Troubleshooting
Row
-DENCO
78
FläktGroup DC-2014-0106-GB 2019-02/R3 • Subject to modifications
Insufficient air flow-rate
See “LOW OR NO AIR FLOW”.
FAULT
CAUSE
FAULT
HEATER SAFETY THERMO-
STAT ACTIVATED
Thermostat connection wire cut or broken
Faulty thermostat
Check the continuity of the connection from the safety
thermostat to the control system.
Replace the heater safety thermostat.
HIGH COMPRESSOR
DISCHARGE PRESSURE
A) Air or incondensable gas in the refrigerant Empty and
recharge the circuit. circuit, seen by the presence of bub-
bles, despite measuring a high subcooling.
B) Insufficient air flow-rate to the remote heat exchanger
or air too hot
Insufficient water flow-rate to the condenser or water too
hot.
Excessive refrigerant charge; condenser partially floo-
ded. Excessive subcooling of the liquid at the condenser
outlet.
Valves on the high pressure side of the circuit partially
closed.
The condensing pressure control system isn't working.
HIGH PRESSURE SWITCH
ACTIVATED
(high compressor discharge pres-
sure)
Empty and recharge the circuit.
Check the operation and the correct direction of rotation
of the fans on the outdoor heat exchanger.
Check that the exchanger is not dirty and remove any
material that may be blocking it (leaves, paper, seeds,
dust, etc.) with a jet of compressed air or with a brush;
Check the outdoor unit for any obstacles to the flow of air
and any recirculation of the cooling air;
Check that the temperature of the cooling air does not
exceed the design value.
Check the flow-rate, the pressure and the temperature of
the cooling water in the closed circuit;
Check the calibration and the operation of the pressure
control valve.
Remove refrigerant from the circuit.
Check the opening of the valves.
Check the operation of the condenser fans and the cor-
responding protection device; repair or replace the faulty
fans;
Check the calibration and the operation of the remote
condenser fan pressure switch or the speed controller.
(See CONTROLLING THE CONDENSING PRES-
SURE)
The system is affected by an excessive discharge pres-
sure
See “HIGH COMPRESSOR DISCHARGE PRESSURE”.