31
VIBRONET Installation 06.2016
Connecting a MUX string line to the basic unit
The MUX string line is connected via the shock pulse module (VIB
5.815-3) to the VIBRONET Signalmaster basic unit.
• Open the VIBRONET Signalmaster cabinet.
• Open a suitable fitting M20 on the bottom of the cabinet and remo-
ve the sealing.
• Lay a cable loop (approx. 30 cm).
• Insert the open cable end through the open fitting.
• Prepare the cable end for connection:
• Strip off the outer sheath of the triaxial cable, so that you can
apply the outer shielding to the shield clamp in the cabinet.
• Crimp on a straight TNC connector (e.g. VIB 93022).
• Connect the TNC connector to the corresponding TNC socket at
the shock pulse module ('String 1 ... String 3').
• Apply the outer shielding to the shield clamp.
• Tighten down the open fitting.
Traixial cable and crimping
Details on the connection of triaxial cables and on crimping are given
in chapter 8 (see 'Triaxial cable', page 61), (see 'Instructions for
crimping (BNC/ TNC)', page 60).
Installation
Threaded fittings M20 for MUX
string line
S
P
M
B
U
S
S
Y
S
T
E
M
B
U
S
Str
ing 1
Str
ing 2
Str
ing 3
100
m V
/g
max. 6 MUX per string line
3x TNC for
MUX string line
Triaxial
Coaxial
VIBRONET Signalmaster
basic unit, VIB 5.802
Shock pulse module,
VIB 5.815-3
Shield clamp
for outer shielding