LI5X Process & Temperature Meter Instruction Manual
66
Reset Meter to Factory Defaults
When the parameters have been changed in a way that is difficult to
determine what’s happening, it might be better to start the setup proc-
ess from the factory defaults.
Instructions to load factory defaults:
1. Enter
the
Advanced
features menu. See
Advanced Features Menu
,
page 50.
2. Press
Up
arrow to go to
Diagnostics
menu
3. Press and hold
Right
arrow/Reset for five seconds, press
Enter/Ack
when display flashes
reset
.
Note: If
Enter/Ack
is not pressed within three seconds, display re-
turns to
Diagnostics
menu.
4. The meter goes through an initialization sequence (same as on
power-up), and loads the factory default settings.
rset
diag
Press and Hold for 3 Sec
Meter Re-
Initializes
Press and Hold
for 5 Sec
Flashing