Limitorque
®
Master StationI V EEP-SN4001 FCD LMENIM5010-00-AQ – 03/19
49
flowserve.com
Table 7.10 – Function code 06 message breakdown
Query
Response
01
MSIV Unit Address
01
MSIV Unit Address
06
Function
06
Function
13
Register Address Hi
13
Register Address Hi (Register 45089; MOV45)
E1
1
Register Address Lo
E1
Register Address Lo (Register 45089; MOV45)
1A
Force Data Hi
1A
Force Data Hi
00
2
Force Data Lo
00
Force Data Lo
D618
Error Check (CRC)
D618
Error Check (CRC)
Note 1:
13E1h equals register address 45089 (field unit 45 command register)
Note 2:
1A00h equals 6656d
Example of multiple register write command
Write the command to close an actuator to field units 50, 51, and 52. This corresponds to
writing the value 768 into command registers 45050, 45051, and 45052.
Query: 011013B90003060300030003006ABB
Response: 011003B900035569
Table 7.11 – Function code 16 message breakdown
Query
Response
01
MSIV Unit Address
01
MSIV Unit Address
10
Function
10
Function
13
Starting Address Hi
13
Starting Address Hi
B9
1
Starting Address Lo
B9
Starting Address Lo
00
Number of registers Hi
00
Number of registers Hi
03
Number of registers Lo
03
Number of registers Lo
06
Byte count
5569
Error Check (CRC)
03
Preset Data Hi (MOV 50)
00
2
Preset Data Lo (MOV 50)
03
Preset Data Hi (MOV 51)
00
Preset Data Lo (MOV 51)
03
Preset Data Hi (MOV 52)
00
Preset Data Lo (MOV 52)
6ABB
Error Check (CRC)
Note 1:
13B9h equals register address 45050 (field unit 50 command register)
Note 2:
0300h requests the register to be preset with 768d (field unit close)
See the following tables for valid register operations. For further reference, see DDC (Modbus) Field Unit Installation,
Operation, and Maintenance manual LMENIM2329.
Содержание MASTER STATION IV EEP-SN4001
Страница 2: ...Limitorque Master Station IV EEP SN4001 FCD LMENIM5010 00 AQ 03 19 2...
Страница 12: ...Limitorque Master Station IV EEP SN4001 FCD LMENIM5010 00 AQ 03 19 12 System Configuration branch continued...
Страница 63: ...Limitorque Master StationI V EEP SN4001 FCD LMENIM5010 00 AQ 03 19 63 flowserve com Notes...