HF131PEN_v0501_05
Page 44
Sensor excitation
Standard / option PB
Supply voltage: 3.2V DC for pulse signals and 1.2V DC for coil pick-up.
Option PD
Sensor supply voltage 8 - 12 and 24V DC - max. 50mA@24V DC
Option PM
Sensor supply voltage 8 - 12 and 24V DC - max. 100mA@24V DC
Terminal connections
Type:
Removable plug-in terminal strip. Wire max. 1.5mm2 and 2.5mm2
Data protection
Type
EEPROM backup of all setting. Backup of running totals every minute.
Data retention at least 10 years.
Pass code
Configuration settings can be pass code protected.
Hazardous area
(optional)
Intrinsically safe
Option XI
ATEX approval:
II 1 G Ex ia IIB/IIC T4 Ga
II 1 D Ex ia IIIC T100°C Da IP6x
IECEx approval:
Ex ia IIB/IIC T4 Ga
Ex ia IIIC T100°C Da IP6x
Explosion proof
Option XD/XF
ATEX approval ref: II 2 EEx d IIB T5. Weight appr. 20kg.
Dimensions of enclosure: 218 x 418 x 213mm (8.58” x 16.45” x 8.38”) LxHxD.
Environment
Electromagnetic
compatibility
Compliant ref: EN 61326 (1997), EN 61010-1 (1993), NAMUR NE21 (1998)
Flowmeter
Type P
Coil/sine wave (minimum 20mVpp or 80mVpp - sensitivity selectable), NPN/PNP, open
collector, reed-switch, Namur, active pulse signals 8 - 12 and 24V.
Frequency Minimum 0 Hz - maximum 7 kHz for total and flowrate.
Maximum frequency depends on signal type and internal low-pass filter.
E.g. Reed switch with low-pass filter: max. frequency 120 Hz.
K-Factor 0.000010 - 9,999,999 with variable decimal position.
Low-pass filter Available for all pulse signals.
Type A
(0)4-20mA - with signal calibration feature. Resolution: 14 bit.
Type U
0-10 V, 0-5 V, 1-5 V - with signal calibration feature. Resolution: 14 bit.
Accuracy 0.05%. Low level cut-off programmable.
Span 0.000010 - 9,999,999 with variable decimal position.
Update time Four times a second.
Voltage drop 2.5 Volt.
Load impedance 3kOhm
Relationship Linear and square root calculation.
Note For signal type A and U: external power to sensor is required; e.g. option PD.