Appliance Tester
Specifications
23
Earth Bond Test (R
PE
)
Operational Error Measurement Range .................................. 0.2 to 1.99
Ω
Operational error ..................................................................... 10.0 %
Accuracy (after Bond Test zeroing) ........................................ (5 % + 4 counts)
Display Range ......................................................................... 0 to 19.99
Ω
Resolution ............................................................................... 0.01
Ω
Test Current ............................................................................ 200 mA ac -0 % +40 % into 1.99
Ω
UK, NL, AU ..................................................................... 25 A ac ±20 % into 25 m
Ω
at 230 V
DE ................................................................................... 10 A ac ±10 % into 0
Ω
at 230 V
Open Circuit Voltage ............................................................... >4 V ac, <24 V ac
Bond Test Zeroing .................................................................. can subtract up to 1.99
Ω
Used Current for Bond Test Zeroing ....................................... 10A
Insulation Test (R
ISO
)
Operational Error Measurement Range .................................. 0.1 to 5 M
Ω
Operational Error .................................................................... 9.0 %
Accuracy ................................................................................. ±(5 % + 2 counts) from 0.1 to 50 M
Ω
±(10 % + 2 counts) from 50 to 299 M
Ω
Display Range ......................................................................... 0 to 299 M
Ω
Resolution ............................................................................... 0.01 M
Ω
(0 M
Ω
to 19.99 M
Ω
)
0.1
M
Ω
(20.0 M
Ω
to 99.9 M
Ω
)
1
M
Ω
(100 M
Ω
to 299 M
Ω
)
Test Voltage ............................................................................ 500 V dc –0 % +25 % at 500 k
Ω
load
Test Current ............................................................................ >1 mA at 500 k
Ω
load, <15 mA at 0
Ω
Auto discharge time ................................................................ <0.5 s for 1
μ
F
Max. Capacitive Load ............................................................. operational up to 1
μ
F
Substitute Leakage Current Test (I
SUB
)
Operational Error Measurement Range .................................. 0.25 mA to 19.00 mA
Operational Error .................................................................... 10 %
Accuracy ................................................................................. ± (5 % + 5 counts)
Display Range ......................................................................... 0 mA ac to 19.99 mA ac
Resolution ............................................................................... 0.01 mA
Test Voltage ............................................................................ 100 V ac ±20 % (at nominal mains input voltage), <3.5 mA at
0 ohms
Touch Current Test (I
TOUCH
)
Operational Error Measurement Range .................................. 0.1 mA to 1.99 mA
Operational Error .................................................................... 6.0 %
Accuracy ................................................................................. ±(4 % + 2 counts)
Display Range ......................................................................... 0 mA ac to 3.5 mA ac
Resolution ............................................................................... 0.01 mA
Internal Resistance (via probe) ............................................... 2 k
Ω
Measurement method ............................................................. Probe
The appliance under test is energized at mains potential.