51-12

Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611

time a Quick-Cal is performed based on the setting
of the rotary 

Gain switch.

If the rotary 

Gain selector switch is set to E with the

auto tune switch 

On, a Flowserve nominal

response tuning set will be calculated and used.

If the rotary 

Gain selector switch is set to D, C, B, or

A  with the Auto Tune switch On, progressively
lower gain settings will be calculated and used.

If the rotary 

Gain selector switch is set to F, G, or H

with the 

Auto Tune switch On, progressively higher

gain settings will be calculated and used.

Off forces the positioner to use one of the factory
preset tuning sets determined by the rotary 

Gain

selector switch. Settings 

A through H are progres-

sively higher gain predefined tuning sets.

6. Config. Switches  — By selecting 

Enabled, the

Logix 500 will read all of the configuration switches
each time a 

Quick-Cal is performed to determine

the configuration.

Selecting 

Disabled retains the last configuration in

memory (from the last successful calibration) be-
fore the switch was set to 

Disabled. With this setting

Quick-Cal only zeros and spans the positioner.

Setup of the Cal DIP Switch for the Quick
Calibration operating mode

1. Select 

Auto if the valve/actuator assembly has an

internal stop in the 100% stroke position. In 

Auto

mode the positioner will fully close the valve and
register the 0% position and then open the valve to
the stop to register the 100% position when per-
forming a self-calibration. See detailed instructions
in the next section on how to perform an auto
positioner calibration.

2. Select 

Jog if the valve/actuator assembly has no

calibration stop in the open position. In the 

Jog

mode the positioner will fully close the valve for the
0% position and then wait for the user to set the
open position using the 

Jog buttons labeled with the

up and down arrows. See the detailed instructions
in the next section on how to perform a manual
calibration using the 

Jog buttons.

WARNING: During the Quick-Cal operation the
valve may stroke unexpectedly. Notify proper
personnel that the valve will stroke, and make
sure the valve is properly isolated.

Quick-Cal Operation

The 

Quick-Cal button is used to locally initiate a calibra-

tion of the positioner. Pressing and holding the 

Quick-Cal

button for approximately three seconds will initiate the
calibration. If the 

Config-Switches option is enabled, the

settings of all the configuration switches are read and
the operation of the positioner adjusted accordingly.

The 

Gain Selector switch is also read and action will be

taken to adjust the gain according to the settings of the
calibration switches as described in the previous section.

Quick-Cal can be aborted at any time by briefly pressing

the 

Quick-Cal  button and the previous settings will be

retained.

If the 

Quick calibration switch (not to be confused with the

Quick-Cal button) is set to Auto and the valve/actuator
assembly has the necessary internal stops, the calibra-
tion will complete automatically. While the calibration is in
progress you will notice a series of different lights flash-
ing indicating the calibration progress. When the lights
return to a sequence that starts with a green light, the
calibration is complete. (See the appendix for an expla-
nation of the various light sequences.)

WARNING: When operating using local control of the
valve, the valve will not respond to external com-
mands. Notify proper personnel that the valve will not
respond to remote command changes, and make sure
the valve is properly isolated.

If the 

Quick calibration switch is set to Jog, the calibration

will initially close the valve then cause a small jump in the
valve position. The jog calibration process will only
allow the user to manually set the span; zero posi-
tion is automatically always set at the seat.
 If an el-
evated zero is needed a handheld or other PC based
configuration software is required. The LEDs will then flash
in a sequence of Y-R-R-G (yellow-red-red-green) which
indicates the user must now use the 

Jog keys to manu-

ally position the valve to approximately 100%. When the
valve is approximately 100% open press both 

Jog but-

tons simultaneously to proceed to the next step. The valve
will then stroke and then wait while flashing the Y-R-R-G
sequence again, allowing the user to adjust the valve
position a second time to exactly 100% using the 

Jog

buttons. When the stem is properly positioned press both
Jog buttons simultaneously again to register the 100%
position and proceed. No more user actions are required
while the calibration process is completed. When the lights
return to a sequence that starts with a green light the cali-
bration is complete. (See the appendix for an explanation
of the various light sequences.)

