FW_F113A_v1901_02_EN.docx
Page 33
5.2.
TERMINAL CONNECTORS INTRINSICALLY SAFE APPLICATIONS
The unit is classified as group IIB/IIIC by default
Classification of the unit as group IIC is only possible under the following conditions:
The indicator is either supplied by
•
the internal supply (type PC);
•
the external supply connected to terminals 0 and 1 (type PD);
•
the circuit supply connected to terminals 7 and 8 (type AP);
•
The maximum values for any of those circuits are those as defined for group IIB/IIIC;
•
No other active external intrinsically safe circuits may be connected to the indicator, with
exception of circuits connected to terminals 3 and 4 and/or terminals 5 and 6; the maximum
values for any of those circuits are those as defined for group IIB/IIIC.
Terminal connectors F113-A-XI:
For intrinsically safe applications, consult the safety values in the certificate.
Fig. 25: Overview terminal connectors - Intrinsically safe (typical)