Fläkt Woods
8217 GB 2014.07.02 24
Specifications are subject to alteration without notice
TopMaster Air Handling unit
CONTROL AND REGULATION EQUIPMENT
Parameter list (cont.)
Parameter
Type of value
1)
Range
Unit
Default value Comments
2. Commissioning Wizard
See page 16
3. Timer functions
See page 5.
Timer function
R/W
1
–
5 2
Timer off delay
R/W
0
–
999 min
0
4.
Fans
4.1 Speed of fans
Commissioning of fans is done in
menu
2, Commissioning Wizard.
Automatic return to the previous
Auto Stop forced mode
R/W
Yes/No
No
operating mode in the choice of
high
speed.
Forcing time
R/W
0
–
9999
min
120
Time before return, see above.
Start delay
R/W
0
–
32767
s
10
During this time SF and rotor run.
Off delay
R/W
0
–
32767
s
0
After cooling, set to 180 s at
electric
heater.
Pressure/Flow control of fans
4.2 Pressure / Flow
The unit must be equipped with
pressure sensors. See page xx.
If pressure control
Pressure control supply air
R/W
Yes/No
Yes
Pressure control extract air
R/W
Yes/No
Yes
Only SF, EF slave
R/W
Yes/No
No
Proportion SF / EF
R/W
0
–
200
%
100
Only if the above parameter is active.
Supply air pressure setpoint
R/W
0
–
2000 Pa 150
Extract air pressure setpoint
R/W
0
–
2000 Pa 150
If flow control
Flow control supply air
R/W
Yes/No
Yes
Flow control extract air
R/W
Yes/No
Yes
Only SF, EF slave
R/W
Yes/No
No
Proportion SF / EF
R/W
0
–
200
%
100
Only if the above parameter is active.
Supply air flow, low speed
R/W
0
–
9999 l/s
80
Supply air flow, normal speed
R/W
0
–
9999 l/s 100
Supply air flow, high speed
R/W
0
–
9999 l/s 120
Extract air flow, low speed
R/W
0
–
9999 l/s
80
Extract air flow, normal speed
R/W
0
–
9999 l/s 100
Extract air flow, high speed
R/W
0
–
9999 120
5. Heating / Cooling
5.1 Pre-heater
No such function in TopMaster.
5.2 Heating / Cooling
See also pages 20
–
22.
Control mode
R/W
1-2
1
1 = Standard, supply air control
2 = Cascade control.
Cascade reference
R/W
0-1
0
0 = Extract air control
1 = Outdoor air compensation.
Cooling sequence
R/W
Yes/No
No
Cooling sequence activated.
DX-cooling
R/W Yes/No No
Dead zone cooling
R/W
Yes/No
Yes
Dead zone cooling activated.
Dead zone
R/W
0
–
25 °C 2
Block cooling in winter
R/W
Yes/No
Yes
Block heating in summer
R/W
Yes/No
Yes
Post-heater
R/W Yes/No Yes
Absolute/Relative temperature
R/W
abs/rel
rel
Absolute or relative temperature
in schedules.
1) R/W = Read and write value, R = Read only value