- 7 -
CLEARANCE TO COMBUSTIBLES:
TOP
FRONT
SIDES
REAR
FLUE PIPE
3 ft
10 ft
3 ft
3 ft
3 ft
DUCTING:
Hitex heater duct with a minimum temperature handling of
300 deg F. including wire reinforcement to prevent
collapsing. Heater is designed for use with 2 x 12” diameter
ducts equipped with pin lock couplings (FV-HD12)
.
Install ducting to outlet on the heater using pin-locks
provided on collar of ducting. Ducting should be inspected
periodically for tearing and/or wear marks. Ducting should be
stored in a dry area when not in use
FLUE PIPE:
Flue pipe connection must terminate with a vertical run at
least 2 ft long. Horizontal runs should have a rise ratio of 1
in 10 away from the heater. The chimney should have a 0.2”
W.C. draft to ensure safe operation of the unit.
The vent outlet on the heater is 6” diameter. Certified
venting must be used at all times. Vent cap should be
installed in situations where downdrafts occur. All venting
must correspond with the CSA B149 standard or in its
absence, local codes.