13
VIBRONET Installation 06.2016
Technical data
Connection modules for VIBRONET MUX - VIB 8.31x
PARAMETER
VIB 8.310 /
VIB 8.310 EX
VIB 8.312
VIB 8.313 /
VIB 8.313-1 EX
VIB 8.314 EX
Electrical
Input
Pt100 temperature probe
Current / Voltage
Inductive
proximity sensor
CLD-type
accelerometer
Output
Digitalized current signal
Measurment range
-40C° ...+ 250°C
0 ...20mA / -10...+10V
-
-
Sensitivity
0,385 Ohm/°C
--
2 mA
--
Current output to sensor
< 2 mA
--
< 4 mA
--
Voltage output to sensor
< 1 V
< 2.2 V (at connector, current module)
10 kOhm (Input resistance, voltage module)
< 8 V
--
Balancing resistor
--
100 Ohm
General
Operation temperature
-20C° ...+ 80°C (... +70°C with EX version)
-40C° ...+ 70°C
Dimensions
46 x 50 x 2 mm
* only for installation in hazardous areas