Fläkt Woods
8217 GB 2014.07.02 23
Specifications are subject to alteration without notice
TopMaster Air Handling unit
CONTROL AND REGULATION EQUIPMENT
Parameter list
Parameter
Type of value
1)
Range
Unit
Default value Comments
Temperature
status
Setpoint
R/W 15
–
35
°C
18
Desired setpoint.
Actual setpoint for supply air.
Actual setpoint
R
15
–
35
°C
-
Used for extract air control or out-
door temperature compensation.
Supply air
R
-40
–
100
°C
-
Supply air temperature.
Outdoor air
R
-40-100
°C
-
Outdoor air temperature.
Extract / Room
R
-40
–
100
°C
-
Extract air / Room temperature.
Freeze protection
R
-40
–
100
°C
-
Freeze protection temperature.
Fan
status
Supply air fan, speed
R
0 or 30
–
100 %
-
Extract air fan, speed
R
0 or 30
–
100 %
-
Air qual ity
No such function in TopMaster.
Overview
This menu is used for maintenance
and
troubleshooting.
Software version, Control panel
R
-
-
-
Speed, Supply air fan
R
0 or 30
–
100 %
-
Speed, Extract air fan
R
0 or 30
–
100 %
-
Output, Post-heater
E
0
–
100 %
-
Output, Pre-heater
R
-
-
-
No such function in TopMaster.
Output, Heat recovery
R
0
–
100 %
-
Outout, Cooling
R
0
–
100 %
-
Summer/Winter mode
R
Summer/Winter
-
-
Supply air temperature
R
-40
–
100 °C
-
Supply air temperature
R
-40
–
100 °C
-
Extract air temperature
R
-40
–
100 °C
-
“Cold corner” temperature
R
-
-
-
No such function in Topmaster.
Freeze protection temperature
R
-40
–
100
°C
-
Only in case of water heating.
Setpoint set
R/W
15
–
35 °C 18
Operation codes
R
-
-
-
No such function in Topmaster.
Schedules
Only reading, programming of
schedules is done under Settings.
Weekly
1-8
R
Daily
1-4
R
Date period 1-4
R
Settings
Time / Date
R/W
This can also be done directly
from the home page.
Choose language
R/W
English
Login
R/W 0000
–
9999
0000
For installers and service personnel.
Settings
For installers and service personnel.
1. Schedules
See page 17.
Some parameters and functions have a more detailed explanation after the parameter list. The Curo ™ Touch control
panel has a wide range of applications. Only relevant parameters are listed below. It is strongly recommended to avoid
the adjustment of any system parameters that are not outlined in this section.
1) R/W = Read and write value, R = Read only value