Set Up MAS Relay Module
Instruction
MRM 01 is an optional output unit containing four relays. It enables communication for
individual monitoring channel alarms (A and/or B alarms) to speci
fi
c relays and LEDs
on the relay module(s).
Follow these steps to set up the MAS Relay Module, MRM 01:
1.
Make sure that the communication with the relay module(s) is activated. See
section
Con
fi
gure Communication (RS-485, Modbus)
.
2.
Click Setup – General con
fi
guration – Relay Modules, MRM 01.
Result:
The Relay Modules, MRM 01 window is opened.
3.
• Activate a module by ticking
Activate
.
• Select the monitoring channels that should be associated with the each of the four
relays on the module.
• Select the Action priority for each relay, that is, if the relay should communicate an
A-alarm or a B-alarm on the speci
fi
ed monitoring channel.
4.
Repeat the settings in step 3 for all connected modules.
5.
Click Update.
97