Wiring, Midrange Pumps, SubCab 12–lead Sensor Cable, Alternative 2
Sensor/Component
Sensor cable, no.
1)
Base unit terminal
block, no.
• Supply, ground
11
36
• Supply, 12V +
12
35
(Screen)
If applicable, attach
screen to ground
terminals in the
• pump top
and
• electrical cabinet.
NOTE!
1)
If the sensor cable contains a green-yellow lead, that lead should
not
be connected.
2)
VIS 10 is not applicable to pump type 3153.
3)
Communication port 37-38 for RS-485 is common to both pump memory and
operator panel.
Terminal
Diagram
This is a wiring diagram of the sensor terminals (section 2) used for a SubCab 12-lead
sensor cable, 2 (vibration sensor, no leakage sensor in junction box):
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
VIS 10
+
Gnd
+
+
Gnd
Terminal
Description
This table describes the sensor terminals (section 2) used for a SubCab 12-lead sensor
cable, 2 (vibration sensor, no leakage sensor in junction box):
Terminal
Number
Type
Description
19
Not used
18
+
Vibration or optional sensor input, 4-20 mA
17
+
Leakage in inspection chamber, FLS
16
Ground
Leakage in inspection chamber/vibration, common ground
40
Содержание MAS 711
Страница 1: ...Installation and Operation MAS 711 895115 10...
Страница 2: ......
Страница 5: ...Overview 5...
Страница 6: ......
Страница 8: ......
Страница 14: ......
Страница 22: ......
Страница 98: ......
Страница 108: ......
Страница 142: ......
Страница 148: ......
Страница 150: ...www flygt com Installation and Operation MAS 711 895115 10 20071212 ITT Flygt AB Printed in Sweden...