background image

www.fmiproducts.com

125079-01F

18

FIREPLACE INSTALLATION

CHECK GAS TYPE

Use proper gas type for the fireplace unit you 

are installing. If you have conflicting gas types, 

do not install fireplace. See retailer where you 

purchased the fireplace for proper fireplace 

according to your gas type.

INSTALLING GAS PIPING TO 

FIREPLACE LOCATION

  WARNING:  A  qualified 

service  person  must  connect 

fireplace to gas supply. Follow 

all local codes.

  CAUTION:  For  propane/LP 

units,  never  connect  fireplace 

directly to the propane/LP sup

-

ply.  This  fireplace  requires  an 

external regulator (not supplied). 

Install the external regulator be

-

tween the fireplace and propane/

LP supply.

 WARNING: For natural 

gas, never connect fireplace to 

private  (non-utility)  gas  wells. 

This  gas  is  commonly  known 

as wellhead gas.

Installation Items Needed

Before  installing  fireplace,  make  sure  you 

have the items listed below.

•  external regulator (supplied by installer)

•  piping (check local codes)

•  sealant (resistant to propane/LP gas)

•  equipment shutoff valve *

•  test gauge connection *

•  sediment trap

•  tee joint

•  pipe wrench

•  approved flexible gas line with gas connec

-

tor (if allowed by local codes)

* An equipment shutoff valve with 1/8" NPT 

tap is an acceptable alternative to test gauge 

connection. Purchase the equipment shutoff 

valve from your retailer.

For propane/LP connection only, the installer 

must supply an external regulator. The exter

-

nal regulator will reduce incoming gas pres

-

sure. You must reduce incoming gas pressure 

to between 11" and 14" of w.c. pressure. If 

you  do  not  reduce  incoming  gas  pressure, 

fireplace regulator damage could occur. Install 

external regulator with the vent pointing down 

as shown in Figure 21. Pointing the vent down 

protects it from freezing rain or sleet.

 CAUTION: Use only new, 

black  iron  or  steel  pipe.  Inter

-

nally-tinned copper tubing may 

be used in certain areas. Check 

your  local  codes.  Use  pipe  of 

1/2" diameter or greater to allow 

proper gas volume to fireplace. 

If pipe is too small, undue loss 

of volume will occur.

Installation must include an equipment shutoff 

valve, union and plugged 1/8" NPT tap. Locate 

NPT tap within reach for test gauge hook up. 

NPT tap must be upstream from fireplace (see 

Figure 22, page 19).

IMPORTANT:

 Install main gas valve (equip

-

ment shutoff valve) in an accessible location. 

The main gas valve is for turning on or shutting 

off the gas to the appliance.

Figure 21 - External Regulator with Vent 

Pointing Down (Propane/LP Only)

Propane/LP 

Supply Tank

External Regulator 

with Vent Pointing 

Down 

Содержание DVF-36LT-D

Страница 1: ...liance Do not touch any electrical switch do not use any phone in your building Immediatelycallyourgassupplierfromaneighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a quali fied installer service agency or the gas supplier INSTALLER Leave this manual with the appliance CONSUMER Retain...

Страница 2: ...ng may lead to death This vented gas fireplace is a sealed combus tion gas fireplace designed for residential ap plications This fireplace must be installed with FMI PRODUCTS LLC vent pipe components and terminations This fireplace complies with the National Safety Standards and is listed and tested by PFS Corporation to ANSI Z21 50 CSA 2 22 standard as vented gas fireplace NOTICE Decorative produ...

Страница 3: ... can be dangerous Do not modify this fireplace under any circumstances Any parts removed for servicing must be replaced prior to operat ing fireplace WARNING Do not use a blower insert heat exchanger insert or other accessory not approved for use with this fireplace WARNING This appliance is only for use with the type of gas indicated on the rating plate This appliance is not convertible for use w...

Страница 4: ...re servicing installing or repairing Only a qualified service person should install service or repair this fireplace Have fire place inspected annually by a qualified service person 5 You must keep control compartments burners and circulating air passages clean More frequent cleaning may be needed due to excessive lint and dust from carpeting bedding material etc Turn off the gas valve and pilot l...

Страница 5: ...al codes and these installation instructions are followed Each time you turn on your fireplace you may notice some amount of condensation on the inside of the fireplace glass This is normal and will disappear after 10 20 minutes of operation Your direct vent gas fireplace system fireplace and venting is a balanced and sealed gas operating unit It requires ap proximately 10 20 minutes of operating ...

Страница 6: ... fireplace is designed to be used in zero clearance installations Wall or fram ing material can be placed directly against any exterior surface on back sides or top of your fireplace except where standoff spacers are integrally attached If standoff spacers are attached to your fireplace these spacers can be placed directly against wall or framing material See framing details page 7 When locating t...

Страница 7: ...ou may run system s circulat ingblowerwhileusingfireplace This will help circulate the heat throughout the house FRAMING AND FINISHING Figure 5 shows typical framing of this fire place Figure 6 shows framing for corner installation All minimum clearances must be met If you are using a separate combustible man tel piece refer to Figure 7 for proper instal lation height You can install noncombustibl...

Страница 8: ...in US if greater than 50 000 36 91 cm in Canada if greater than 100 000 K clearance to a mechanical air supply inlet In Canada 6 ft 1 83m minimum In US 3 ft 91 cm above if within 10 ft 3 m horizontally L clearance above paved side walk or a paved driveway located on public property 84 213 3 cm minimum M clearance under veranda porch deck 12 30 5 cm minimum N clearance above a roof shall extend a m...

Страница 9: ...ectly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than 1 2 in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless upon inspection the inspect...

Страница 10: ...ipe components and terminations The venting system must terminate on the outside of the structure and can not be at tached to a chimney or flue system serving a separate solid fuel or gas burning appliance A direct vent appliance must have its own venting system DO NOT common vent this appliance These models are approved to be vented either horizontally through an outside wall or vertically throug...

Страница 11: ...dentations These lugs will slide straight into match ing slots on male ends of adjacent pipes Push pipe sections together and twist one section clockwise approximately one quarter turn until sections are fully locked see Figure 9 Note Horizontal runs of vent must be sup ported every three feet Use wall straps for this purpose 3 Assemble desired combination of pipe and elbows to fireplace flue coll...

Страница 12: ... Siding standoff must sit flush against exterior fascia material 6 Connecting Vent Cap with Horizontal Vent Pipe Slide wall firestop over vent pipe before connecting horizontal run to vent cap see Figure 13 Figure 11 Installing Horizontal Vent Cap Noncombustible Exterior Wood Screw Vent Cap Figure 12 Installing Siding Standoff Combustible Exterior Wall Cut Siding Away to Fit Standoff Wood Screw Sc...

Страница 13: ...ermination Configurations Figures 15 and 16 show a configuration for venting with horizontal termination with a chart of critical minimum and maximum dimensions which MUST be met If using a venting configuration of only hori zontal venting with no vertical run a rise for every 12 of run toward the termination is required NOTICE Donotsealtermination cap to vent pipe Cap must be removable for vent i...

Страница 14: ...D FLOOR INSTALLATION Recommended Applications Through the wall using round or square termination NOT FOR CORNER INSTALLATION Figure 15 Horizontal Termination Using One 90 Elbow Wall Firestop H 90 Elbow V 90 Elbow Horizontal High Wind Square Termination 76 Min 42 73 Min 36 1 Pipe Min On Horizontal Run V Vertical Minimum Required Vertical Pipe H Horizontal Maximum 33 2 ft 7 ft 45 3 ft 11 ft 57 4 ft ...

