
Limitorque
®
Master StationI V EEP-SN4001 FCD LMENIM5010-00-AQ – 03/19
13
flowserve.com
3
Quick Startup
1. Connect earth ground (#18AWG minimum) wiring, MOV network cables (Belden #3074F/#9841/#3107), and DC
power cabling.
2. Apply power to the MSIV and turn the power switch to the ON position.
3. Wait for the MSIV to display the start-up screen.
4. Touch the screen once and wait for the login prompt.
5. Enter default username “FLOW”. Press Enter.
6. Enter default password “100”. Press Enter.
7. Select “System Configuration” then “Redundant Configuration”.
8. Set the requested mode to “Disabled”, startup mode to “Active”, and redundancy mode to desired setting.
9. Press the “Back” button and in the “System Configuration” page select “User Administration”.
10. Set up user accounts.
11. Select “MOV Network Config” and set up the MOV network.
12. Select “DCS Configuration” and set up the DCS communications.
a. For remote DCS control, the three primary registers of interest are:
i. 46001: Register for HS Status (Ready Only): 0=idle, 1=standby, 2=hot
ii. 46002: Register for Host System to toggle (Write Only): 3=toggle state
iii. 46191: Register for Internal Program Execution Heartbeat (Read Only): Updates every scan, 8-bit integer.
13. Tap the “Back” button to return to the “System Configuration” screen.
14. Select “Redundant Config” and change the requested mode to “Active”.
Содержание MASTER STATION IV EEP-SN4001
Страница 2: ...Limitorque Master Station IV EEP SN4001 FCD LMENIM5010 00 AQ 03 19 2...
Страница 12: ...Limitorque Master Station IV EEP SN4001 FCD LMENIM5010 00 AQ 03 19 12 System Configuration branch continued...
Страница 63: ...Limitorque Master StationI V EEP SN4001 FCD LMENIM5010 00 AQ 03 19 63 flowserve com Notes...