background image

User Manual 

E115-P

Page 44

FW_E115-P_M_v0301-01_EN

6.4.5

TERMINAL CONNECTORS – MEM

The following terminal connectors are available for the Main Electronics Modus (MEM).

P2

POWER

REQUIREMENTS

P1

PX: 9 - 27V DC

PD: 9 - 27V DC

R1

R2

D1

R3

+

+

OT: passive transistor output

+

PB: battery powered
(PX: is standard available: if supply PX/PD
is connected, the battery supply will be 
switched off automatically.

R4

+

PULSE OUTPUT

D2

PULSE OUTPUT

MEM

Fig. 25: 

Terminal connectors MEM – upper row

S4

S5

E1

E2

S6

E3

P3

S2

S3

SENSOR INPUT

A

S1

P: reed switch / NPN

P: coil

P: namur

P: PNP

P: active signal

+

-

+

+

3V

+

3V

+

8.2 / 12 

/ 24V

-

+

3V

+

8.2 / 12 

/ 24V

+

8.2 / 12 

/ 24V

+

8.2 / 12 

/ 24V

+

8.2 / 12 

/ 24V

SENSOR

SUPPLY

C1

C2

C4

COMMUNICATION

C3

LOOP POWERED

ANALOG OUTPUT

A1

A2

AH: Isolated 4 - 20mA

I

-/+

I

-/+

CB: RS232

CH: RS485 - 2 wire

A

B

RXD

TXD

CU: USB Communication

White Green

DTR

+12V

Black

Red

RESET INPUT

Note: The sensor supply (P3)
is only available with PD.

Note: Non-polarity
sensitive.

IB: Reset total/Clear-lock

+

SENSOR INPUT

B

P: reed switch / NPN

P: coil

P: namur

P: PNP

P: active signal

+

-

+

+

3V

+

3V

-

+

3V

MEM

Fig. 26: 

Terminal connectors MEM - lower row

Содержание E115-P

Страница 1: ...Flowmeter type P Pulse NAMUR and coil Signal outputs Analog referenced flowrate Bi directional scaled or unscaled pulse referenced total Remote control External reset with clear lock Options Modbus co...

Страница 2: ...Internal error 14 5 CONFIGURATION 15 5 1 Introduction 15 5 2 Operating the Main Electronics Module MEM 15 5 2 1 Configuring using PC Configuration tool 16 5 2 2 Mechanical keys 16 5 2 3 Optical keys s...

Страница 3: ...t with clear lock Type IB 50 6 4 12 Terminals C1 C4 Communication RS232 RS485 USB Type CB CH CU 50 6 4 13 Terminals A1 A2 Isolated analog output Type AH 51 7 MAINTENANCE 52 7 1 Check for wear or damag...

Страница 4: ...zardous situation that could cause injury or death A caution indicates a condition that could cause moderate minor personal injury or equipment damage incorrect functioning of the unit or connected in...

Страница 5: ...apter of this manual Never remove the earth lead between the housing and the removable terminal block The local labor and safety laws and regulations must be adhered to Modifying the unit without prio...

Страница 6: ...ccumulated totalized flow current and previous day total and several historical day totals The E115 P is designed to detect flow direction and to show a positive or negative flowrate totals for both d...

Страница 7: ...s input to reset total remotely or to lock the clear total key Standard outputs Configurable pulse output to transmit pulses representing a certain differential total quantity Transmission is done eit...

Страница 8: ...EXAMPLE Following parts can be recognized in below installation example 1 2 6 4 5 9 7 3 8 9 Fig 3 Installation example E115 P 1 Cover 4 Display 7 Grounding 2 Armed cable connection 5 Optical touch ke...

Страница 9: ...a setting is being changed this is indicated by the mode indicator PROG on the display The following paragraphs describe the modes of operation in more detail SETUP mode and PROGRAM mode are described...

Страница 10: ...used to control the unit through the glass without the need to open the enclosure To activate an optical key position a finger clean and without gloves in front of the glass above the indicated area...

Страница 11: ...n Electronics Module MEM 15 for more information 4 2 3 BACKLIGHT The E115 is equipped with a backlight to illuminate the display for improved readability Depending on the type of supply the backlight...

Страница 12: ...FUNCTION 24 TOTAL FLOWRATE ACC TOTAL MAIN SCREEN Total 1 Flowrate Flowrate Total 1 Acc Total SCREEN 1 Total 1 Acc Total Total 1 Acc Total Total 1 Flowrate SCREEN 2 2 Current day Total SCREEN 3 2 Previ...

Страница 13: ...e to be displayed The arrows and indicate the trend increase or decrease of the flowrate The flowrate is calculated and processed 8 times per second To obtain a readable value the flowrate shown on th...

