background image

51-16

Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611

HART 275 HANDHELD COMMUNICATOR
AND SOFTTOOLS CONFIGURATION AND
DIAGNOSTIC SOFTWARE

The Logix 520 supports and is supported by the HART
275 Handheld Communicator. The DD and the manu-
als listed below can be obtained from the HART
Communication Foundation or from your Flowserve rep-
resentative. For more information please see the fol-
lowing guides:

Product Manual for the HART Communicator

Logix 520 Digital Positioner with HART 275
Communicator User Guide

Flowserve corporation has written custom configura-
tion and diagnostic software for the Logix 500 series
called SoftTools™. This software and the 

SoftTools

Quick Start Guide are available from a Flowserve rep-
resentative.

LIMIT SWITCH UNIT (Optional)

CAUTION: The installation of explosion proof elec-
trical equipment must comply with the procedures
contained in the certificates of conformance. Coun-
try specific regulations may apply. Electrical safety
is determined only by the power supply device
(Positioner operation with limited voltage only).

General

The Logix 500 digital positioner can be equipped with
an additional limit switch unit, designed as a two-wire
sensor in accordance with NAMUR. The low voltage
and current characteristics of these sensors allows
operation in hazardous areas.

Model Selection

To select the suitable Logix 500 version see product
information.

Principle of operation

The stroke of the diaphragm actuator or the rotary angle
of the rotary valve actuator is picked up by a stroke

lever or by a coupling at the actuator connection. The
lever/coupling moves the vane into the slot of the limit
switches LS1 or LS2 via shaft. The sensors are de-
signed as a proximity vane type switch. The switching
function is triggered if a ferromagnetic object (vane) is
inserted between the coils. The switching point can be
set by adjustment of the vane.

Installation

The limit switch unit is delivered already fitted to the
positioner and can not be retrofitted.

Start-up

After the Logix 500 digital positioner start-up in accor-
dance with the application is complete, the limit switch
unit can be adjusted and operation can be effected.
For adjustment remove the positioner cover. Figure 14
shows the maximum switching range of the limit
switches LS1 and LS2.

The switching points of the limit switches can be set by
an adjustment of the vane as follows (Figure 13):

1. Loosen the knurled screw (Figure 13) at the stroke

lever axis (1/2 to 1 rotations).

2. Move the positioner to the first switching position.

3. Set the switching point of the limit switch LS2 by

adjusting the vane of the lower switch. For adjust-
ment turn the corresponded slotted screw clock-
wise or counterclockwise.

4. Move the positioner to second switching position.

5. Set the switching point of the limit switch LS1 by

adjusting the vane of the upper switch. For adjust-
ment turn the corresponded slotted screw clock-
wise or counterclockwise.

6. Tighten the knurled screw.

7. Check the two switching points and repeat the

adjustment steps 1 to 6, if necessary.

Figure 12: Principle of Operation

Linear Version

Rotary Version

Rotary Valve Actuator

Limit Switch Unit

Limit Switch Unit

+

-

+

-

Diaphragm Actuator

Stroke
Lever

Butterfly Damper

Содержание Logix 500 Series

Страница 1: ...to personnel and equip ment and may void existing warranties WARNING This product has electrical conduit connections in either thread sizes 0 5 inch NPT or M20 which appear identical but are not interchangeable Forcing dissimilar threads Logix 500 Digital Positioner Valtek Part No together will damage equipment cause personal injury and void hazardous location certifications Conduit fittings must ...

Страница 2: ...rs 7 Tubing Positioner to Actuator 8 Wiring and Grounding Guidelines 9 Grounding Screw 9 Compliance Voltage 9 Startup 10 Initial DIP Switch Setting 11 Quick Cal Operation 12 Logix 500 Status Condition Codes 13 HART 275 Handheld Communicator 16 Limit Switch Unit 16 General 16 Model Selection 16 Principle of operation 16 Installation 16 Start up 16 Troubleshooting 18 Spare Part Kits 20 Mounting Kits...

Страница 3: ... 10 C below ambient temperature particle size below five mi crons one micron recommended and oil content not to exceed one part per million Specifications Linearity 1 0 Resolution 0 1 Repeatability 0 2 Deadband 0 2 Table 5 Performance Characteristics typical Operating Temperature Standard 4 178 F 20 80 C Low 40 178 F 40 80 C Transport and Storage 40 178 F Temperature 40 80 C Operating Humidity 0 1...

Страница 4: ...age control algorithm The pneumatic amplifier con trols the airflow to the actuator The change of pres sure and volume of the air in the actuator causes the valve to stroke As the valve approaches the desired position the difference between the commanded posi tion and the measured position becomes smaller and the output to the piezo is decreased This in turn causes the pilot valve to close and the...

Страница 5: ...s according to NAMUR is described in Figure 6 For the two mounting possibilities of cast yoke actua tors according to NAMUR lEC 534 part 6 refer to Fig ure 4 After installation ensure all screw connections are tightened correctly and all moving parts are free from excessive friction Valtek 2000 Kammer KA Kammer KP or standard NAMUR linear valves use the same mounting kits Mounting of the Logix 500...

Страница 6: ...R IEC 534 part 6 Figure 5 Take off Arm standard Mounting A Hexagon Head Screw Lock Washer Mounting B 15 20 30 40 50 60 65 mm Follower Pin Follower Arm Nut Washer A c t u a t o r S t r o k e 50 Valve Stroke Stroke 100 ATO Stroke 0 ATC Stoke 0 ATO Stroke 100 ATC m m 65 60 50 40 30 20 m m 65 60 50 40 30 2 3 1 Control Marking Actuator Stroke Control Marking Follower Pin Follower Arm ...

Страница 7: ...y as described in step 3 As the actuator strokes the rotation of the feedback gear should be between the inner control markings If the length of rotation is outside the control markings adjust the follower pin far ther out on the feedback lever to reduce the angle of rotation NOTE Stroke the actuator carefully and ensure the follower arm does not interfere with valve parts actuator or positioner D...

Страница 8: ... fasten it with two hexagon head screws 3 and lock washers 2 2 Place the mounting plate 1 with the positioner onto the mounting block 4 of the actuator Ensure the coupler 8 fits on to the shaft of the quarter turn connection on the part turn valve actuator 3 Hand tighten the plate 1 onto the actuator with four nuts 5 and lock washers 6 center it and fasten the nuts 4 Tighten all screws and nuts Tu...

Страница 9: ...be used to provide the unit with an ad equate and reliable earth ground reference This ground should be tied to the same ground as the electrical con duit Additionally the electrical conduit should be earth grounded at both ends of its run The grounded screw must not be used to terminate signal shield wires Compliance Voltage Figure 9 Output compliance voltage refers to the voltage limit the curre...

Страница 10: ...runs longer than 5000 feet No 20 AWG cable should be used Electromagnetic Compatibility The Logix 520 digital positioner has been designed to operate correctly in electromagnetic EM fields found in typical industrial environments Care should be taken to prevent the positioner from being used in environments with excessively high EM field strengths greater than 10 V m Portable EM devices such as ha...

Страница 11: ... air to close actuator configuration Selecting 4 mA will make the valve fully closed when the signal is 4ma and fully open when the signal is 20 mA Selecting 20 mA will make the valve fully closed when the signal is 20 mA and fully open when the signal is 4 mA 3 Pos Characterization Select Linear if the actuator position should be directly proportional to the input signal Select Optional if anothe...

Страница 12: ...f the calibration switches as described in the previous section AQuick Cal canbeabortedatanytimebybrieflypressing the Quick Cal button and the previous settings will be retained If the Quick calibration switch not to be confused with the Quick Cal button is set to Auto and the valve actuator assembly has the necessary internal stops the calibra tion will complete automatically While the calibratio...

Страница 13: ...mmand signal back in the specified range GYRY 7 Soft Stop Upper The unit is being commanded to exceed a user defined upper travel limit and the internal software is holding the position at the limit To clear the condition use handheld or Flowserve supplied software to reset the limit if more travel is needed or adjust the command signal back in the specified range GRYR 8 Position Lower The position h...

Страница 14: ...ing the Quick Cal button which will force the positioner to use the parameters from the last good calibration YRYR 20 Feedback 0 saturated Calibration error indicating that the position sensor was out of range during the calibration To correct the condition adjust the positioner mounting link age or feedback potentiometer to move the position sensor back into range then restart the calibration Thi...

Страница 15: ... pneumatic relay assembly RYRY 29 Hall sensor upper position Check to make sure the air supply is connected This error may be cleared by briefly pushing the Quick Cal button which will force the positioner to use the parameters from the last good calibration If the positioner still does not operate replace the pneumatic relay assembly RRGG 30 1 23v reference Bad electronic assembly replace RRGR 31 ...

Страница 16: ... is picked up by a stroke lever or by a coupling at the actuator connection The lever coupling moves the vane into the slot of the limit switches LS1 or LS2 via shaft The sensors are de signed as a proximity vane type switch The switching function is triggered if a ferromagnetic object vane is inserted between the coils The switching point can be set by adjustment of the vane Installation The limi...

Страница 17: ...it switch unit does not change the Logix 500 dimensions Supply Supply voltage Umax 16Vdc Supply current Imax 52mA Output signal With target 1mA Without target 3mA Short circuit proofed Control characteristics Switching hysteresis 5 1mm STROKE in acc with 20mm STROKE Repeatability 0 05 0 01mm STROKE Ambient temperature sensitivity 1 5 0 3mm 10K Vibration sensitivity 1 at 2g 0 5 500 Hz in accordance...

Страница 18: ...on reading is not what is expected 1 Stem position sensor mounting is off 180 degrees 2 Stroke not calibrated 3 Tight shutoff M P C is active 4 Custom characterization or soft stops active Position is driven fully open or closed and will not respond to com mand 1 Stroke not calibrated 2 Inner loop hall sensor not connected 3 Wrong air action entered in software 4 Actuator tubing backward 5 Electro...

Страница 19: ... Exploded View Cover Item No 1 Electronic Control Boards Item No 2 E P Piezo Driver Pneumatic Amplifier Relay Unit Item No 3 Feedback Potentiometer Assembly Item No 4 Feedback Gear Shaft Item No 5 Limit Switch Assembly Item No 6 Base Housing Item No 7 Follower Item No 8 Follower arm ...

Страница 20: ...tinually improving and upgrading its product design the specifications dimensions and information contained herein are subject to change without notice Should any question arise concerning these provisions the purchaser user should contact Flowserve Corporation at any of its worldwide operations or offices For more information contact For more information about Flowserve and its products contact w...

Отзывы: