EPE2-Controller for Meter Draining System
EPE2
Installation Manual
MN F08 003 US /
DOK-450E
Rev. 1.03 / JS / jp / March 2010
21
After carrying out the residue removal operation (for this period the MultiFlow is switched off
by the residue removal controller) the MultiFlow starts up again and the driver must repeat
the drop pre-set entries. The query as to whether residue removal has been carried out is
this time confirmed by pressing the
<F1>
key. The confirmation is saved in the logbook.
If parameter
3.1.8.5.1
(residue removal control) is set to
“3”
and/or
“4”
the wet leg sensor
connected to the EPE2 is continuously monitored to check whether residue removal has
been carried out on the measuring system (complete discharge and refilling). If residue re-
moval is detected, this is recorded in the MultiFlow logbook. If residue discharge has been
detected, the residue removal message is not displayed when switching between diesel and
heating oil / heating oil with additives. If residue removal has not been detected, the corre-
sponding message is displayed. Delivery in this case is not started until the measuring sys-
tem has undergone residue removal. The MultiFlow does not need to be restarted in this
case.
If parameter
3.1.8.5.1
is set to
“4”
it is also pos-
sible to control the residue removal from the
measuring system from the MultiFlow using a
residue removal pump. A suitable pump must be
connected to the
EPE2
output for this purpose.
The "Autom. residue removal" menu item (
menu
8
) can be used for removal of residue from the
measuring system. It is controlled in accordance
with the maximum operating time (parameter
3.1.8.5.2
), with the
<START>
and
<STOP>
keys.
Parameters: Menu 8
No.
Name
Seal
K Factory
setting
Meaning
8
Autom.res.remov
al
D
Control of a residue discharge pump con-
nected to the EPE2. For this purpose the
"EPE2 automatic" mode must be activated
(parameter 3.1.8.5.1).
Seal sense:
K Priority
Meaning
2 M
aster
High security level due to additional checksum;
parameter transfer
from
the chip card only possible when
seal is broken
!
3 M
aster
Medium security level
x D
river
Lowest security level; parameters which are
not
saved on the chip card
Autom.res.removal
-------------------
Press START to
continue
Press STOP to exit
-------------------
Residue removal
timeout
. . . . .
9 min