HF170AEN_OS_v0501_04
Page 29
ANALOG OUTPUT OPTIONS:
The analog output can be used to output the measured value. The following analog output
configurations are available.
Analog output option AP:
A 4-20mA current-sinking signal proportional to the level is available as standard.
A DC power supply should be connected to terminal 08 and 09, the current is then regulated by
unit). When a power supply is connected but the output is disabled, a 3.5mA signal will be
generated. Max. driving capacity 1000 Ohm.
ANALOG INPUT OPTIONS:
Terminal 03-05; Sensor input option A
:
The F170-A-OS requires a (0)4-20mA sensor signal which will be processed 4 times a second with a
14 bits accuracy. The input is not isolated.