Limitorque L120-85 Installation, Operation and Maintenance FCD LMENIM1202-03-A4 – 06/15
22
4. Remove the Mechanical Dial Position Indicator Plate and flip over for indication of CCW
rotation to the valve’s CLOSED position.
See figure 13 for MDPI Dial Plate.
5. Reverse the OPEN/CLOSE directional arrow on the Handwheel.
4.5 Position Indication
The MDPI is used to indicate the current position of the valve or other actuated devices. Adjustments must be done after mounting the
actuator on the application. If your supplier has not set the MDPI or your application has changed and requires resetting, use the following
procedure to complete the MDPI settings.
c
WARNING:
Hazardous Voltage. Turn power OFF before opening the Electrical Compartment Cover, calibrating the MDPI or
installing the Remote Voltmeter Indicator.
4.5.1 Local Position Indication
1. Turn OFF all power to the actuator.
2. Manually position the valve in the fully CLOSED position.
3. Loosen the Round Head Machine Screw (piece 523) on the MDPI Pointer (piece 522).
Figure 13: Aligning MDPI Pointer for Fully CLOSED Position
#523 Round
Head
Machine
Screw
#522 MDPI
Pointer
MDPI
Dia
l
Plate
4. Move the MDPI Pointer to the (CLOSED) position.
NOTE:
If your application uses CW
Handwheel rotation to OPEN, flip the MDPI Plate over to properly orient the OPEN and
CLOSED position on the MDPI Plate.
5. Tighten the Round Head Machine Screw on the MDPI Pointer.
4.5.2 Remote Position Indication
c
WARNING:
Hazardous Voltage. Use extreme caution if the power is ON and Electrical Compartment Cover is open or removed.
NOTE:
Typical voltmeter remote indicators furnished by Limitorque are built to accept a maximum of 10 volts. In order to make
voltmeter adjustments, you will need a separate voltmeter with a scale suitable for the maximum incoming control voltage.