Страница 14: ...urn to the OPERATOR mode again press the PROG key for 3 seconds or wait for 3 minutes 4 5 OPERATOR ALARMS 4 5 1 LOW BATTERY When a battery is used to supply the unit Type PB and the battery voltage be...

Страница 15: ...is present Opening and servicing of the unit may only be carried out by authorized and trained personnel who have read and understood this manual particularly Section 2 Safety 5 Before opening the en...

Страница 16: ...SETUP mode and three mechanical keys push buttons at the side of the MEM available with the cover removed PROG CLEAR SELECT Fig 12 Control panel pushbuttons The mechanical keys copy the functionality...

Страница 17: ...SING SETUP MODE For an overview of Operating modes see Section 4 1 1 Operating modes 9 Changing settings may influence current operation In SETUP mode the unit remains fully operational Make sure the...

Страница 18: ...em either contains a value a number with optionally a decimal point and sign e g 123 45 or a selection list e g L m3 USGAL After a menu item is selected in the SETUP menu a new value can be programmed...

Страница 19: ...E When all configuration settings are set correctly return to OPERATOR mode by pressing the PROG key for three seconds or do not press any key for 2 minutes to return automatically The RUN indicator i...

Страница 20: ...ULATE differ additive not negative differ 6 5 K FACTOR single dual single 6 6 UNITS hand auto vol auto mass auto vol 6 7 UNIT Auto vol L m3 US GAL IGAL cf oil bbl Auto mas kg ton US ton lb L 6 8 K FAC...

Страница 21: ...o unit 1 2 DECIMALS Determines for Total and Accumulated Total the number of digits after the decimal point 1 3 K FACTOR This value is used to convert the flowmeter pulse signals into a total unit The...

Страница 22: ...e of flowmeter unit is changed in SETUP 6 6 FLOWMETER UNITS or 6 7 FLOWMETER UNIT the units in 2 1 FLOWRATE A UNIT will change to the default setting of the selected flowmeter If the settings in SETUP...

Страница 23: ...maximum time is 999 9 seconds approximately 15 minutes 5 5 3 MENU 3 TOTAL B For Total you can only set K Factor B when Dual is selected in 6 5 FLOWMETER K FACTOR By default this variable is set to Sin...

Страница 24: ...viewed from the operator level See Section 4 Operation 9 for information on reviewing historical day totals 5 3 SHOW A B ACC TOTAL This setting determines the Totals shown at operator level Disable or...

Страница 25: ...an be set for volume or mass units Refer to the test calibration certificate provided with your flowmeter The automatic unit conversion feature can be set to Hand allowing for independent configuratio...

Страница 26: ...er 51 k pull down max 700 Hz Less sensitive NAMUR NAMUR input 820 pull down max 4 kHz External sensor power required COIL HI Coil input high sensitivity min 20 mVpp Sensitive for interference Type ZF...

Страница 27: ...he K factor must then be set at SETUP 1 3 TOTAL A K FACTOR and menu 2 4 FLOWRATE A K FACTOR 6 7 UNIT Determines the measurement unit for the flowmeter When automatic unit conversion is used the units...

Страница 28: ...te For example enter 800 L min 7 4 RATE MAX 20MA Enter the flowrate at which the output should generate the maximum signal 20 mA in most applications at maximum flow The number of decimals displayed d...

Страница 29: ...CHANGE OF INPUT VALUE IN OF END VALUE Filter value 50 75 90 99 01 filter disabled filter disabled filter disabled filter disabled 02 0 1 sec 0 2 sec 0 4 sec 0 7 sec 03 0 2 sec 0 4 sec 0 6 sec 1 2 sec...

Страница 30: ...th is set in milliseconds in the range 0 001 9 999 sec The value zero will disable the pulse output The scaled pulse signal always has a 50 duty cycle This means the minimum time between pulses is equ...

Страница 31: ...uracy of the system clock is limited and it will be interrupted if there is a power down When the unit is powered up again and the Daily Total feature is enabled the operator will be prompted to enter...

Страница 32: ...trained personnel Take careful notice of the Section 2 Safety 5 at the front of this manual 6 1 INSTALLATION ENVIRONMENTAL CONDITIONS Take the relevant IP classification of the enclosure into account...

Страница 33: ...Main Electronics Module MEM 6 Grounding terminal 3 Battery 7 Label 4 Supply Module RSM or BSM BSM RSM MEM 1 1 2 2 2 2 3 5 5 4 6 Fig 16 Main Electronic Module and two types of Supply Module BSM RSM 1 F...

Страница 34: ...el placed on the outside of the unit Information on this label includes the configuration options chosen for your product E Y YY YY YYY YY YY YY YY YY Th e r ad Sizes P uct Configuration rod and Seria...

Страница 35: ...ate serial number of the electronics product configuration and connectors and more The MEM is supplied with two labels Fig 19 Example MEM labeling The Supply Module is also labeled Depending on produc...

Страница 36: ...ing Make sure the MEM inside doesn t fall out or gets damaged Remove the cover carefully 3 Store the cover in a safe location Make sure the mounting thread and glass screen are protected and the fixin...

Страница 37: ...nto the housing in one of the four positions 0 90 180 270 so the display is best readable Closing the cover 1 Apply a very thin layer of the specified anti seize compound see Section A Technical speci...

Страница 38: ...ENTRIES WITHIN 18 INCHES For CSA Group B C D SEAL ALL CONDUIT ENTRIES WITHIN 18 INCHES For CSA Group A SEAL AT ENCLOSURE WALL Use certified cable glands and conduit sealing devices All flameproof join...

Страница 39: ...osure 6 3 3 MOUNTING THE UNIT The Main Electronics Module MEM can be placed into the body in 4 directions 0 90 180 270 This allows the unit to be mounted in any direction while still allowing the MEM...

Страница 40: ...unit on a flowmeter 1 Remove the cover and the MEM see Section 6 2 3 Opening assembling and closing the unit 36 2 If present remove the cap from the bottom connector of the housing 3 Position the uni...

Страница 41: ...tection level Gb and Db the unit must be installed such that even in the event of rare incidents an ignition source due to impact or friction sparks between the enclosure and aluminum steel is exclude...

Страница 42: ...ion the housing temperature exceeds 70 C 158 F use suitable cable and gland to withstand high temperatures 6 4 2 GROUNDING OF THE ENCLOSURE For Class 1 applications make sure to apply proper in and ex...

Страница 43: ...can use some low power NPN or PNP output signals but battery life will be significantly reduced consult your distributor Type PD Sensor supply 8 2 VDC 12 VDC or 24 VDC Vin P2 minus 1 V This option pro...

Страница 44: ...Terminal connectors MEM upper row S4 S5 E1 E2 S6 E3 P3 S2 S3 SENSOR INPUT A S1 P reed switch NPN P coil P namur P PNP P active signal 3V 3V 8 2 12 24V 3V 8 2 12 24V 8 2 12 24V 8 2 12 24V 8 2 12 24V SE...

Страница 45: ...on 6 4 4 Voltage selection sensor supply 43 6 4 8 TERMINALS P3 SENSOR SUPPLY TYPE PD This terminal may be used for sensor supply See Section 6 4 4 Voltage selection sensor supply 43 for relevant infor...

Страница 46: ...upply voltage is 24 27 VDC Be sure that the output frequency does not exceed 0 5 Hz else the relay life time and reliability will be reduced significantly The output functionality of digital output D5...

Страница 47: ...L HI sensitivity Pulse signal NPN NPN LP The unit is suitable for use with flowmeters which have a NPN output signal For reliable pulse detection under all circumstances the signal should be above 1 4...

Страница 48: ...or 24 VDC S1 S2 S3 P3 J1 J2 8 2 12V 24V V Common system ground PNP LP R 3V MEM Fig 32 Terminals S1 S3 and P3 Pulse signal input PNP Reed switch The unit can be used with flowmeters which have a reed...

Страница 49: ...2V Common system ground R MEM Fig 34 Terminals S1 S2 and P3 NAMUR input signal Active signals 8 2 V and 24 V The unit is suitable for flowmeters with an Active signal The detection levels are about 50...

Страница 50: ...for at least 100 ms The input must be switched with a normally open contact to GND R 3V E1 E2 Common system ground MEM Fig 36 Terminals E1 E2 External reset 6 4 12 TERMINALS C1 C4 COMMUNICATION RS232...

Страница 51: ...ith a voltage between 6V and 10V 6 4 13 TERMINALS A1 A2 ISOLATED ANALOG OUTPUT TYPE AH The flowrate proportional output AH is standard available This output is an isolated 4 20 mA output with the poss...

Страница 52: ...damage or aging symptoms 2 Check the process accuracy If necessary re calibrate the flowmeter Do not forget to re enter any updated K factor values 3 Check the battery indicator for low level replace...

Страница 53: ...is with the next clip 2 Carefully lift the back cover and remove the battery from the battery holder 3 Dispose of the battery according to local regulations Insert new battery in MEM 1 Unpack the new...

Страница 54: ...t 3600 gram Rating IP66 67 TYPE 4X TYPE 7 TYPE 9 Thread type H_A 2 x NPT 1 x 1 NPT Thread type H_B 3 x NPT Thread type H_C 2 x NPT 1 x 1 NPT Thread type H_D 2 x NPT 1 x NPT Thread type H_G 2 x M20 1 x...

Страница 55: ...ck the Clear total button Type IB Internally pulled up switch contact NPN Pulse duration 100 msec minimum A 3 OUTPUT DIGITAL OUTPUT Function Transmitting scaled accumulated total positive and negative...

Страница 56: ...n be reset to zero by pressing the CLEAR key twice TOTAL Digits 7 digits Unit L m3 US gal igal cf Oil bbl kg ton US ton lb or none Decimals 0 1 2 or 3 Note Total can be reset to zero DAILY TOTALS Digi...

Страница 57: ...0 1 12 FM FM3600 FM3615 FM3616 FM3810 IP TYPE EN 60529 NEMA 250 HAZARDOUS AREA CLASSIFICATION ATEX Gas II 2 G Ex d IIC T6 Gb Dust II 2 D Ex tb IIIC T85 C Db IECEx Gas Ex d IIC T6 Gb Dust Ex tb IIIC T8...

Страница 58: ...actual signal generated SETUP 6 FLOWMETER 26 Sensitivity of coil input SETUP 6 FLOWMETER 26 Grounding Reconnect ground cables and avoid ground loops Connect screen to the ground input terminal of the...

Страница 59: ...de shown is the sum of the error codes as given below For example 0048 is a combination of error code 0016 and 0032 Alarm Explanation 0001 Display error 0002 Data storage error 0004 Initialization err...

Страница 60: ...62 2 When a transmission is done register 560 the MSW most significant word arrives first followed by register 561 in the middle and register 562 at the end the LSW least significant word The followin...

Страница 61: ...mals depending on variables 48 49 50 d 2272 h 0x08E0 42273 grand current day total 4 R uint64 0 000 9999999999 Representation unit decimals depending on variables 32 33 d 2280 h 0x08E8 42281 grand pre...

Страница 62: ...tion unit decimals depending on variables 32 33 d 6182 h 0x1826 46183 accumulated total B reverse 4 R uint64 0 000 99999999999999 Representation unit decimals depending on variables 32 33 d 6186 h 0x1...

Страница 63: ...h 0x1A1C 46685 accumulated total B reverse 4 R float64 0 99999999999 Representation unit depending on variable 32 Note The list of runtime variables shown above can be read as one contiguous list of...

Страница 64: ...S GAL 5 I GAL 6 CF 7 OilBBL 8 nL 9 nm3 10 SCF 11 mg 12 g 13 kg 14 ton 15 lb 16 US 17 rev 18 P d 49 h 0x0031 40050 time unit 1 R W uint16 0 sec 1 min 2 hour 3 day d 50 h 0x0032 40051 decimals 1 R W uin...

Страница 65: ...N LP 2 reed 3 reed LP 4 PNP 5 PNP LP 6 Namur 7 coil hi 8 coil lo 9 act 8 2V 10 act 24V d 207 h 0x0CF 40208 bi directional 1 R W uint16 0 disable 1 90 2 270 d 140 h 0x08C 40141 calculate 1 R W uint16 0...

Страница 66: ...entation 0 000001 9999999 depending on variables 32 133 d 133 h 0x085 40134 pulse quantity decimals 1 R W uint16 0 3 MODBUS REGISTERS MODBUS COMMUNICATION PDU ADDRESS HOLDING REGISTER VARIABLE NO OF R...

Страница 67: ...erial number 2 R uint32 0 9999999 Representation xxxxxxx d 176 h 0x0B0 40177 local time 2 R W uint32 00 00 00 23 59 59 Representation hh mm ss Stored decimal 23 59 59 235959d 0x0003 99B7 d 168 h 0x0A8...

Страница 68: ...py for each product With the software programming of multiple products can be done very easy D 2 CABLE CONNECTION Before opening the enclosure consult Section 6 2 3 Opening assembling and closing the...

Страница 69: ...e package can be downloaded from our website at www fluidwell com software and installed using the installation program The installation also contains a Quickstart manual which gives detailed instruct...

Страница 70: ...User Manual E115 P Page 70 FW_E115 P_M_v0301 01_EN APPENDIX E LEGAL INFORMATION E 1 EU DECLARATION OF CONFORMITY...

Страница 71: ...E115 P User Manual FW_E115 P_M_v0301 01_EN Page 71 NOTES...

Страница 72: ...O Box 6 Voltaweg 23 Website www fluidwell com 5460 AA Veghel 5466 AZ Veghel Find your nearest representative www fluidwell com representatives the Netherlands the Netherlands Copyright 2022 FW_E115 P...

Отзывы: