LI5X Process & Temperature Meter Instruction Manual
49
Entering the correct four-digit number sets the password to 0000, dis-
abling the protection.
Changes to the programmed parameter settings are allowed only with
the password set to 0000.
If the password entered is incorrect, the meter displays
LoCd
(Locked)
for about two seconds, then it returns to Run Mode. To try again, press
Enter/Ack
while the
Locked
message is displayed.
Forgot the Password?
The password may be disabled by the following
procedure:
1.
Note display reading prior to pressing the Menu
button. Ignore decimal point and sign.
2. Access
the
Password
menu, add 2 to the noted
reading and enter that number as the password
(e.g. display reading = -1.23, password = 0125).