7.2.5.4 General Settings
General DCS settings can be accessed by pressing the “General” button in the DCs Configuration menu. It is recom-
mended to keep these settings at their default values unless specifically needed for the application.
Figure 7.26 – General DCS Settings (defaults shown)
1.
1. The MS1 Legacy Mapping Mode setting can be Enabled/Disabled for use of the A/B style mapping as explained
in section 7.2.5.3.1 FC 02 Read Input Status.
2. The HMI State During Comms setting allows the user to enable or disable use of the local (touchscreen) display
when DCS communication is active.
3. The DCS Comm Lockout Time setting defines the duration of the touchscreen lockout period during DCS
communications. Valid range in milli-seconds is 1-10,000.