FW_F113A_v1901_02_EN.docx
Page 16
For intrinsic safe applications (XI):
The
setting
of this output (fast output) is assigned to R1 (option XI has
only two outputs).
RELAY 4
84
Only available for option OS: This submenu is used to set the function of
related output R1. Mind that when set to pulse, the output has a maximum
frequency of 5Hz to prevent contact bounce.
WIDTH
85
The pulse width determines the time that the output will be active; in other
words the pulse duration. Value “zero” will disable the pulse output.
The pulse signal always has a 50% duty cycle, hence the minimum time
between the pulses is equal to the pulse width setting. If the frequency
should go out of range
– when the flow rate increases for example – an
internal buffer will be used to “store the missed pulses”: As soon as the
flow rate slows down, the buffer will be “emptied”.
It might be that pulses will be missed due to a buffer-overflow, so it is advised to
program this setting within its range!
DECIMALS
86
This setting is used to set the amount of digits behind the decimal point for the
amount.
AMOUNT
87
A pulse will be generated every time a certain quantity is added to the total. Enter
this quantity here while taking the decimals for pulse into account.
3.1.10.
EXPLANATION OF SETUP-MENU 9 - COMMUNICATION (OPTION)
This product is designed for the connection to a communication network. Products with a
communication option do not include cyber security functions. Fluidwell cannot take any
responsibility for the cyber security, omissions or errors in the communication safety. To maintain a
secure operation, automation and control, it is the sole responsibility of the owner to install and
manage the appropriate safety measures to protect the network, the product and the communication
against any kind of security breaches.
The functions described below deal with hardware that is not part of the standard delivery.
Programming of these functions does not have any effect if this hardware has not been installed.
Consult Appendix C and the Modbus communication protocol description for a detailed explanation.
SPEED
91
This setting is used to set the Baudrate.
ADDRESS
92
This setting is used to set the communication address for the F113-A.
MODE
93
This setting is used to set the Modbus transmission mode. Select OFF to
disable the communication.
DATABITS
94
This setting determines for communication the number of data bits.
Select 8 bit for bus-rtu and 7 bits for bus-asc.
PARITY
95
As demanded by the connected equipment, select a parity bit (odd, even
or none).
3.1.11.
EXPLANATION OF SETUP-MENU A - OTHERS
For support and maintenance it is important to have information about the characteristics of the
F113-A. Your supplier will ask for this information when support is required.
MODEL
A1
This setting shows the model name.
SOFTWARE VERSION
A2
This setting shows the version number of the firmware (software).
SERIAL NO
A3
This setting shows the serial number.
PASSWORD
A4
This setting is used to set a password (pin code) to limit the access for the
setup menu. Only persons who know the pin code can access the setup
menu. The pin code 0000 disables the pin code to allow for access by any
person.
TAG-NR
A5
This setting is used to set a tag number for the F113-A .