this warranty Travel handling transportation diagnostic material laborandincidentalcostsas...

Отзывы: