Troubleshooting
FläktGroup DC-2014-0106-GB 2019-02/R3 • Subject to modifications
79
The condensing pressure control system isn't working
(see the control panel manual).
Check the calibration and the operation of the conden-
ser fan pressure switch or the speed controller;
FAULT
CAUSE
FAULT
LOW COMPRESSOR
DISCHARGE PRESSURE
Excessive water flow-rate to the condenser or water too
cold.
Check the temperature of the cooling water.
Check the calibration and the operation of the pressure
control valve (if fitted).
Install a pressure control valve to manage the flow-rate
of water according to the condensing pressure.
HIGH COMPRESSOR
SUCTION PRESSURE
Suction pressure too low
Thermal load higher than expected
The system is affected by an excessive discharge pres-
sure
Too much refrigerant in the circuit.
Return of liquid refrigerant to the compressor intake
LOW COMPRESSOR SUCTION
PRESSURE
(and possible defrosting of the
coil)
Check the ambient thermal load; check, above all for
intense dehumidification, the flow-rate and the conditi-
ons of the outside air; check the inflow of outside air.
See “LOW COMPRESSOR SUCTION PRESSURE”.
See “HIGH COMPRESSOR DISCHARGE PRES-
SURE”.
Remove refrigerant from the circuit
Check that the thermostatic valve superheating value is
correct; check that the valve sensor bulb is not dischar-
ged and that it is correctly positioned, secured and insu-
lated”.
Room temperature too low
See “ROOM TEMPERATURE TOO LOW”.
The air flow-rate is too low or null
See “LOW OR NO AIR FLOW”.
Liquid receiver outlet valve not completely open
Check the opening of the valve.
Refrigerant filter blocked
Check that the thermostatic valve superheating value is
correct; check that the valve sensor bulb is not dischar-
ged and that it is correctly positioned, secured and insu-
lated”.
Insufficient refrigerant charge
Check the liquid subcooling at the condenser outlet; if
necessary, restore the charge.
Thermostatic valve not correctly calibrated or faulty
Check that the thermostatic valve superheating value is
correct (around 5 °C).
Dewatering filter cartridge dirty
Check and if necessary replace the dewatering filter
cartridge; the temperature difference measured
upstream and downstream of the filter must be less
than 2 °C.
The system is affected by an excessively low discharge
pressure
See “LOW COMPRESSOR DISCHARGE PRES-
SURE”.
LOW PRESSURE SWITCH
ACTIVATED
(low compressor suction pres-
sure)