Страница 15: ...45 elbows instead of 90 elbows The 45 elbow offers less restriction to the flow of flue gases 5 Place flashing over pipe section s extend ing through roof Secure base of flashing to roof and framing with roofing nails Be sure roofing material overlaps top edge of flashing as shown in Figure 17 There must be a 1 clearance from vent pipe to combustible materials Vent Termination Chart Minimum Height...

Страница 16: ... P58 48 48 Section Double Wall Pipe Galvanized PA58 712 Adjustable 7 12 Section Double Wall Pipe Galvanized E58 45 45 Elbow Galvanized E58 90 90 Elbow Galvanized HTS 58 Horizontal Square Termination Galvanized HHT 58 High Wind Round Termination Galvanized VT 58 Vertical Round Termination Galvanized SC 58 Storm Collar Galvanized WF 58 Wall Firestop Galvanized RF 58 6 Roof Flashing 0 to 6 12 Pitch G...

Страница 17: ...nting Configuration Vertical Venting V 40 max V1 V2 40 max Figure 20 Vertical Venting Configuration Using Two 90 Elbows Venting with Two 90 Elbows Vertical V1 Horizontal H 6 min 12 max 7 min 18 max 8 min 20 max 20 max 20 max Note Install Restrictor into Inner Collar of Fireplace as Shown ...

Страница 18: ...ent shutoff valve with 1 8 NPT tap is an acceptable alternative to test gauge connection Purchase the equipment shutoff valve from your retailer For propane LP connection only the installer must supply an external regulator The exter nal regulator will reduce incoming gas pres sure You must reduce incoming gas pressure to between 11 and 14 of w c pressure If you do not reduce incoming gas pressure...

Страница 19: ... in Figure 22 Locate sediment trap drip leg where it is within reach for cleaning Install in piping system between fuel supply and fireplace Locate sediment trap drip leg where trapped matter is not likely to freeze A sediment trap traps moisture and contaminants This keeps them from going into fireplace gas controls If sediment trap drip leg is not installed or is in stalled wrong fireplace may n...

Страница 20: ...fluid to all joints Bubbles forming show a leak Correct all leaks at once 5 Reconnect fireplace and equipment shutoff valve to gas supply Check recon nected fittings for leaks Test Pressures Equal To or Less Than 1 2 PSIG 3 5 kPa 1 Close equipment shutoff valve see Fig ure 24 2 Pressurize supply piping system by either opening propane LP supply tank valve for propane LP gas fireplace or opening ma...

Страница 21: ...nto frame before removing 1 Remove screens if installed 2 Open bottom access panel 3 Unlock 2 door latches on bottom of firebox 4 Tilt open glass door 45 from the bottom of firebox and lift up to release door from firebox top retainer see Figure 27 Replacing Glass Door 1 Position door frame in front of firebox opening with bottom of door tilted away from firebox see Figure 27 2 Hook top flange of ...

Страница 22: ...gure 29 Installing Lava Rock Lava Rock Figure 28 Installing Loose Logs Figure 28a Installing Loose Log 1 Figure 28b Installing Loose Logs 2 and 3 Loose Log 3 Loose Log 1 Loose Log 2 Loose Log 2 Loose Log 3 Loose Log 1 Underneath Log 2 Glowing Embers 3 Pull glowing ember material apart into pieces no larger than a dime Place these pieces loosely and sparingly directly onto exposed burner ports Figu...

Страница 23: ...he glowing ember ap pearance as the flame touches the ember flakes Do not block burner ports or pilot ports by overlapping ember flakes in one area It is not necessary to use all ember material provided 6 Place scrap log pieces randomly behind grate as shown in Figure 31 on lava rock and around but not on burner ports 7 Place grate in front of logs as shown in Figure 31 Be sure grate is balanced s...

Страница 24: ... 1 Using a 5 16 hex socket wrench or nut driver connect or disconnect flexible gas line and control valve see Figure 32 2 After connecting gas line to control valve always test for leaks REMOVING LOG SET BURNER MODULE WARNING Neveruseanopen flame to check for a leak Apply noncorrosiveleakdetectionfluid to joints Bubbles forming show a leak Correct leaks at once CAUTION The gas supply shall be shut...

