HF131PEN_v0501_05
Page 28
Terminal 03-04; transistor or relay output R2:
This output is available to drive a low-power device (e.g. relays) to control the batch process.
Relay 1 is switched-on during the whole process while relay 2 can be used for two-step control or as
pulse output. In case of a pulse output function: the maximum pulse frequency of this output is 60Hz.
Please note: if the communication option has been supplied, the pulse output function is not
available.
Terminal 05-06; transistor or relay output R1:
This output is available to drive a low-power device (e.g. relays) to control the batch process.
Relay 1 is switched-on during the whole batch process.
Option OA:
:
An active 24V DC signal according to the functions R1 and R2 is available with this option.
Max. driving capacity 20mA@24V per output. (Requires power supply option PD / PF / PM).