TopMaster Air Handling unit
CONTROL AND REGULATION EQUIPMENT
1) R/W = Read and write value, R = Read only value
Parameter
Type of value
1)
Range
Unit
Default value Comments
8.
Configuration
8.1 IP address
Static = IP address is manually set.
Static/Dynamic
R/W
Static/Dynamic
Dynamic
Dynamic = IP-address is automa-
tically set via DHCP.
IP- address
Subnet mask
8.2 Menu configuration
Logon to USB
R/W
Yes/No
No
Is set to Yes for copying the log
files to the USB memory.
Unit type
L
TopMaster
Auto logout
R/W
0
–
32767
min
10
Time before automatic logout
occurs in the control panel.
Thresholds
Not used in Topmaster.
8.3 Screen saver
Screen saver
R/W
Yes / No
Yes
Time
R/W
min
10
Time before the screen saver is
activated in the control panel.
8.4 Modbus
Sea also the Modbus manual.
Address BMS
R/W
2
Baud rate
R/W
9600, 19200,
9600
38400
Parity
R/W
none, odd, even
none
Data bit
R/W
7,8
8
Stop bit
R/W
1,2
1
8.5 MAC address
MAC address
L
Displays the network card
MAC address.
8.7 Password
Automatic logout
R/W
Yes/No
Yes
Password 1
R/W
0000-9999
0000
The password can be changed. If
passcode is forgotten, Fläkt
Woods must be contacted.
8.8 About
Software HMI
L
Displays the current software
version of the control panel.
Software Control card
L
Displays the current software
of the control card.
9. Save values
Store the set values in the control
panel (to copy to another unit).
10.Uploading values
Uploading saved values to unit.
11. Save to SD
Stored values can be saved in SD
card, this requires that the values
have already been saved in menu 9.
12.Load from SD
Stored values may be loaded from
the SD card.
13. Log out
Parameter list (cont.)