Local control of valve position — Can be done from
the user interface by holding both jog buttons and then
simultaneously pressing the 

Quick-Cal button. While in

this mode the LEDs will flash a Y-G-R-R (yellow-green-
red-red) sequence. To exit the local control mode and re-
turn to normal operation, briefly press 

Quick-Cal.

Factory reset — hold 

Quick-Cal button while applying

power and all of the internal variables including calibra-
tion will be reset to factory defaults. The positioner must
be re-calibrated after a factory reset. Tag names and other
user configured limits, alarm settings, and valve informa-
tion will also need to be restored. A factory reset will al-
ways reset the command source to analog 4-20 mA.

Содержание Logix 500 Series

Страница 1: ...to personnel and equip ment and may void existing warranties WARNING This product has electrical conduit connections in either thread sizes 0 5 inch NPT or M20 which appear identical but are not interchangeable Forcing dissimilar threads Logix 500 Digital Positioner Valtek Part No together will damage equipment cause personal injury and void hazardous location certifications Conduit fittings must ...

Страница 2: ...rs 7 Tubing Positioner to Actuator 8 Wiring and Grounding Guidelines 9 Grounding Screw 9 Compliance Voltage 9 Startup 10 Initial DIP Switch Setting 11 Quick Cal Operation 12 Logix 500 Status Condition Codes 13 HART 275 Handheld Communicator 16 Limit Switch Unit 16 General 16 Model Selection 16 Principle of operation 16 Installation 16 Start up 16 Troubleshooting 18 Spare Part Kits 20 Mounting Kits...

Страница 3: ... 10 C below ambient temperature particle size below five mi crons one micron recommended and oil content not to exceed one part per million Specifications Linearity 1 0 Resolution 0 1 Repeatability 0 2 Deadband 0 2 Table 5 Performance Characteristics typical Operating Temperature Standard 4 178 F 20 80 C Low 40 178 F 40 80 C Transport and Storage 40 178 F Temperature 40 80 C Operating Humidity 0 1...

Страница 4: ...age control algorithm The pneumatic amplifier con trols the airflow to the actuator The change of pres sure and volume of the air in the actuator causes the valve to stroke As the valve approaches the desired position the difference between the commanded posi tion and the measured position becomes smaller and the output to the piezo is decreased This in turn causes the pilot valve to close and the...

Страница 5: ...s according to NAMUR is described in Figure 6 For the two mounting possibilities of cast yoke actua tors according to NAMUR lEC 534 part 6 refer to Fig ure 4 After installation ensure all screw connections are tightened correctly and all moving parts are free from excessive friction Valtek 2000 Kammer KA Kammer KP or standard NAMUR linear valves use the same mounting kits Mounting of the Logix 500...

Страница 6: ...R IEC 534 part 6 Figure 5 Take off Arm standard Mounting A Hexagon Head Screw Lock Washer Mounting B 15 20 30 40 50 60 65 mm Follower Pin Follower Arm Nut Washer A c t u a t o r S t r o k e 50 Valve Stroke Stroke 100 ATO Stroke 0 ATC Stoke 0 ATO Stroke 100 ATC m m 65 60 50 40 30 20 m m 65 60 50 40 30 2 3 1 Control Marking Actuator Stroke Control Marking Follower Pin Follower Arm ...

Страница 7: ...y as described in step 3 As the actuator strokes the rotation of the feedback gear should be between the inner control markings If the length of rotation is outside the control markings adjust the follower pin far ther out on the feedback lever to reduce the angle of rotation NOTE Stroke the actuator carefully and ensure the follower arm does not interfere with valve parts actuator or positioner D...

Страница 8: ... fasten it with two hexagon head screws 3 and lock washers 2 2 Place the mounting plate 1 with the positioner onto the mounting block 4 of the actuator Ensure the coupler 8 fits on to the shaft of the quarter turn connection on the part turn valve actuator 3 Hand tighten the plate 1 onto the actuator with four nuts 5 and lock washers 6 center it and fasten the nuts 4 Tighten all screws and nuts Tu...

Страница 9: ...be used to provide the unit with an ad equate and reliable earth ground reference This ground should be tied to the same ground as the electrical con duit Additionally the electrical conduit should be earth grounded at both ends of its run The grounded screw must not be used to terminate signal shield wires Compliance Voltage Figure 9 Output compliance voltage refers to the voltage limit the curre...

Страница 10: ...runs longer than 5000 feet No 20 AWG cable should be used Electromagnetic Compatibility The Logix 520 digital positioner has been designed to operate correctly in electromagnetic EM fields found in typical industrial environments Care should be taken to prevent the positioner from being used in environments with excessively high EM field strengths greater than 10 V m Portable EM devices such as ha...

Страница 11: ... air to close actuator configuration Selecting 4 mA will make the valve fully closed when the signal is 4ma and fully open when the signal is 20 mA Selecting 20 mA will make the valve fully closed when the signal is 20 mA and fully open when the signal is 4 mA 3 Pos Characterization Select Linear if the actuator position should be directly proportional to the input signal Select Optional if anothe...

Страница 12: ...f the calibration switches as described in the previous section AQuick Cal canbeabortedatanytimebybrieflypressing the Quick Cal button and the previous settings will be retained If the Quick calibration switch not to be confused with the Quick Cal button is set to Auto and the valve actuator assembly has the necessary internal stops the calibra tion will complete automatically While the calibratio...

Страница 13: ...mmand signal back in the specified range GYRY 7 Soft Stop Upper The unit is being commanded to exceed a user defined upper travel limit and the internal software is holding the position at the limit To clear the condition use handheld or Flowserve supplied software to reset the limit if more travel is needed or adjust the command signal back in the specified range GRYR 8 Position Lower The position h...

Страница 14: ...ing the Quick Cal button which will force the positioner to use the parameters from the last good calibration YRYR 20 Feedback 0 saturated Calibration error indicating that the position sensor was out of range during the calibration To correct the condition adjust the positioner mounting link age or feedback potentiometer to move the position sensor back into range then restart the calibration Thi...

Страница 15: ... pneumatic relay assembly RYRY 29 Hall sensor upper position Check to make sure the air supply is connected This error may be cleared by briefly pushing the Quick Cal button which will force the positioner to use the parameters from the last good calibration If the positioner still does not operate replace the pneumatic relay assembly RRGG 30 1 23v reference Bad electronic assembly replace RRGR 31 ...

Страница 16: ... is picked up by a stroke lever or by a coupling at the actuator connection The lever coupling moves the vane into the slot of the limit switches LS1 or LS2 via shaft The sensors are de signed as a proximity vane type switch The switching function is triggered if a ferromagnetic object vane is inserted between the coils The switching point can be set by adjustment of the vane Installation The limi...

Страница 17: ...it switch unit does not change the Logix 500 dimensions Supply Supply voltage Umax 16Vdc Supply current Imax 52mA Output signal With target 1mA Without target 3mA Short circuit proofed Control characteristics Switching hysteresis 5 1mm STROKE in acc with 20mm STROKE Repeatability 0 05 0 01mm STROKE Ambient temperature sensitivity 1 5 0 3mm 10K Vibration sensitivity 1 at 2g 0 5 500 Hz in accordance...

Страница 18: ...on reading is not what is expected 1 Stem position sensor mounting is off 180 degrees 2 Stroke not calibrated 3 Tight shutoff M P C is active 4 Custom characterization or soft stops active Position is driven fully open or closed and will not respond to com mand 1 Stroke not calibrated 2 Inner loop hall sensor not connected 3 Wrong air action entered in software 4 Actuator tubing backward 5 Electro...

Страница 19: ... Exploded View Cover Item No 1 Electronic Control Boards Item No 2 E P Piezo Driver Pneumatic Amplifier Relay Unit Item No 3 Feedback Potentiometer Assembly Item No 4 Feedback Gear Shaft Item No 5 Limit Switch Assembly Item No 6 Base Housing Item No 7 Follower Item No 8 Follower arm ...

Страница 20: ...tinually improving and upgrading its product design the specifications dimensions and information contained herein are subject to change without notice Should any question arise concerning these provisions the purchaser user should contact Flowserve Corporation at any of its worldwide operations or offices For more information contact For more information about Flowserve and its products contact w...

Отзывы: