Electrical Tester

 

 

Symbols

 

 

  

Symbols 

Table 1 describes the symbols that appear on the Tester or in this document. 

Table 1. Symbols 

Symbol Explanation Symbol  Explanation 

W

 

WARNING - RISK OF DANGER. Consult 
user documentation. 

X

 

WARNING. HAZARDOUS VOLTAGE. Risk of 
electric shock. 

T

 

Double insulated 

 

Earth 

)

 

Certified by CSA Group to North American 
safety standards. 

R

 

Continuity beeper  

 

Measurement Category III is applicable to 
test and measuring circuits connected to the 
distribution part of the building’s low-voltage 
MAINS installation. 

 

Measurement Category IV is applicable to test 
and measuring circuits connected at the source 
of the building’s low-voltage MAINS installation. 

~

 

This product complies with the WEEE Directive marking requirements. The affixed label indicates that you 
must not discard this electrical/electronic product in domestic household waste. Product Category: With 
reference to the equipment types in the WEEE Directive Annex I, this product is classed as category 9 
"Monitoring and Control Instrumentation" product. Do not dispose of this product as unsorted municipal 
waste. 

Contacting Fluke 

To contact Fluke, call one of the following telephone numbers: 

 

Technical Support USA: 1-800-44-FLUKE (1-800-443-5853) 

 

Calibration/Repair USA: 1-888-99-FLUKE (1-888-993-5853) 

 

Canada: 1-800-36-FLUKE (1-800-363-5853) 

 

Europe: +31 402-675-200 

 

Japan: +81-3-6714-3114 

 

Singapore: +65-6799-5566 

 

China: +86-400-921-0835 

 

Anywhere in the world: +1-425-446-5500 

Or, visit Fluke's website at 

www.fluke.com

To register your product, visit

 http://register.fluke.com

To view, print, or download the latest manual supplement, visit 

http://us.fluke.com/usen/support/manuals

Содержание EW-26046-44

Страница 1: ... Information A Warning identifies conditions and procedures that are dangerous to the user A Caution identifies conditions and procedures that can cause damage to the Product or the equipment under test XWWarning To avoid possible electric shock or personal injury follow these guidelines Use the Tester only as specified in this document otherwise the protection provided by the Tester may be impair...

Страница 2: ...n working in hazardous areas Use caution when working above 30 V ac rms 42 V peak or 60 V dc Such voltages pose a shock hazard When using probes keep fingers away from the probe tips Connect the common test lead before connecting the live test lead When disconnecting the test leads disconnect the live test lead first Do not operate the Tester with the battery door or portions of the cover removed ...

Страница 3: ...ive marking requirements The affixed label indicates that you must not discard this electrical electronic product in domestic household waste Product Category With reference to the equipment types in the WEEE Directive Annex I this product is classed as category 9 Monitoring and Control Instrumentation product Do not dispose of this product as unsorted municipal waste Contacting Fluke To contact F...

Страница 4: ... This will be displayed on the LED and LCD T PRO Duty Cycle Indefinitely for voltages up to 240 V For voltages between 240 V to 600 V the duty cycle is 30 s on 300 s off For voltages above 240 V the Tester must connect to a voltage source only for a MAXIMUM of 30 s and then disconnect for a MINIMUM of 300 s Voltage Hazard LED LEDs turn on voltages 30 V ac dc 35 LEDs LEDs turn on between 70 and 100...

Страница 5: ...ompartment Do not operate the Tester with the battery door or portions of the cover removed or loosened To replace the batteries do the following 1 Remove the battery door by using a flat blade screwdriver to turn the battery door fastener one quarter turn counterclockwise 2 Observing proper polarity replace the batteries with two new AAA alkaline batteries 3 Replace the battery door and secure it...

Страница 6: ...e the batteries WCaution Although the Tester may be used with depleted batteries replace depleted batteries immediately to avoid Tester damage from battery acid leakage To perform the self test short the two probes The self test lights all LEDs and all LCD segments T PRO The beeper sounds unless disabled and the Tester switches to continuity mode To complete the self test measure a known voltage b...

Страница 7: ...zard volts ac and dc and continuity Testing the Backlight T PRO Use the following procedure to test the backlight 1 Insert the test probes into a voltage source of 10 V ac or dc 2 Observe that the backlight lights Testing the Audible Signal Use the following procedure to test the audible signal 1 Short the UUT test probes together The beeper should sound 2 If inactivated press and hold until you h...

Страница 8: ...ge Measurement dc V 0 50 V 10 5 V 12 V LED On 10 1 to 10 9 6 10 5 V 12 V LED On 10 1 to 10 9 7 48 V LED On 12 48 V LED On Hazard On Beeper Vibration On 46 8 to 49 2 8 48 V LED On 12 48 V LED On Hazard On Beeper Vibration On 46 8 to 49 2 9 dc V 0 600 V 55 V LED On 12 48 V LED On Hazard On Beeper Vibration On 52 to 58 10 55 V LED On 12 48 V LED On Hazard On Beeper Vibration On 52 to 58 11 590 V LED ...

Страница 9: ...47 V Canada 347 V 347 V LED On 20 480 V 480 V 480 V LED On 21 Continuity 0 20 kΩ Short Continuity LED On Continuity Sign 22 Resistance 0 00 9 99 kΩ Short None 0 00 to 0 03 23 100 Ω None 0 06 to 0 14 24 9 kΩ None 8 52 to 9 48 Load Current Test To test the load current set up the UUT with equipment as shown in Figure 2 and complete the following procedure 1 Set the DMM to the mA dc function 2 Apply ...

Страница 10: ...nt as shown in Figure 2 and complete the following procedure Note When you press the GFCI pushbutton the resulting test will last for up to seven seconds 1 Set the DMM to the mA ac function 2 Apply 100 V 60 Hz from the Source The DMM reading should light the 12 48 V LEDs and Hazard symbol 3 Press the UUT GFCI pushbutton for one second The UUT DC and DC LEDs should alternately switch on and off whi...

Страница 11: ...urchase price free of charge repair or replacement of a defective product which is returned to a Fluke authorized service center within the warranty period To obtain warranty service contact your nearest Fluke authorized service center to obtain return authorization information then send the product to that service center with a description of the difficulty postage and insurance prepaid FOB Desti...

Страница 12: ...T and T PRO Calibration Information 12 ...

Отзывы: