FW_E115-P_M_v0301-01_EN
4
FLOWRATE B
DEFAULT
4.1
K-FACTOR
auto, 0.000010 - 9999999
auto
5
DISPLAY
DEFAULT
5.1
FUNCTION
total, flowrate, acc. total
total
5.2
DAY TOTALS
off, operate, hidden
off
5.3
SHOW A-B (ACC.
TOTAL)
enable, disable
disable
5.4
LCD NEW
fast, 1 sec, 3 secs, 15 secs, 30 secs, off
1 sec
5.5
BACKLIGHT
(BRIGHTNESS)
0%, 20%, 40%, 60%, 80%, 100%
100%
5.6
BARGRAPH
disable, absolute, rate a, rate b
absolute
5.7
RATESPAN
-999999 - 999999
1000
6
FLOWMETER
DEFAULT
6.1
SIGNAL A
NPN, NPN_LP, REED, REED_LP, PNP, PNP_LP, NAMUR,
Coil_Hi, Coil_Lo, Act_8.2 (8.2V DC), Act_24 (24V DC)
Coil_Lo
6.2
SIGNAL B
NPN, NPN_LP, REED, REED_LP, PNP, PNP_LP, NAMUR,
Coil_Hi, Coil_Lo, Act_8.2 (8.2V DC), Act_24 (24V DC)
Coil_Lo
6.3
BI-DIRECTIONAL
disable, 90 deg, 270 deg
disable
6.4
CALCULATE
differ, additive, not negative
differ
6.5
K-FACTOR
single, dual
single
6.6
UNITS
hand, auto-vol, auto-mass
auto-vol
6.7
UNIT
Auto-vol: L, m3, US GAL, IGAL, cf, oil bbl
Auto mas: kg, ton, US ton, lb
L
6.8
K-FACTOR A
0.000010 - 9999999
1
6.9
K-FACTOR B
0.000010 - 9999999
1
7
ANALOG OUTPUT
DEFAULT
7.1
OUTPUT
enable, disable
disable
7.2
RATE SELECT
signed, absolute, rate A, rate B
signed
7.3
RATE MIN (4MA)
-999999 - 999999
0
7.4
RATE MAX (20MA)
-999999 - 999999
99999
7.5
CUT-OFF
0.0 - 9.9 %
0.0 %
7.6
TUNE MIN (4MA)
0000 - 9999
-
7.7
TUNE MAX (20MA)
0000 - 9999
-
7.8
FILTER
01 - 99 (01 = off)
01
8
PULSE OUTPUT
DEFAULT
8.1
MODE
disable, not negative, separate, signed, retransmit
disable
8.2
WIDTH
0.000 - 9.999 sec (0.000 = off)
0.000
8.3
AMOUNT
0000.000 - 9999999 per pulse
1000 L per
pulse
9
MODBUS COMMUNICATION
DEFAULT
9.1
SPEED
1200, 2400, 4800, 9600, 9600HP, 19200, 38400
9600
9.2
ADDRESS
001 - 247
1
9.3
MODE
off, bus asc, bus rtu
bus rtu
9.4
DATABITS
8 bits, 7 bits
8 bits
9.5
PARITY
none, even, odd
none