Error
no.
Error
message
Error / Name
Effect / Action
holding/
subject to
mandatory
acknowledgement
23
Top-up
inadmissible
Top-up without request (IWZ
delivers signals without supply)
Top-up off / check motor ball valve for leaks
for top-up.
YES
24
Top-up interval
↓
minimum top-up cycle interval
undershot
Top-up of / correct defaults if necessary;
exclude pipe burst.
YES
25
Top-up
number
↑
maximum number of cycles
within a time window exceeded
Top-up of / correct defaults if necessary;
exclude pipe burst.
YES
26
Top-up
volume
↑
Maximum volume exceeded in a
top-up cycle (with IWZ)
Top-up of / correct defaults if necessary;
exclude pipe burst.
YES
27
Top-up time
↑
Maximum time for top-up cycle
exceeded (without IWZ)
Top-up of / correct defaults if necessary;
exclude pipe burst.
YES
31
v 3
↑
Water treatment module
processing amount exceeded
Top-up off / correct defaults if necessary;
replace treatment module.
YES
35
Temp
controller
Pressure controller faulty
Fault shutdown - target pressure in vessel
not reached / contact service.
Possibility of a contaminated filter.
YES
37
P output
Discharge pressure not reached
within the "maximum duration
for waiting for ejection pressure
cycle end to be reached"
Fault shutdown - target pressure in vessel
not reached / contact service.
Possibility of a contaminated filter.
YES
39
Pa max
↑
Pa max exceeded
Fault shutdown / Reduce pressure to within
the working pressure range.
YES
41
Adjust psys
Adjust system pressure fault
Motor shutdown / Ensure inlet pressure from
the system.
YES
42
No
characteristic
curve
No valid degassing characteristic
curve
No valid degassing characteristic curve.
YES
55
v 1
↑
Water treatment module
processing amount warning
threshold 1
No / Prepare module replacement.
(consumption at 70%)
YES
56
Maintenance
1!
Next maintenance type 1 is
pending
No / Perform maintenance 1.
YES
57
Maintenance
2!
Next maintenance type 2 is
pending
No / Perform maintenance 2.
YES
60
Extension
Last external module action with
errors ended
No / repeat action if necessary.
YES
61
v 2
↑
Water treatment module
processing amount warning
threshold 2
No / prepare module replacement
(consumption at 90%) perform module
replacement immediately if necessary.
YES
If any errors other than those described occur and they cause permanent problems (not self-acknowledging), please contact
the service to solve the problem!
Содержание Vacumat Eco 300
Страница 4: ...4 ...
Страница 28: ...28 ...
Страница 52: ...52 ...
Страница 76: ...76 ...
Страница 100: ...100 ...
Страница 124: ...124 ...
Страница 148: ...148 ...
Страница 172: ...172 ...
Страница 196: ...196 ...
Страница 220: ...220 ...
Страница 244: ...244 ...
Страница 268: ...268 ...
Страница 292: ...292 ...
Страница 316: ...316 ...
Страница 340: ...340 ...
Страница 364: ...364 ...