Row
-DENCO
Overview of Units and Packaged Content
FläktGroup DC-2014-0106-GB 2019-02/R3 • Subject to modifications
9
Filters
Regenerable polyester fibre filtering media (G2 efficiency) treated with synthetic resins,
supported by a frame with protective metal mesh. The filtering media is flame retar-
dant.
Air-Sources Heat Exchanger
Finned coil with large frontal surface area, made from mechanically expanded tubes
and aluminium fins with hydrophilic treatment and high heat transfer area. The coil is
placed upstream of the fans for optimum air distribution.
Electrical Ppanel
Built and wired in compliance with IEC 204-1/EN60204-1 standards, complete with fan
contactor and overload protection.
Microprocessor Control System
The microprocessor, by managing the compressor for the direct expansion unit and the
modulating 3-way valve for the water chiller, controls cooling capacity and operating
alarms, with the possibility of connection to supervisory systems.
Immersed Electrode Humidifier (optional)
Modulating steam production and automatic control of salt concentration in the water
tank to allow the use of untreated water.
3.2.2 Outdoor condensing unit
Description of the DROU unit
For direct expansion versions, the DROU outdoor condensing unit combined with the
DRX indoor unit, is aircooled with axial-flow fans, fitted with INVERTER-DRIVEN HER-
METIC SCROLL compressor for operation on R-410A refrigerant, mounted on rubber
vibration dampers, complete with oil pre-charge, supplied with oil separator to ensure
correct lubrication even at minimum speed, and fitted with thermal protector.
Structure
Powder coated metal plate base panelling and inside structure. Non-flammable closed
cell polyethylene foam thermal insulation and soundproofing on the inside.
Inverter-Driven compressors
High efficiency hermetic scroll compressor with brushless DC motor, complete with
thermal protector, with electronic capacity control managed by INVERTER. This ensu-
res unit operating efficiency even at part loads, which represent more than 75 % of nor-
mal operating time, meaning effective overall average energy savings of up to 50 %
compared to traditional ON/OFF technology. Mounted on rubber vibration dampers,
complete with sump heater, oil charge and oil separator to prevent migration of the gas
charge and ensure lubrication of the compressor sump during operation at minimum
speed. Complete with thermal protector and sump heater installed as standard on all
versions.
Electrical panel
Power and control electrical panel constructed in accordance with IEC 204-1/
EN60204-1, complete with control and terminal blocks for connection to the power sup-
ply and auxiliary controls.
Protection grille
The unit comes with a protection grill on the condenser coil.
Содержание Row-DENCO DRC 020
Страница 1: ...Row DENCO OPERATION MANUAL ...