Страница 25: ...ing Equipment Shutoff Valve to the OFF Position Equipment Shutoff Valve 1 STOP Read the safety information in column 1 2 Turn off all electric power to fireplace 3 Turn safety shutoff switch to the OFF position 4 Remove center brick control cover 5 Turn equipment shutoff valve clockwise to the OFF position see Figure 34 Do not force 6 Wait five 5 minutes to clear out any gas Then smell for gas inc...

Страница 26: ...Pilot Off On Switch Remote Off Switch ADJ S Pilot Connection I Pilot Connection AF 4000 MOD Module Rt Side Figure 35 Gas Module Right Side 1 There is a switch located on the right side of the module that reads REMOTE OFF Figure 36 2 When the remote off switch is in the OFF position the burner will operate from the rocker switch or wall switch connected to the two BROWN wires on the module 3 When t...

Страница 27: ...SEMBLY The pilot assembly is factory preset for the proper flame Alterations may have occurred during shipping and handling The pilot is located on right hand side of burner The flame must envelope 1 4 of top of the ignitor sensor and grounding stem If your pilot assembly does not meet these requirements Turn the adjustment screw marked PILOT clockwise to decrease or counterclockwise to increase t...

Страница 28: ...e see Replacement Parts page 33 for detail on ordering No substitutions may be made See Removing Replacing Glass Door page 21 for instructions for re placing glass doors CLEANING AND MAINTENANCE Continued WARNING Do not operate fireplace with glass door un latched removed cracked or broken PILOT AND BURNERS Remove material before cleaning burners and replace when cleaning is complete Burner and co...

Страница 29: ...lve is not opening 7 No power to unit or ignition module REMEDY 1 Check to see if you have gas supply and that equip ment shutoff valve is opened 2 Repeat lighting procedure several times to purge all air out of lines If after re peated attempts appliance does not light call for quali fied service and repair 3 Remove debris and dirt inspect and clean any other possible obstructions 4 Contact your ...

Страница 30: ...lights Check the two plastic connectors that plug in the face of the gas control valve Confirm the gas control valve is properly grounded to the module 1 Check electrical connec tions 1 Clean and adjust pilot flame for maximum flame im pingement on thermopile 2 Have vent system inspect ed including termination cap Remove any restriction or obstruction 1 This is normal with most fireplaces If noise...

Страница 31: ...s blocked 3 Improper venting or exces sive blockage 4 Excessive amounts of em bers and pan material OBSERVED PROBLEM Gas odor even when gas control valve is off Gas odor during combustion Glass soots Dark residue on logs or inside of fireplace REMEDY 1 Locate and correct all leaks see Checking Gas Con nections page 20 2 Replace control valve 1 Take apart gas tubing and remove foreign matter 2 Loca...

Страница 32: ...PS D DVF 36PH D DVF 36PSR D DVF 36PHR D Rating 47 000 28 000 Btu hr Gas Type Propane LP Gas Only Ignition Electronic Manifold Pressure 10 w c Minimum Inlet Supply Pressure 11 w c Maximum Inlet Supply Pressure 13 w c Front Orifice 53 Rear Orifice 53 DVF 42PLT D DVF 42PS D DVF 42PH D DVF 42PSR D DVF 42PHR D Rating 53 000 28 000 Btu hr Gas Type Propane LP Gas Only Ignition Electronic Manifold Pressur...

Страница 33: ... When Gas Pressure Is Too Low pilot will not stay lit burners will have delayed ignition fireplace will not produce specified heat propane LP gas supply might be low pro pane LP units only You may feel your gas pressure is too low If so contact your local gas supplier ACCESSORIES Purchase these accessories from your local dealer If they can not supply these accessories call FMI PRODUCTS LLC at 1 8...

Страница 34: ...D DVF 42PS D DVF 42NH D DVF 42PH D DVF 36NSR D DVF 36PSR D DVF 36NHR D DVF 36PHR D DVF 42NSR D DVF 42PSR D DVF 42NHR D DVF 42PHR D DVF 36NLT D DVF 36PLT D DVF 42NLT DAND DVF 42PLT D 1 2 3 8 32 32 33 36 32 42 8 9 10 11 17 22 25 26 27 7 4 5 12 16 18 19 20 29 31 30 23 24 28 21 13 14 15 38 3 6 34 35 36 37 ...

Страница 35: ...oor Latch 2 9 Firebox Leg 4 10 Firebox Bottom 1 11 121431 01 Gasket 36 1 111913 02 Gasket 42 1 12 122919 01 Draft Diverter 1 13 Air Exchange 1 14 5 Gasket 1 15 5 Inner Connector 1 16 A E Insulation 1 17 Firebox Surround 1 18 Firebox Top 1 19 Relief Assembly 2 20 Relief Bracket 4 21 Top Plenum 1 22 Rear Plenum 1 23 5 Gasket 1 24 Connector 8 x 3 25 1 25 121295 01 36 Fireplace Surround 1 121302 01 42...

Страница 36: ...21 22 23 25 26 27 28 29 29 PARTS M O D E L S D V F 3 6 N S D D V F 3 6 P S D D V F 3 6 N H D D V F 3 6 P H D DVF 42NS D DVF 42PS D DVF 42NH D DVF 42PH D DVF 36NSR D DVF 36PSR D DVF 36NHR D DVF 36PHR D DVF 42NSR D DVF 42PSR D DVF 42NHR D DVF 42PHR D DVF 36NLT D DVF 36PLT D DVF 42NLT D AND DVF 42PLT D ...

Страница 37: ...Dia x 24 1 16 Pilot Bracket 1 17 125063 01 Gas Valve NG 1 125063 02 Gas Valve LP 1 18 111800 01 Screw 10 24 x 0 375 Self Thread 2 19 125064 01 Control Module 1 20 125067 01 Power Module 1 21 14396 Connector 3 8 Tube x 3 8 MPT 1 22 116786 01 Brass Fitting 1 2 Flare x 3 8 MPT 1 23 125061 01 Valve Module Bracket 1 24 Log Assembly 36 1 Log Assembly 42 1 25 125062 01 Valve Bracket 1 26 125068 01 Batter...

Страница 38: ... Stacked 42 Ivory Tan 1 125089 03 Left Refractory Stacked 36 Ivory Tan 1 3 125128 03 Right Refractory Herringbone 42 Ivory Tan 1 125092 03 Right Refractory Herringbone 36 Ivory Tan 1 125127 03 Right Refractory Stacked 42 Ivory Tan 1 125091 03 Right Refractory Stacked 36 Ivory Tan 1 4 125129 03 Left Front Refractory 42 Ivory Tan 1 125093 03 Left Front Refractory 36 Ivory Tan 1 5 125131 03 Center Fr...

Страница 39: ... Refractory Stacked 42 Warm Red 1 125091 02 Right Refractory Stacked 36 Warm Red 1 4 125129 02 Left Front Refractory 42 Warm Red 1 125093 02 Left Front Refractory 36 Warm Red 1 5 125131 02 Center Front Refractory 42 Warm Red 1 125095 02 Center Front Refractory 36 Warm Red 1 6 125130 02 Right Front Refractory 42 Warm Red 1 125094 02 Right Front Refractory 36 Warm Red 1 D V F 4 2 N P L T D D V F 3 6...

Страница 40: ...LC who will provide original factory replacement parts Failure to use original factory replacement parts voids this warranty Travel handling transportation diagnostic material laborandincidentalcostsassociatedwithwarrantyrepairs unless expressly covered by this warranty are not reimbursable under this warranty and are the responsibility of the owner All warranty will be voided if this product is u...

Отзывы: